01
AGCS Type Low Voltage Withdrawable Switchgear
Product Overview and Features
AGCS type Low-voltage withdrawable switchgear, (hereinafter referred to as the device) is a low-voltage withdrawable switchgear designed and developed by the joint design group of the two ministries according to the requirements of the competent authorities of the industry, the majority of electric power users and the design units, which conforms to the national conditions, has high technical performance indexes, and is able to meet the needs of the development of electric power market and to compete with the existing introduced products, and the device has been widely selected by the electric power users at present.
In power plants, AGCS switchgear can effectively manage and distribute the electrical energy generated during the power generation process, ensuring stable power output; in the petroleum and chemical industries, it can cope with extreme environments such as high temperature and high pressure to ensure the normal operation of equipment; in the metallurgical and textile industries, AGCS switchgear provides flexible power solutions to meet the diverse needs of production lines; and in high-rise buildings, it is an important component in ensuring the security of power supply.


The AGCS low-voltage withdrawable switchgear exhibits excellent compatibility, seamlessly integrating with existing power equipment and systems to enhance the efficiency and reliability of the overall power distribution system. With its superior performance and wide applicability, the AGCS switchgear has been widely adopted and recognized across various industries, becoming an indispensable component of modern power distribution systems.
This product conforms to the standards: GB7251.12-2013 Low-voltage Complete Switchgear, JB/T9661 Low-voltage Withdrawable Complete Switchgear, lEC60439-1 Low-voltage Complete Switchgear and Control Equipment.
Model Meaning

Areas of application and environments of use
Suitable for power plants, petroleum, chemical, metallurgy.textile, high-rise buildings and other industries in the power distribution system,in large power plants,petrochemical systems and other high degree of automation,the requirements of the place of interface with the computer, as a three-phase AC frequency of50(60)HZ,the rated operating voltage of 380(400)V,insulation voltage(660 V),the rated current for the generation of 4,000 A and the following power; power supply system in the distribution, centralized control of motors, reactive power compensation of the use of low-voltage power distribution units.
1. The surrounding air temperature: the maximum temperature of +40℃, the lowest temperature -5 ℃; 24-hour average temperature shall not be higher than +35 ℃:
2. The surrounding air relative humidity in the maximum temperature of +40 ℃does not exceed 50%, in the lower temperature allows a greater relative humidity, such as +20℃ for 90%, should be taken into account due to changes in temperature may be occasional frost effects;
3.Altitude: indoor use of the location shall not exceed 2000m;
4. The inclination of the device to the vertical plane when it is installed shall not exceed 5%;
5. The device should be installed in the absence of severe vibration and shock and not enough to make the electrical components subject to undue corrosion of the place.
Main technical parameters
| Name | Parameters |
| Rated insulation voltage | AC660 |
| Rated working voltage | AC380V(AC400) |
| Horizontal busbar rated current | ≤4000A |
| Vertical busbar rated current | 1000A |
| Maximum current of drawer circuit | 400A |
| Rated frequency | 50(60) |
| Horizontal busbar peak withstand current | 105,176 |
| Horizontal busbar short-time withstand current (1s) | 50,80 |
| Vertical busbar peak withstand current | 105 |
| Horizontal busbar short-time withstand current (1s) | 50 |
| Rated frequency withstand voltage(1min) | 2500 |
| Secondary frequency withstand voltage(1min) | 2500 |
| Shell protection grade | IP40 |
| Shell size(mm) | W600(800,1000)xD800(1000)xH2200 |
| Effective height of functional unit(mm) | 1760 |