Advantages of Current Transformer: Isolation, Class Pairing, and Limits
A current transformer isolates meters and relays from the primary circuit and steps high AC line current down to a standard 1 A or 5 A secondary so ordinary instruments can do the work. The advantages of current transformer hardware hold only when a metering-class core for billing accuracy is paired with a protection-class core for fault current and the secondary stays closed. Indoor 12 kV switchgear is where that pairing is specified, and LZZBJ9-12 is the indoor body for that duty.

Why Use a Current Transformer Instead of Measuring Line Current Directly
A current transformer exists so ordinary meters and relays can see a high-current feeder without sitting on that current.
The device is an instrument transformer: it copies a large alternating line current as a small, isolated secondary current. Direct measurement would mean a heavily insulated in-line ammeter, or a shunt that still shares the primary circuit and struggles on AC.
On a 12 kV indoor feeder the specifier wants a standard energy meter and a relay, not a custom high-voltage instrument. The series-connected current transformer is what makes that ordinary instrument possible.
A shunt also dissipates heat and offers no isolation. The CT presents a negligible load to the primary and keeps the measuring circuit off the line.
Isolation Plus a Standardized 1 A or 5 A Secondary
The working advantage is galvanic isolation plus a standardized 1 A or 5 A secondary that ordinary instruments already expect.
Galvanic isolation keeps the meter, the relay, and the person in front of them off the high-voltage conductor. The secondary is a separate circuit, so the low-current side can be serviced while the feeder stays live if that secondary remains closed.
Instrument makers already build for 1 A or 5 A inputs. That standard is cheaper than inventing a meter stout enough to sit in the line.
IEC 61869-1 names the metering accuracy classes 0.1, 0.2S, 0.2, 0.5, 0.5S, 1 and 3 so a specifier can pick a core that stays accurate at load.

One indoor body can carry more than one secondary winding, so a metering circuit and a protection circuit do not have to share a core. That is how isolation stays useful after the first instrument is connected.
Metering-Class Advantages Versus Protection-Class Trade-offs
A metering-class CT is built to stay accurate at load and to limit how hard it drives a meter during a fault; that same core is the wrong feed for a protection relay.
Metering-class CTs hold tight ratio and phase error near rated current. They are also built to saturate relatively early — the instrument-security habit — so a fault does not drive the billing meter with a faithful copy of huge current.
A protection-class CT trades some of that steady-state precision for a usable secondary while fault current is many times load. Saturation / knee point is the flux limit: once the core fills, the secondary stops copying the primary and the relay can under-reach.
Metering cores are typically held accurate only around 1.2 to 1.5 times rated current. Protection cores may be asked to stay useful at 20 to 30 times rated.
Feed a relay from the metering core and you inherit the advantage that protects the meter as the disadvantage that starves the relay.
| Job on the feeder | What the core is good at | What that same core will not do |
|---|---|---|
| Metering-class CT (measuring CT, 0.2S / 0.5 class) | Tight error at normal load; earlier saturation that shields the meter | Faithful fault-current copy for a protection relay |
| Protection-class CT (relay-class CT, 10P15) | Usable secondary across a wide current range so the relay can operate | Billing-grade error at every load point |
| Dual-class indoor body | A metering winding and a 10P15 winding in one resin-cast assembly | Substituting the metering winding for the protection winding |
Metering CTs are purposely designed to saturate just above their primary ratio, so they will not give the relay a true picture of the fault.

Disadvantages of a Current Transformer: Open Secondary, Burden, and Saturation
The advantages reverse if the secondary is left open, if secondary burden exceeds rating, if a metering core is asked to track fault current, or if the circuit is DC.
On a conventional current-output secondary, the first disadvantage is an open-circuit secondary. Primary current then becomes magnetizing current, flux rises, and the secondary voltage can damage insulation or shock the person holding the leads.
Important: Never leave a conventional current transformer secondary open while primary current is flowing. Short the secondary at the terminal block before removing a meter or relay. Forum language matches that rule: don’t mess with the output wiring; opening it can create a dangerously high voltage.
Secondary burden is the VA of the meters, relays, and lead resistance hanging on those small-current wires. Extra cable length is often what uses up the margin; once burden is high, ratio error and phase displacement grow and the core can saturate earlier than the class implies.
A conventional iron-core current transformer measures alternating current. If the circuit is DC, a CT is the wrong instrument.
Isolation and a standard secondary help only while the loop stays closed and inside the published burden.
Voltage-transformer pairing is a different buying question than the class pairing on a CT secondary.
Current Transformer Application in Indoor Switchgear
The usual current transformer application on indoor medium-voltage gear is feeder metering and relay control, not a clamp-on energy-monitor retrofit.
Energy meters, protective relays, and monitoring inputs all sit on the secondary in the cubicle.
Split-core CTs are the retrofit device when a feeder cannot be opened; the hinge air gap typically costs some accuracy versus a solid core. Indoor resin-cast switchgear CTs are closed-core bodies built in from the start, not split-core donuts.

