01
GW4-40.5KV Outdoor High Voltage Disconnecting Switch
Service Environment
(1)The altitude does not exceed 3000 meters;
(2) The ambient temperature shall not exceed +40℃ and not be lower than -30℃.
(3) Only suitable for horizontal installation locations, with wind speeds not exceeding 35m/s;
(4)The seismic intensity shall not exceed 8 degrees;
(5) The ordinary type is suitable for Class 0 polluted areas, while the anti-pollution type is suitable for Class III polluted areas.
Structrue Feature
1. The GW4 series isolation switch is a single pole type of double-post isolation switch, which is connected by pole-to-pole connecting rods when used synchronously with three poles.
2. Figure 1 and figure 2 show the structural appearance of the GW4 series isolation switch, which mainly consists of base, post insulator, wiring terminal, movable conductive tube, fixed conductive tube,grounding contact, grounding knife switch and connecting rod. Each pole has two porcelain pillars, which are fixed on the bearing seats at both ends of the base and connected by crossed connecting rods. The conductive part is composed of movable and fixed parts, which are fixed on the top of the two porcelain pillars for horizontal opening and closing. The contact part is in the middle of the two porcelain pillar,sand the waterproof cover can fully cover the middle contact part.
Outline and Installing Dimensions(mm)


Technical Parameters
| Product model | GW4-35(DW) | |
| Rated voltage (kV) | 35 | |
| Maximum working voltage (kw) | 40.5 | |
| Rated current(A) | 630 1250 2000 | |
| Rated thermostable current effective value 2S (KA) | 20 315 315 | |
| Rated dynamic current peak value (KA) | 50 80 1000 | |
| 1min power frequency withstand voltage | To ground | 80 |
| (Effective value KV) | Across isolating distance | 90 |
| Lightning impulse voltage | To ground | 185 |
| (Peak value KV) | Across isolating distance | 215 |