Low Voltage Static Var Generator Specification

Application
The Static Var Generator(SVG)is an advanced reactive power compensation device based on a power electronic converter. Its basic principle is to connect a voltage-source converter in parallel with the grid through an inductor,adjusting the phase and amplitude of the converter's AC-side output voltage to absorb or supply the required reactive current. This enables dynamic reactive power compensation and provides an optimal solution in the field of power quality management.

    Features

    Theory: Use a DSP + CPLD fully digital control core, three-level topology technology, advanced reactive power detection algorithms, and PWM control strategies to achieve dynamic and precise reactive power compensation.
    Operating frequency: 50Hz.
    Power grid structure: three-phase three-wire, three-phase four-wire.2
    External current sampling channel: Two current sampling channel.
    Operation Mode: Reactive power, Unbalance
    Compensation mode: Low voltage sampling low voltage compensation, High voltage sampling low voltage compensation,Reactive power component.
    Reactive power compensation:compensation rate>98%
    Full response time: <10ms
    2Stability: Capacities for 100%, current limiting output to ensure long-term stable operation of the equipment.
    SVG (2)
    SVG (1)
    SVG

    Application

    Residential power distribution system
    Automobile manufacturing industry
    Drainage and sewage treatment industry 
    Data centers
    Distributed photovoltaic industry
    Hospitals
     Mining and industrial enterprises
    Pharmaceutical manufacturing industry
    Petrochemical industry
    Semiconductor manufacturing industry

    Model Definition

    Low Voltage Static Var Generator Specification

    Moudule Model

    Moudule Model
    Model Compensation capacity(kvar) System Voltage(V) Dimensions Width*Depth*Height(mm) Cooling System
    ADL SVG-0.4-20k/4L-R 20 400 461*430*163 Forced air cooling
    ADL SVG-0.4-30k/4L-R 30 400 461*430*163 Forced air cooling
    ADL SVG-0.4-50k/4L-R 50 400 510*430*163 Forced air cooling
    ADL SVG-0.4-75k/4L-R 75 400 643*496*213 Forced air cooling
    ADL SVG-0.4-100k/4L-R 100 400 643*496*213 Forced air cooling
    ADL SVG-0.4-150k/4L-R 150 400 573*500*280 Forced air cooling
    ADL SVG-0.69-120k/4L-R 120 690 737*495*275 Forced air cooling
    ADL SVG-0.8-140k/4L-R 140 800 737*495*275 Forced air cooling
    ADL SVG-0.4-200k/4L-C 200 400 1000*1000*2200 Forced air cooling
    ADL SVG-0.4-250k/4L-C 250 400 1000*1000*2200 Forced air cooling
    ADL SVG-0.4-300k/4L-C 300 400 1000*1000*2200 Forced air cooling
    ADL SVG-0.4-400k/4L-C 400 400 1000*1000*2200 Forced air cooling
    ADL SVG-0.69-240k/4L-C 240 690 1000*1000*2200 Forced air cooling
    ADL SVG-0.69-360k/4L-C 360 690 1000*1000*2200 Forced air cooling
    ADL SVG-0.69-480k/4L-C 480 690 1000*1000*2200 Forced air cooling
    ADL SVG-0.8-280k/4L-C 280 800 1000*1000*2200 Forced air cooling
    ADL SVG-0.8-420k/4L-C 420 800 1000*1000*2200 Forced air cooling
    ADL SVG-0.8-560k/4L-C 560 800 1000*1000*2200 Forced air cooling

    Technical Specification

    400V series 690V series 800V series
    Altitude < 2000m, Usage should be derated according to the international standard IEC 3859-2 for altitudes above 2000 meters.
    Ambient Temperature -10---+50℃(derated above 40℃)
    Relative Humidity ≤ 90%, monthly minimum temperature 25℃, no condensation on the surface
    Pollution Level Below Level III
    Operating Voltage AC400V(-20%-+20%) AC690V(-20%-+20%) AC800V(-20%-+20%)
    Operating Frequency 50Hz
    Rated Compensation Capacity 30kvar,50kvar,75kvar,100kvar,150kvar, 120kvar 140kvar
    Power Grid Structure Three-phase three-wire,Three-phase four-wire
    Numbers in Parallel Unlimited
    System Efficiency ≥97%
    Switching Frequency 16kHz   12.8kHz
    Function Selection Reactive Power, Reactive Power + Unbalanced
    Full Response Time <10ms
    Noise <65dB
    Communication Rs485 Communication port
    Protection Overload, Software/Hardware Overcurrent Grd Over/Under Voltage. Voltage Imbalance,Power Supply Fault Overtemperature. Frequency Abnormality Short Circuit Protection
    Installation Rack-Mounted, Wall-Mounted   Rack-Mounted
    Entry Line Method Rear Inlet
    Protection Level Ip20