A window-type or bar-type indoor CT takes the feeder conductor as its primary. The advantage the buyer paid for — isolation plus a standard secondary — only shows up if the secondary wiring, the shorting block, and the class pairing were specified with the cubicle.
Mapping LZZBJ9-12 to Indoor 12 kV Metering and Protection
LZZBJ9-12 is the indoor 12 kV and below metering-and-protection CT; outdoor duty is a different family on the same hub.
The LZZBJ9-12 current transformer is specified for indoor metering and protection in 12 kV and below AC systems. It transforms high primary current into standardized low secondary values for energy measurement and relay control.
Published LZZBJ9-12 combinations include 0.2S/10P15, 0.2/10P15 and 0.5/10P15, with 10 VA on the metering classes and 15 VA on 10P15 at cosφ=0.8.
| Family | Where it belongs | Published scope for this family |
|---|---|---|
| LZZBJ9-12 | Indoor 12 kV and below, metering plus protection | Dual-class strings 0.2S/10P15, 0.2/10P15, 0.5/10P15; 10 VA / 15 VA at cosφ=0.8 |
| LZZBJ71-12 | Outdoor family on the same hub | Do not stretch an indoor LZZBJ9-12 into pole-top or outdoor duty |
| LZZBJ9-10 | Indoor 10 kV resin-cast switchgear CT | Metering and feeder protection in compact 10 kV cubicles |
LZZBJ9-10 is Andeli's resin-cast indoor 10 kV switchgear CT for metering and feeder protection. Outdoor service is LZZBJ71-12, shown separately on the current transformer hub.
Recommended Indoor 12 kV Current Transformer: LZZBJ9-12
Open LZZBJ9-12 when the job is indoor 12 kV metering and protection; send outdoor duty to the outdoor family instead.
If you are weighing the advantages and disadvantages of current transformer class pairing on an indoor 12 kV feeder, the LZZBJ9-12 type current transformer already publishes dual-class combinations for metering plus 10P15 protection on that indoor body. If the duty is outdoor, or indoor 10 kV, return to the current transformer hub and pick LZZBJ71-12 or LZZBJ9-10 rather than stretching this indoor 12 kV unit.

FAQ
What are the advantages of a current transformer?
Isolation from the primary, a standardized 1 A or 5 A secondary, and the ability to feed ordinary meters and relays are the advantages. They hold only while class pairing is right and the secondary stays closed.
What are the disadvantages of using a current transformer?
The disadvantages of current transformer secondaries that still use a current output are an open-circuit secondary, excess burden, the wrong class at fault current, and AC-only sensing. A metering core asked to feed a protection relay belongs on that list.
What is the most common current transformer application?
Indoor switchgear metering and relay control is the common industrial use. Retrofit split-core monitors are a different construction and a different buying problem.
Why shouldn't a CT secondary be left open?
With primary current flowing, an open secondary lets flux rise without an opposing ampere-turn and can produce a dangerous voltage plus heating. Short the secondary before a meter or relay comes off.
What is the difference between a metering CT and a protection CT?
A metering-class CT is accurate at load and saturates early enough to protect the instrument. A protection-class CT keeps a usable secondary during fault current so the relay can operate.
Can a conventional current transformer measure DC?
No. A conventional iron-core current transformer is an AC device. DC needs a shunt, a Hall sensor, or a fluxgate transducer.
Where does an indoor 12 kV CT like LZZBJ9-12 fit?
It fits indoor metering and protection in 12 kV and below AC systems, including published 0.2S/10P15, 0.2/10P15 and 0.5/10P15 combinations. Outdoor duty is LZZBJ71-12; indoor 10 kV is LZZBJ9-10.
Does extra secondary wiring cancel the accuracy advantage?
It can. Lead resistance is part of secondary burden, and extra length is often what uses up the published VA. Size the wire and the run so meter, relay, and cable stay inside the rated burden.