Leave Your Message

6-10kv Series Oil Immersed Distribution Transformer

Application
This type of transformer adopts high-permedibility cool-rolling si-steel piece as iron core. lt is processed with big fill factor and there is no spacing inside the mangnetic path. The HV and LV coil is continuously winded around the core with good concentricity and compact winding. The product is of low con-sumption and slight noise pollution by combining new generation of technolgy good performance and energy saving. lt is widely used in power distribution system.

    Product Fectures

    1.Our company's improved oil immersed distribution transformer iron core is made of imported high-quality cold-rolled silicon steel sheets stacked together, greatly reducing no-load losses and no-load currents. The iron core is tied to ensure its compactness and reduce noise.
    2.The transformer connection group adopts the Dyn11 wiring method to reduce the impact of harmonics on the power grid and improve the quality of power supply.
    3.The transformer is a fully sealed structure that extends its service life, eliminates the need for hanging cores, and requires no maintenance.
    4.The high and low voltage windings are made of oxygen free copper. For low voltage windings of 500kVA and below, a double-layer cylindrical structure is used. For windings of 630kVA and above, a double helix or four helix structure is used. For high voltage windings, a multi-layer cylindrical structure is used
    6-10kV series oil immersed distribution transformer (1)
    6-10kV series oil immersed distribution transformer (2)
    6-10kV series oil immersed distribution transformer (3)

    Transformer Standards

    GB 1094.1-2013: GB 1094.2-2013
    GB 1094.3-2017: GB 1094.5-2008
    GB/T 6451-2015: GB 7595-2017
    GB/T 25289-2010: GB 3837-2016

    Transformer Normal Service Conditions

    The height above the sea level is below 1000m
    Ambient temperature:
    Highest air temperature +40℃
    Highest daily average air temperature +30℃
    Highest annual average air temperature +20℃
    Lowest outdoor air temperature -25℃

    Transformer Special Service Conditions

    The height above the sea level is above 1000m
    Ambient temperature:
    Highest air temperature is above 40℃
    Lowest air temperature Lower than25℃

    Ordering Instructions

    When placing an order, the product model, rated capacity, high and low voltage ratings, high voltage tap range,number of phases, frequency, and connection group number should be provided.

    Transformer Model description

    Transformer Model description (1)
    Transformer Model description (2)
    Transformer Model description (3)

    S11 distribution transformer

    Rated Capacity KW.A Voltage combination and tap range connection group label Loss W No-load current % Impedance Voltage % Weight kg External dimensions L*B*H Track gauge portrait/landscape
    HV kV Tapping range of tigth verttage% LV kV No-load Load 75°℃ Body weight oil Total weight
    30 11 10.5 10 6.3 6 ±5 士2×2.5 0.4 Dyn11 Yzn11 Yyn0 100 630/600 1.5 4.0 135 55 325 680*480*846 550/400
    50 130 910/870 1.3 210 75 435 765*690*876
    63 150 1090/1040 1.2 245 85 490 795*645*915
    80 180 1310/1250 1.2 290 90 550 825*660*925 550/550
    100 200 1580/1500 1.1 315 95 590 810*770*980
    125 240 1890/1800 1.1 365 100 660 825*800*960
    160 280 2310/2200 1.0 440 115 720 1115*735*985
    200 340 2730/2600 1.0 490 160 790 1186*815*1050
    250 400 3200/3050 0.9 600 150 960 1290*860*1050 660/660
    315 480 3830/3650 0.9 710 180 1120 1350*920*1090
    400 570 4520/4300 0.8 920 210 1440 1485*1030*1120
    500 680 5410/5150 0.8 1050 320 1800 1470*1030*1160
    630 Dyn11 Yyn0 810 6200 0.6 4.5 1130 260 1770 1550*1045*1225
    800 980 7500 0.6 1340 290 2060 1730*1220*1285 820/820
    1000 1150 10300 0.6 1440 420 2505 1670*1160*1375
    1250 1360 12000 0.5 1750 480 2970 1750*1240*1425
    1600 1640 14500 0.5 2240 600 3950 1860*1260*1485
    2000 1940 18300 0.4 5.0 2575 635 4305 1990*1315*1620
    2500 2290 21200 0.4 3270 815 5440 2065*1360*1750 1070/1070

