01
JN15-12/31.5 Series Indoor High Voltage Ground Switch
Using environment conditions
Altitude:s 1000m;
Ambient temperature:+40℃~-10℃
(allowed for storage and transportation at 30℃℃)Earthquake intensity:≤ 8 degree.In place free of danger of flame and explosion, in places of no severe dust,chemical corrosion and no intense vibration.
Structure
Grounding switch structure is mainly composed of chassis l, flexible connection 2. adjusting locating ring 3, post insulator 4, static contact 5, contact spring 6, bus bar 7, moving contact knife 8, main shalt 9. control board 10, spiral energy storage spring ll,ete (as shown in figure 3, 4).According to user needs, it can also be equipped with electric display device and auxiliary switch
Working principle
When operating mechanism uses earthing switch to switch on, the applied moment uses the main shaft 9 to overcome the resistance torque and drive control board 10 along the switch-on direction.which makes the rocker on the moving contact knife 8 pass through spring dead point,and the spring releases energy to make the grounding switch fast switch on. In the closing position, the moving contact knife 8 firmly and reliably contacts through contact spring 6 and the flange (edge) of static contact 5.
During opening operation, the applied moment make the main shaft 9 to overcome the main moment and torque spring force and drives the control board 10 to turn along the switch-on direction, which makes the rocker on the moving contact 8 to compress spring II to dead center, At this moment, the grounding switch switches off and the spring energy storage ends for another switching on.
Outline and Mounting Dimension


detail pictures


Main technical parameters
|
NO. |
Item |
Unit |
Parameter |
||
|
1 |
Rated voltage |
kV |
12 |
||
|
2 |
Rated short-time withstand current |
kV |
31.5 |
||
|
3 |
Rated duration of short circuit |
S |
4 |
||
|
4 |
Rated short circuit making current |
kA |
80 |
||
|
5 |
Rated peak withstand current |
kA |
80 |
||
|
6 |
Interphase center distance |
mm |
150,210,275 |
||
|
7 |
Rated insulation level |
1min power frequency withstand woltage |
KV |
Phase-to-earth, |
42/48 75/85 |
|
Lightning impulse withstand voltage |
|||||