01
AHN-12 Medium Voltage Ring Network Switchgear
Product Overview and Features
The AHN-12 environmentally friendly medium-voltage ring main switchgear is a new, advanced, green metal-enclosed switchgear designed to meet the environmental and sustainable development requirements of modern power systems. The materials used in its manufacturing process are non-toxic and harmless, ensuring environmental friendliness during production, use, and disposal. Compared to traditional switchgear, the AHN-12 utilizes nitrogen or dry air as its insulating medium, which not only effectively reduces greenhouse gas emissions but also significantly minimizes negative environmental impacts, demonstrating its significant environmental advantages.

During operation, the AHN-12 switchgear emits no toxic or hazardous substances, ensuring the safety of operators and the surrounding environment. This feature makes the AHN-12 particularly suitable for use in environmentally sensitive locations, such as city centers, schools, hospitals, and other public facilities. Furthermore, the equipment's materials are recyclable at the end of their lifecycle, further enhancing its environmental friendliness and aligning with current societal initiatives promoting resource recycling.

The AHN-12 environmentally friendly medium-voltage ring main switchgear not only achieves technological innovation but also embodies a commitment to sustainable development in its design philosophy. Its compact structure and stable performance effectively meet the demands of medium-voltage distribution systems and are suitable for a variety of complex power environments. By utilizing environmentally friendly materials and advanced insulation technology, the AHN-12 provides users with a safe, reliable, and environmentally friendly power solution, helping to build a green power network and promote sustainable development in the power industry.The environmentally friendly gas insulated ring network cabinet is suitable for industrial and civil cable ring network and distribution network terminal project.
Model Meaning

Areas of application and environments of use
As the acceptance and distribution of electric energy, it is especially suitable for power distribution in urban residential areas,small secondary substations, open and close houses,cable branch boxes, box-type substations, industrial and mining enterprises,shopping malls,airports,subways,wind power generation, stadiums, railroads, tunnels and other places to use.
Ambient temperature: upper limit +55℃, lower limit -40℃.
Altitude: no more than 3000m;
Relative humidity: daily average value ≤95%, monthly average value ≤90%
Water vapor pressure: daily average value ≤2.2kPa; monthly average value ≤1.8kPa.
Workplace: the surrounding air is not obviously subject to dust, smoke,corrosive and/or combustible gases, vapors or salt spray pollution; no firehouse explosion, serious filth, serious chemical corrosion and severe vibration.
The amplitude of electromagnetic interference induced in the secondary system ≤ 1.6kV.
Note: Altitude greater than 3000m or special use conditions require customized product solutions.
Main technical parameters
| Name | Unit | Load switch | Circuit breaker |
| Ring Network Cabinet Technical Parameters | |||
| Rated Voltage | KV | 12 | 12 |
| Rated current | A | 630 | 630 |
| Rated Frequency | Hz | 50 | 50 |
| Rated short-circuit breaking current | KA | 25 | 25 |
| Rated closing current (peak) | KA | 63 | 63 |
| Rated short-time frequency withstand voltage (phase-to-phase,relative ground/outlet) | KV | 42/48 | 42/48 |
| Rated lightning impulse withstand voltage (phase-to-phase, relative ground/outllet) | KV | 75/85 | 75/85 |
| Rated operation program | O-0.3S-CO-180S-CO | / | |
| Rated short-time withstand current/duration | KA/S | 25/4s | 25/4s |
| Rated peak withstand current | KA | 63 | 63 |
| Rated active load breaking current1 Rated closed loop breaking current | A | / | 630 |
| Rated cable charging breaking current(CC2) | A | 25 | 25 |
| 5% rated active load current | A | / | 31.5 |
| Main circuit resistance | μQ | ≤140 | ≤140 |
| Mechanical life (circuit breaker,load switch/isolation/earthing) | 次 | 20000/5000/3000 | 10000/5000/3000 |
| Insulation Gas | Nitrogen or dry air | Nitrogen or dry air | |
| Annual air leakage rate | %/year | ≤0.01 | ≤0.01 |
| Rated filling pressure(abs20℃) | Mpa | 0.02 | 0.02 |
| Protection class (cabinet/gas box) | IP41/IP67 | IP41/IP67 | |
| Dimension(WxDxH) | mm | 420x850x2000 | 420x850x2000 |
| Switching Mechanical Characteristics | |||
| Rated Current | A | 630 | 630 |
| Rated short-circuit breaking current | KA | 25 | 25 |
| Contact opening distance | mm | 9±1 | 9±1 |
| Contact overtravel | mm | 3.5±0.5 | 3.5±0.5 |
| Rated contact pressure | N | 1640±160 | 740±160 |
| Contact closing bounce time | ms | ≤2ms | ≤2ms |
| Closing and breaking non-simultaneity | ms | ≤2ms | ≤2ms |
| Average opening speed | m/s | 1.1±0.2 | 1.1±0.2 |
| Average closing speed | m/s | 0.6±0.2 | 0.6±0.2 |
| Closing time | ms | ≤80 | ≤80 |
| Breaking time | ms | ≤50 | ≤50 |