01
AGN Solid State Cabinet
Product Overview and Features
AGN-12 series solid insulated ring network switchgear is a new generation of environmentally friendly composite insulated ring network cabinet developed by our company. lt is mainly composed of three parts, namely unit v (circuit breaker unit), unit c (load switch unit, unit f (combined electrical unit, each unit can be used separately or can be expanded freely, and its structure is divided into intelligent control instrument room, operating mechanism and primary part, the instrument room can be equipped with microcomputer protection (controller, and the primary part adopts the APG auto-gelding process, which seals the disconnecting switches and interrupting chambers into epoxy resin and has special connectors to connect with the busbar.


The primary part adopts APG automatic gelation process to completely seal the disconnecting switch and the interrupter in epoxy resin, and has a special connector to connect with the busbar. The interrupters are made of special copper-chromium contact material, R-type longitudinal magnetic field contacts and a complete primary sealing process. The interrupters' short-circuit current breaking capacity, stability.electric life, temperature rise and insulation level are significantly higher than those of the previous interrupters (copper-aluminum contact material,cup-shaped longitudinal magnetic field contact structure, and incomplete primary sealing process).
The actuating mechanism adopts the pop-up actuating mechanism integrated with the switch, i.e. the popup actuating mechanism of the disconnecting switch and the main switch is a whole,which can realize interlocking conveniently, and there are fewer parts in the mechanism, which reduces the unnecessary transmission links, and the reliability is high, and the electric operation can be realized according to the user's needs.
Model Meaning

Areas of application and environments of use
The Ring Unit is suitable for 12kV, 50Hz three-phase AC power distribution system, used for ring power supply or terminal power supply.It can be installed in the power distribution system of industrial and mining enterprises,residential districts, schools, parks, etc.lt can also be installed in compact box-type substations for the control and protection of distribution transformers. Therefore, both indoor and outdoor ring units can realize power distribution automation.
Altitude≤4000 meters (please specify when the altitude of equipment operation is higher than 1000m).
Adapt to the ambient temperature -40℃~+50℃, 24h
Average temperature does not exceed 35℃
Air relative humidity 95%(+25℃)
Groundinclination≤5 °
Seismicintensity: no more than 8 degrees.
Main technical parameters
| Name | Unit | Load switch | Combined electrics | Circuit breaker | |
| Rated voltage | kV | 12 | 12 | 12 | |
| Rated frequency | Hz | 50 | 50 | 50 | |
| Rated current | A | 630 | Depends on fuse current rating | 630 | |
| Rated insulation level | Frequency withstand voltage (phase-to-phase and phase-to-ground) | kV | 42 | 42 | 42 |
| Frequency Withstand Voltage (isolation) | kV | 48 | 48 | 48 | |
| Industrial frequency withstand voltage (control and auxiliary circuits) | kV | 2 | 2 | 2 | |
| Lightning impulse withstand voltage (phase-to-phase and phase-to-ground) | kV | 75 | 75 | 75 | |
| Lightning Impulse Withstand Voltage (isolated circuit) | kV | 85 | 85 | 85 | |
| Rated short-time withstand current | kA | 25 | - | 25 | |
| Rated peak withstand current | kA | 63 | - | 63 | |
| Rated short-circuit closing current | kA | 63 | Limited by high voltage fuses | 63 | |
| Rated short-circuit breaking current | kA | - | Limited by high voltage fuses | 25 | |
| Rated transfer current | A | - | 3150 | - | |
| Rated active load breaking current | A | 630 | - | - | |
| Rated closed loop breaking current | A | 630 | - | 630 | |
| Mechanical life | Load switches/circuit breakers | time | 5000 | 5000 | 10000 |
| Disconnect/Earth Switch | time | 3000 | 3000 | 3000 | |
| Main circuit resistance | μQ | ≤150 | ≤300 | ≤150 | |