Leave Your Message

12kV GN30-12 Indoor Rotary High Voltage Disconnecting Switch from China Suppliers and Factory

,

Product Overview
Introducing the GN30-12 series indoor high-voltage rotary isolation switch, an essential component for electrical systems operating at 12KV with three-phase AC at 50Hz. This isolation switch is designed for indoor use, ensuring reliability and safety in various applications. Manufactured in China, our factory is committed to producing high-quality isolation switches that meet international standards. As a leading supplier in the industry, we prioritize durability and performance, making our products ideal for power distribution and management solutions.

,

    Normal Work Environment
    a.
    Altitude not exceeding 1000m (ordinary type, large climbing distance);
    b.
    The ambient temperature shall not exceed +40℃; Not lower than -10℃;
    c.
    The monthly average relative humidity is not greater than 90%.
    1.2 Isolation switches are not suitable for:
    a.
    Places with gases, water vapor, chemical deposits, salt spray dust, dirt, and explosive and corrosive substances that seriously affect the insulation and conductivity of isolation switches.
    b.
    Places with frequent and intense vibrations.
    Structural Characteristics
    GN30-12/630, 1000, 1250, 2000, 3150 type isolation switch is a new type of rotary knife type isolation switch. The switch body is fixed on the upper and lower planes of the switch chassis through two sets of insulators, and the upper and lower planes are completely separated by a partition fixed on the switch chassis. The switch is closed and opened by rotating the contact knife.
    GN30-12D/630, 1000, 1250, 2000, and 3150 type isolating switches are in the form of adding a grounding knife on the basis of the original switch, which can meet different requirements of the switchgear. The contacts are installed on the upper and lower surfaces of the switch, completely separating the live and non live parts inside the switch cabinet, ensuring absolute safety for workers during maintenance. The conductive part is mainly composed of a contact blade and a contact head. The contact blade is fixed inside the rotating ceramic sleeve by two copper plates, and an external magnetic lock plate is added to enhance the rigidity of the contact blade. The high current conductive parts above 2000A are mainly composed of conductive tubes, contact fingers, and contact seats cast with epoxy resin. The touch finger is fixed on the contact seat from both sides, and spring pressure is applied to make the contact more reliable, so that it has good dynamic and thermal stability when passing through short-circuit current.
    The contact method between the GN30-12/630, 1000, and 1250A contact blades and the contacts adopts curved line contact. The contact method between the GN30-12/2000 and 3150 contact fingers and the contact seat adopts spherical line contact, and the conductive tube and contact fingers adopt line contact to reduce the process difficulty during assembly and ensure good contact.
    Ordering Information
    5.1
    When placing an order, it is necessary to specify in detail the product model and whether a mechanism is required.
    5.2
    If there are special requirements, please indicate and attach drawings.
    5.3
    Incoming and outgoing lines: The wiring terminal is perpendicular to the installation surface of the switch chassis as a vertical incoming and outgoing line, and parallel to the plane of the chassis as a horizontal incoming and outgoing line.
    5.4
    Operation direction: Facing the front of the switchgear, the operating mechanism should be operated on the left for left operation and on the right for right operation (all the figures listed in this manual are operated on the left).
    Frequently Asked Questions (FAQ)
    What is the maximum altitude and ambient temperature for normal operation?
    The altitude should not exceed 1000m. The ambient temperature must remain between -10℃ and +40℃.
    Where should isolation switches NOT be installed?
    They are not suitable for places with frequent and intense vibrations, or areas containing gases, water vapor, chemical deposits, salt spray dust, dirt, explosive, and corrosive substances.
    What distinguishes the GN30-12D series from the standard GN30-12 series?
    The GN30-12D series includes an additional grounding knife based on the original switch design, which can meet different requirements of the switchgear.
    How does the switch design ensure safety during maintenance?
    The contacts are installed on the upper and lower surfaces, completely separating the live and non-live parts inside the switch cabinet, which ensures absolute safety for workers during maintenance.
    What specific details must be provided when placing an order?
    You need to specify the product model, whether a mechanism is required, the operation direction (left or right), incoming/outgoing line preferences, and provide drawings for any special requirements.
    How is the contact method designed to ensure reliability?
    It uses curved line contact for 630-1250A models, and spherical line contact for 2000-3150A models. This reduces assembly process difficulty, ensures good contact, and maintains dynamic and thermal stability.