    S11 power transformer

    Rated capacity KV.A Voltage combination kV Connection Broup label Loss W No-load current % Impedance Voltage % Weight kg External dimensions L*B Track gauge portrait/landscape
    HV LV No-load Load 75'℃ Body meight oil Total weight
    200 10.5 10 6.3 6 6.3 3.15 3 Yd11 Dy11 340 3150 1.8 4.5 650 160 1000 1180*740*1270 660/660
    250 400 3600 1.7 770 200 1190 1230*780*1340
    315 480 4300 1.6 900 215 1360 1260*810*1370
    400 570 5200 1.5 1080 260 1650 1380*900*1390
    500 630 680 6200 1.4 5.5 1250 280 1890 1400*920*1450
    820 6920 0.6 1470 340 2245 1580*1020*1430 820/820
    800 1000 8460 0.6 1735 385 2645 1665*1070*1520
    1000 1180 9910 0.6 1910 430 2980 1740*1160*1550
    1250 1400 11700 0.5 2210 590 3640 1820*1210*1740
    1600 1680 14100 0.4 2640 680 4270 1840*1240*1860
    2000 2010 16900 0.4 2890 725 4775 2210*1920*1970 1070/1070
    2500 2370 19600 0.4 3460 910 5710 2260*1970*1995
    3150 2800 23000 0.4 4230 1350 7085 2320*2280*2360
    4000 3450 27300 0.4 5025 1675 9150 2460*2480*2475
    5000 10.5 10 6.3 3.15 4100 31300 0.4 6020 1940 9610 2575*2640*2590
    6300 4890 35000 0.4 8125 2550 12660 2640*2820*2810
    8000 6520 40500 0.55 9620 2780 15100 2710*2840*3040 1475/1475
    10000 7700 47700 0.55 11660 3070 17480 2850*2880*3265

    S13 series three-level energy

    Rated capacity KV.A Voltage combination kV Cannection sroup labe Loss W No-load current % Impedance Weight kg External dimensions L*BH Track gauge portrait/landscape
    HV kV Tapping range of highuoltage% LV kV No-load Load 75°℃ Voltage% Body eight oil Tota wight
    30 11 10.5 10 6.3 6 ±5 ±2×2.5 0.4 Dyn11 Yzn11 Yyn0 80 630/600 1.5 4.0 140 70 320 745*555*830 550/400
    50 100 910/870 1.3 205 75 390 775*595*890
    63 110 1090/1040 1.2 240 85 450 790*640*930
    80 130 1310/1250 1.2 290 95 520 857*700*950 550/550
    100 150 1580/1500 1.1 340 100 576 845*720*950
    125 170 1890/1800 1.1 390 110 650 850*770*990
    160 200 2310/2200 1.0 470 150 760 1130*770*1013
    200 240 2730/2600 1.0 540 135 861 1160*780*1160
    250 290 3200/3050 0.9 670 160 1030 1220*810*1111 660/660
    315 340 3830/3650 0.9 750 173 1160 1280*880*1150
    400 410 4520/4300 0.8 910 210 1390 1320*900*1196
    500 480 5410/5150 0.8 1070 230 1650 1420*980*1240
    630 Dyn11 Yyn0 570 6200 0.6 4.5 1310 290 1960 1510*1010*1310
    800 700 7500 0.6 1550 320 2320 1640*1120*1335
    1000 830 10300 0.6 1595 360 2550 1675*1145*1365 820/820
    1250 970 12000 0.5 2110 500 3370 1820*1260*1492
    1600 1170 14500 0.5 2635 600 4190 1940*1300*1625
    2000 1360 18300 0.4 5.0 2700 755 4720 2000*1345*1700
    2500 1600 21200 0.4 3240 835 5460 2030*1360*1900 1070/1070

    S20

    Rated Capacty KW.A Voltage combination and tap range Correction Loss W No-load current % Impedance Voltage % Weight kg External dimensions L*B*H Tradk gauge portraitlandscape
    HV kV Tapping range of highud1300% LV kV group labell No-load Load 75℃ Bady weigh oil Totd weight
    30 11 10.5 10 6.3 6 ±5 ±2×2.5 0.4 Dyn11 Yzn11 Yyn0 70 505/480 1.5 4.0 180 70 370 780*355*860 550/400
    50 90 730/695 1.3 288 85 510 860*365*940
    63 100 870/830 1.2 335 95 590 865*370*960
    80 115 1050/1000 1.2 380 100 650 880*380*1015 550/550
    100 135 1265/1200 1.1 440 115 735 920*580*1020
    125 150 1510/1440 1.1 525 120 850 930*675*1080
    160 180 1850/1760 1.0 630 150 1010 965*680*1160
    200 215 2185/2080 1.0 760 165 1170 1010*750*1180
    250 260 2560/2440 0.9 865 180 1290 1015*750*1190 660/660
    315 305 3065/2920 0.9 1050 210 1560 1095*780*1230
    400 370 3615/3440 0.8 1100 230 1675 1100*900*1260
    500 430 4330/4120 0.8 1420 265 2090 1160*940*1310
    630 510 4960 0.6 1705 300 2450 1250*980*1345
    800 Dyn11 Yyn0 630 6000 0.6 4.5 1895 320 2700 1260*990*1360
    1000 745 8240 0.6 2080 360 3045 1615*1095*1450 820/820
    1250 870 9600 0.5 2550 470 3790 1705*1100*1520
    1600 1050 11600 0.5 2910 575 1340 1800*1145*1700
    2000 1225 14640 0.4 5.0 3525 595 5000 1925*1180*1750
    2500 1440 14840 0.4 4860 690 6490 1945*1230*1990 1070/1070

