01
FZ(R)N25-12 Indoor AC High Voltage Vacuum Load Switch
Application
FZN25-12D/T630-20 Type Indoor AC switch is three-phase AC 50Hz, rated voltage of 12kV and indoor installations, for industrial and mining enterprises for distribution in clinics and substation sand other occasions, as electrical protection and control facilities for the division and load current, loop current, no load transformer and cable charging current.
FZRN25-12D/T200-31.5 type indoor AC high voltage vacuum load switch- fuse combination units is three-phase AC 50Hz, rated voltage of 12kV for indoor installations for industrial and mining enterprises and other occasions to change the station distribution institution for load control and short circuit protection purposes. Equipped with grounding switch can withstand short-circuit current. Actuator can be manual and electric, easy remote control three power system requirements.
The FZN25-12D and FZRN25-12D three-phase load switches and combination switches are essential components of modern power systems, widely used in urban distribution networks and three-phase ring networks or terminal power supply systems for industrial equipment. These devices not only effectively control loads but also provide excellent short-circuit protection, ensuring the safety and stability of power systems.


Compared to traditional circuits, switchgear and combination devices offer greater reliability and cost-effectiveness in protecting transformers and other electrical equipment. This makes them an ideal choice for various power supply modes, particularly in ring networks, dual-radial power supply units, and box-type substations. By optimizing power distribution and improving equipment efficiency, the FZN25-12D and FZRN25-12D switchgear and combination devices not only enhance the overall performance of power systems but also provide users with a safer and more stable power environment.
These devices are designed with the demands of modern power systems in mind, offering excellent compatibility and scalability to adapt to power applications of varying sizes and types. Whether in a city's high-density power distribution network or in the complex power consumption environments of an industrial park, the FZN25-12D and FZRN25-12D switchgear and combination devices can leverage their unique advantages to provide a strong guarantee for a reliable power supply.
Outline and Installation Dimension(mm)

Technical Parameter
| No. | ltem | Unit | Value | ||
| FZN25-12D/T630-20 | FZN25-12D/T125-31.5 | ||||
| 1 | Rated voltage | kV | 12 | ||
| 2 | Rated frequency | Hz | 50 | ||
| 3 | Rated current | A | 630 | 125 | |
| 4 | Rated insulation level | 1min power frequency withstand voltage(effective value) | kV | Arc-quenching chamber fracture 30 | |
| Earth, phase 42, insulating fracture 48 | |||||
| Lightning impulse withstand voltage (peak) | kV | Earth, phase 75, insulating fracture 85 | |||
| 5 | Rated dynamic current (peak) | kA | 50 | - | |
| 6 | 4S thermal current | kA | 20 | - | |
| 7 | Rated power load breaking current | A | 630 | 125 | |
| 8 | Rated closed-loop breaking current | A | 630 | 125 | |
| 9 | Rated cable charge breaking current | A | 10 | 10 | |
| 10 | Rated breaking no-load transformer capacity | kVA | 1600 | 1600 | |
| 11 | Rated open circuit breaking current | kA | - | 31.5 | |
| 12 | Rated transfer current | A | - | 2000 | |
| 13 | Fuse model | - | SDLAJ-12,SFLAJ-12 | ||
| 14 | Striker output energy | J | - | 2-5 | |
| 15 | Rated short-circuit closed current | kA | 50 | ||
| 16 | Earth switch rated dynamic current | kA | 50 | ||
| 17 | Earth switch 2s thermal current | kA | 20 | ||
| 18 | Auxiliary circuit rated voltage | V | AC DC220 | AC DC110 | |
| 19 | Mechanical life | times | 10000 | ||