Low Voltage Active Power Filter
Features
Theory: Adopting a DSP+CPLD full digital control core, three-level topology technology, advanced harmonic detection algorithm, and PWM control strategy to achieve precise compensation of harmonic current.
Operating frequency: 50HZ.
Power grid structure: three-phase three-wire, three-phase four-wire.
External current sampling channel: Two current sampling channel.
Operation Mode: Harmonic, Unbalance.
Harmonic current compensation: 2-50 times, Comprehensive harmonic compensation rate>92%.
Full response time:<40ms.
Stability: Capacities for 100% current limiting output to ensure long-term stable operation of the equipment


Application
Residential power distribution system
Automobile manufacturing industry
Drainage and sewage treatment industry
Data centers
Steel industry
Hospitals
Metallurgical industry
Pharmaceutical manufacturing industry
Distributed photovoltaic industry
Light and textile industry
Mining and industrial enterprises
Semiconductor manufacturing industry
Petrochemical industry
Model Definition

Moudule Model
| Moudule Model | ||||
| Model | Compensation capacity(kvar) | System Voltage(V) | Dimensions Width*Depth*Height(mm) | Cooling System |
| ADL APF-0.4-30A/4L-R | 30 | 400 | 461*430*163 | Forced air cooling |
| ADL APF-0.4-50A/4L-R | 50 | 400 | 461*430*163 | Forced air cooling |
| ADL APF-0.4-75A/4L-R | 75 | 400 | 510*430*163 | Forced air cooling |
| ADL APF-0.4-100A/4L-R | 100 | 400 | 643*496*213 | Forced air cooling |
| ADL APF-0.4-150A/4L-R | 150 | 400 | 643*496*213 | Forced air cooling |
| ADL APF-0.4-200A/4L-R | 200 | 400 | 573*500*280 | Forced air cooling |
| ADL APF-0.69-100A/4L-R | 100 | 690 | 737*495*275 | Forced air cooling |
| ADL APF-0.8-100A/4L-R | 100 | 800 | 737*495*275 | Forced air cooling |
| ADL APF-0.4-200A/4L-C | 200 | 400 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.4-250A/4L-C | 250 | 400 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.4-300A/4L-C | 300 | 400 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.4-400A/4L-C | 400 | 400 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.4-500A/4L-C | 500 | 400 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.4-600A/4L-C | 600 | 400 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.69-200A/4L-C | 200 | 690 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.69-300A/4L-C | 300 | 690 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.69-400A/4L-C | 400 | 690 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.8-200A/4L-C | 200 | 800 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.8-300A/4L-C | 300 | 800 | 1000*1000*2200 | Forced air cooling |
| ADL APF-0.8-400A/4L-C | 400 | 800 | 1000*1000*2200 | Forced air cooling |
Technical Specification
| 400V series | 690V series | 800V series | |
| Altitude | < 2000m, Usage should be derated according to the international standard IEC 3859-2for altitudes above 2000 meters. | ||
| Ambient Temperature | -10-+50℃(derated above 40℃) | ||
| Relative Humidity | ≤ 90%, monthly minimum temperature 25℃, no condensation on the surface | ||
| Pollution Level | Below Level III | ||
| Operating Voltage | AC400V(-20%-+20%) | AC690V(-20%-+20%) | AC800V(-20%-+20%) |
| Operating Frequency | 50Hz | ||
| Rated Compensation Capacity | 30A,50A,75A, 100A,150A,200A | 100A | |
| Power Grid Structure | Three-phase three-wire,Three-phase four-wire | ||
| Numbers in Parallel | Unlimited | ||
| System Efficiency | ≥97% | ||
| Switching Frequency | 16kHz | 12.8kHz | |
| Function Selection | Harmonics,Harmonics+Unbalanced | ||
| Compensation Scope | 2-50 times, with adjustable compensation rate per time | 2-25 times. with adjustable compensation rate per time | |
| Harmonic Compensation Rate | >92% | ||
| Full Response Time | <40ms | ||
| Noise | <65dB | ||
| Communication | Rs485 Communication port | ||
| Protection | Overload, software/hardware over current,power grid over voltage/under voltage. power failure. over-temperature, frequency abnormality,short circuit protection | Overload, software/hardware over current, power grid over voltage/under voltage,power grid voltage imbalance. power failure. over-temperature, frequency abnormality,short circuit protection | |
| Installation | Rack-Mounted, Wall-Mounted | Rack-Mounted | |
| Entry Line Method | Rear Inlet(rack-mounted)Top Inlet (wall-mounted) | Rear Line | |
| Protection Level | Ip20 | ||