    S22

    Rated Capacity W.A Voltage combination and tap range Cornection Loss W No-load current % Impedance Voltage % Weight kg External dimensions L*B*H Track gauge portrait/landscape
    HV kv Tapping range of highvokge% LV kV group labef No-load Load 75'℃ Body weight oil Total weight
    30 11 10.5 10 6.3 6 ±5 ±2×2.5 0.4 Dyn11 Yzn11 Yyn0 65 455/430 1.5 4.0 196 65 385 790*345*870 550/400
    50 80 655/625 1.3 320 85 560 845*370*960
    63 90 785/745 1.2 365 90 600 865*380*1000
    80 105 945/900 1.2 430 100 685 895*390*1035 550/550
    100 120 1140/1080 1.1 520 115 810 925*515*1045
    125 135 1360/1295 1.1 590 120 900 945*565*1085
    160 160 1665/1585 1.0 715 150 1075 985*570*1120
    200 190 1970/1870 1.0 895 160 1300 1015*605*1150
    250 230 2300/2195 0.9 985 180 1405 1030*640*1200 660/660
    315 270 2760/2630 0.9 1200 215 1725 1120*750*1245
    400 330 3250/3095 0.8 1280 220 1845 1150*825*1300
    500 385 3900/3710 0.8 1545 240 3150 1205*845*1400
    630 Dyn11 Yyn0 460 4460 0.6 4.5 1890 270 2580 1275*900*1500
    800 560 5400 0.6 2180 335 2990 1365*950*1520 820/820
    1000 665 7415 0.6 2260 400 3255 1430*1050*1550
    1250 780 8640 0.5 2890 470 4060 1480*1075*1590
    1600 940 10440 0.5 3260 510 4600 1520*1115*1725
    2000 1085 13180 0.4 5.0 4070 650 5600 1565*1235*1830
    2500 1280 13360 0.4 5615 670 7195 1680*1290*2110 1070/1070

    SZ13

    Rated Capacty KW.A Voltage combination and tap range Connection group label No load loss W Load loss W No load current% Impedance Voltage %
    HV kV apping range of high volage9 LV kV
    200 250 315 400 500 630 6 6.3 10 10.5 ±4×2.5 0.4 Dyn11 Yyn0 300 2900 1.0 4.0
    350 3420 0.9
    420 4100 0.9
    510 4950 0.8
    600 5890 0.8
    770 7260 0.6 4.5
    800 1000 1250 900 8890 0.6
    1000 10400 0.6
    1250 12300 0.5
    1600 2000 2500 1540 14700 0.5
    1820 18600 0.4 5.0
    2100 21600 0.4

    20kV S11

    Rated capacinyf kV.A Voltage combination and tap range Connection group label No-load loss W Load loss W No-load current % Impedance Voltage %
    HV kV fapping range of high voltage % LV kV
    30 20 ±5 ±2×2.5 0.4 Dyn11 Yzn11 Yyn0 100 690/660 2.1 5.5
    50 130 1010/960 2.0
    63 150 1200/1150 1.9
    80 180 1440/1370 1.8
    100 200 1730/1650 1.6
    125 240 2080/1980 1.5
    160 290 2540/2420 1.4
    200 340 3000/2860 1.3
    250 400 3520/3350 1.2
    315 480 4210/4010 1.1
    400 570 4970/4730 1.0
    500 680 5940/5660 1.0
    630 810 6820 0.9 6.0
    800 980 8250 0.8
    1000 1150 11330 0.7
    1250 1380 13200 0.7
    1600 1660 15950 0.6
    2000 1950 19140 0.6
    2500 2340 22220 0.5

    20kV S12 

    Rated capacty Voltage combination and tap range Connect Group Designation No-load loss W Load loss W No-load current % Impedance Voltage %
    HV kV Tapping range high voltage % LV kV
    30 20 ±5h ±2×2.5 0.4 Dyn11 Yzn11 Yyn0 90 690/660 2.1 5.5
    50 120 1010/960 2.0
    63 140 1200/1150 1.9
    80 160 1440/1370 1.8
    100 180 1730/1650 1.6
    125 220 2080/1980 1.5
    160 260 2540/2420 1.4
    200 310 3000/2860 1.3
    250 360 3520/3350 1.2
    315 430 4210/4010 1.1
    400 510 4970/4730 1.0
    500 610 5940/5660 1.0
    630 730 6820 0.9 6.0
    800 880 8250 0.8
    1000 1030 11330 0.7
    1250 1240 13200 0.7
    1600 1490 15950 0.6
    2000 1750 19140 0.6
    2500 2100 22220 0.5

    Leave Your Message