01
AGCK Type Low Voltage Withdrawable Switchgear
Product Overview and Features
The AGCK low-voltage withdrawable switchgear (hereinafter referred to as the device) is tailored to my country's national conditions and boasts high technical performance indicators, effectively meeting the growing demands of the power market. Furthermore, its design fully considers its competitiveness with existing imported products, resulting in a certain market advantage. It has been widely adopted by power users and has become an indispensable and important piece of equipment in the power system, earning them high recognition and trust. Through continuous technological innovation and optimization, the device has played a significant role in improving the safety, reliability, and economic efficiency of the power system.
This product conforms to the standards: GB7251.12-2013 Low-voltage Complete switchgear, JB/T9661 Low-voltage Withdrawable Complete Switchgear, lEC60439-1 Low-voltage Complete Switchgear and Control Equipment.
Model Meaning

Areas of application and environments of use
Suitable for power plants, petroleum, chemical, metallurgy,textile, high-rise buildings and other industries in the power distribution system,in large power plants, petro chemical systems and other high degree of automation, the requirements of the interface with the computer place, as a three-phase AC frequency of 50 (60) HZ, the rated operating voltage of 380 (400)V, insulation voltage (660 V), the rated current for the generation of 4,000 A and the following power, power supply system in the distribution, centralized control of motors, reactive power compensation of the use of low-voltage power distribution equipment.
1. The surrounding air temperature: the maximum temperature of +40℃, the lowest temperature -5 ℃; 24-hour average temperature shall not be higher than +35 ℃:
2. The surrounding air relative humidity in the maximum temperature of +40 ℃does not exceed 50%, in the lower temperature allows a greater relative humidity, such as +20℃ for 90%, should be taken into account due to changes in temperature may be occasional frost effects;
3.Altitude: indoor use of the location shall not exceed 2000m;
4. The inclination of the device to the vertical plane when it is installed shall not exceed 5%;
5. The device should be installed in the absence of severe vibration and shock and not enough to make the electrical components subject to undue corrosion of the place.
Main technical parameters
| Name | Parameters |
| Rated insulation voltage | AC690V |
| Rated working voltage | AC380V(AC400V) |
| Horizontal busbar rated current | 1250A,1600A,2000A,3200A,4000A |
| Vertical busbar rated current | 1000A |
| Maximum current of feeder circuit | 2500A |
| Maximum current of drawer circuit | 630A |
| Maximum capacity of control motor | 320kW |
| Rated frequency | 50Hz |
| Horizontal busbar peak withstand current | 105kA, 176kA |
| Horizontal busbar short-time withstand current (1s) | 50kA, 80kA |
| Vertical busbar peak withstand current | 63kA, 105kA |
| Vertical busbar short-time withstand current(1s) | 30kA, 50kA |
| Rated frequency withstand voltage(1min) | 2500V |
| Secondary frequency withstand voltage(1min) | 2500V |
| SheⅡ protection grade | IP40 |
| SheⅡ size(mm) | W600(800, 1000)xD800(1000)xH2200 |
| Effective height of functional unit(mm) | 1800 |