HXGN-12 10kV Fixed Ring High Voltage Switchgear

The HXGN-12 box-type (fixed) metal-enclosed ring main unit (RMU) is a new type of high-voltage switchgear designed specifically to meet the needs of urban power grid renovation and construction. It utilizes an advanced metal-enclosed structure, offering excellent protection against environmental influences and ensuring stable operation in all weather conditions. The RMU not only distributes high-voltage power but also enables intelligent monitoring and management of the power grid, improving the reliability and safety of the power system.

    Product Overview and Features

    HXGN-12 type Box-type (fixed) metal-enclosed ring network switchgear (referred to as ring network cabinet) is a new type of high-voltage switchgear produced for the needs of urban power grid renovation and construction. The HXGN-12 ring main unit (RMU) was designed with urban space constraints in mind. Its relatively small size facilitates installation and maintenance in densely populated urban areas. Its modular design allows for flexible expansion and upgrades, adapting to changing power demands. By utilizing this highly efficient RMU switchgear, the power supply capacity and service quality of the urban power grid have been significantly enhanced, providing a more stable and reliable power supply for both residential and commercial users.
    In the power supply system as the opening and closing load current as well as closing short circuit current, this ring network cabinet with vacuum load switch, the operating mechanism for the spring actuator, the mechanism can be manually operated, can also be electrically operated. The switch and disconnecting knife are equipped with manual operating mechanism.The ring main unit is a complete set of strong, small size, no fire and explosion hazards, with reliable "five-proof" function.

    Model Meaning

    HXGN-12

    Areas of application and environments of use

    Widely used in coal mines, iron and steel mills, cement factories, building ceramics, textiles, paper and other industrial and mining enterprises and hydroelectric power plants, solar photovoltaic power plants, wind power plants,thermal power plants and other power generation project sand substations, substations and power distribution room sand other indoor places.
    1.The surrounding air temperature: the highest temperature+40℃, the lowest degree -15℃;
    2. Relative humidity:
    Daily average relative humidity: ≤95%; daily average watervapor pressure does not exceed 2.2kPa;
    Monthly average relative humidity: ≤90%; monthly averagewater vapor pressure does not exceed 1.8kPa;
    3.Altitude: below 1000m;
    4. Earthquake intensity: no more than 8;
    5. The surrounding air should not be corrosive or combustible aases, water yapor and other obvious pollution sites;
    6. No violent vibration places;
    7. Beyond the GB/T3906-2020 provisions of the normal conditions of use, by the user and the company to negotiate.

    Main technical parameters

    Name Unit Parameters
    Rated Voltage/Maximum Operating Voltage KV 10/12
    Rated current A 630
    Main busbar current Inlet Cabinet A 630
    Outlet cabinet A 125
    Rated short-time withstand current KA 20
    Rated short circuit duration S 4
    Rated peak withstand current KA 50
    Rated short-circuit closing current KA 50
    Rated active load breaking current A 630
    Closed non-breaking current A 630
    Rated cable charging current KA 20
    Rated short-time withstand current of the grounding switch KA 20
    Ground switch rated short circuit duration S 4(2)
    Ground switch rated peak withstand current KA 50
    Rated short-circuit shutdown current of the grounding switch KA 50
    1min rated frequency withstand voltage Between phases.Phase to ground. Vacuum load switch opening distance KV 42
    Disconnecting switch opening distance KV 48
    Rated lightning impulse withstand voltage Between phases,Phase to ground. Vacuum load switch opening distance KV 75
    Disconnecting switch opening distance KV 85
    Mechanical life Vacuum load switch time 10000
    Ground switch (knife switch)、Disconnecting switch(knife switch) time 2000
    Crossover current A 3150
    Overall dimensions 800(700)*900*2000 mm 200~300kg