Application of Potential Transformer

2026-10-05

A potential transformer is applied in parallel with the circuit so meters, relays, and a synchronizing check can use a low voltage that follows the line. On a 35 kV indoor switchgear job, the application of potential transformer is feeding those devices from the printed metering output and the protection output.

Maroon epoxy voltage transformer on a steel base, with a ribbed primary bushing, a side cover, a clear secondary terminal box, and a blue ANDELI mark in the corner.

Potential transformer applications in that setting are the work of a voltage transformer for metering and protection. The indoor switchgear voltage transformer is the hardware whose ratio is printed as an image, and the metering output, the protection output, and the thermal limiting output stay separate figures.

Where the Potential Transformer Is Connected

A potential transformer, also called a voltage transformer, PT, or VT, is connected in parallel so the primary tracks bus voltage. Indoor switchgear is the printed setting for this 35 kV unit, described as a three-phase, epoxy-insulated, dry, flame-retardant voltage transformer.

Potential transformer applications named with that hardware are metering, measurement, protection, and ferroresonance damping. Ferroresonance damping is the damping behavior printed for this voltage transformer, and in plain language it is a check on a voltage oscillation associated with the unit.

Meters, relays, and a synchronizing check all take the secondary that follows the line. Billing can take one output while a feeder relay takes another, which is how one voltage transformer serves measurement and protection together.

The IEC 61869-3:2011 abstract covers new inductive voltage transformers used with measuring instruments and protective devices from 15 Hz to 100 Hz. It replaces IEC 60044-2 and is read with IEC 61869-1:2007.

JDZX9-35 does not print that standard.

A buyer still has to match the circuit connection, including a line-to-ground connection when that is how the gear is built, to the ratio image before the secondary numbers mean anything. The images print a primary term of 35000/√3 on both rows, and the job's connection has to agree with that printed form.

Metering and Billing from the Accuracy Output

Metering uses the tighter outputs printed at COS∅=0.8 on the first ratio image: the 0.2 class output is 40 and the 0.5 class output is 80. A metering winding is that accuracy output, and in plain language it is the secondary a meter uses when the reading has to stay inside a tight class.

A voltage transformer for metering and protection can carry both jobs, and the split between them is the accuracy class. The substation components explanation calls protection and metering two main types of potential transformers based on their accuracy classes.

Front view of a maroon cast voltage transformer with the clear secondary terminal box facing forward and a ribbed bushing above the body.

That explanation's own examples use a secondary generally at 110 V, including a 33 kV/110 V case. The ratio images print 100/√3 and 100/3, so the 110 V example stays on that education page.

Billing follows the metering winding, because a revenue reading is only as tight as the class printed for that output. The thermal limiting output on the first row prints 600, and that figure sits apart from 40 and 80.

Relay Protection and Generator Synchronizing

Protection and generator synchronizing use the voltage reference, including the printed 3P and 6P output of 100 on both ratio rows. A protection winding is that 3P and 6P output, and in plain language it is the secondary a relay uses to watch high voltage or low voltage.

A voltage transformer for metering and protection still has to land the relay on the correct polarity. Polarity is the mark that keeps the voltage direction honest for the relay, and the same note ties a PT output to overvoltage and undervoltage detection.

Feeder protection takes that protection winding when the scheme is watching feeder voltage. Synchronizing compares voltage before a generator or a feeder connects to the system, and the secondary used for that check remains a reference.

Side view of a maroon cast voltage transformer showing the rounded body, ribbed primary bushing, and steel mounting base.

The polarity mark has to match the relay or the sync-check wiring, or the voltage arrives reversed. That is a connection detail on the protection output, separate from which class number is printed in the 3P and 6P place.

Reading the Image-Only 35 kV Ratio

The ratio is printed only as an image, under the header that reads Rated transformation ratio(A). One image prints 35000/√3 / 100/√3 / 100/3, and the other image prints 35000/√3 / 100/√3 / 100/√3 / 100/3.

The catalog heading is JDZX9-35. The specification table type cell prints JDZ9-35(W), so a buyer keeps both strings when the drawing, the order, and the catalog card have to agree.

The first image carries three voltage terms, and the second image carries four, with an added 100/√3 between the first secondary and the final 100/3. That extra term is why the second row can print paired class outputs such as 0.2/0.5 and 0.5/0.5.

Printed item First ratio image Second ratio image
Type cell JDZ9-35(W) JDZ9-35(W)
Ratio as printed on the image 35000/√3 / 100/√3 / 100/3 35000/√3 / 100/√3 / 100/√3 / 100/3
0.2 at COS∅=0.8 40 blank
0.5 at COS∅=0.8 80 blank
0.2/0.5 at COS∅=0.8 blank 20/50
0.5/0.5 at COS∅=0.8 blank 30/30
3P 6P at COS∅=0.8 100 100
Thermal limiting output 600 300
Insulation under Rated insulation level(kA) 40.5/95/200 40.5/95/200

On the first ratio row, at COS∅=0.8, the 0.2 class output prints 40 and the 0.5 class output prints 80. The 0.2/0.5 and 0.5/0.5 places on that row are blank, the 3P 6P output prints 100, and the thermal limiting output prints 600.

On the second ratio row the 0.2 and 0.5 places are blank, while 0.2/0.5 prints 20/50 and 0.5/0.5 prints 30/30. The 3P 6P output again prints 100, and the thermal limiting output prints 300.

The insulation figures 40.5/95/200 appear once across both rows under the header Rated insulation level(kA). COS∅=0.8 is the power-factor mark over the accuracy outputs, the same mark written as cos φ 0.8, and a blank class place stays blank.

The ratio header is printed as Rated transformation ratio(A), and the insulation header is printed as Rated insulation level(kA). The (A) and the (kA) stay in those headers.

The note under the specification table says any special requirements can be negotiated. The note leaves the blank places blank, and it leaves 600 and 300 under thermal limiting output.

Accuracy Output Versus Thermal Limiting Output

The accuracy-class outputs and the thermal limiting output are different printed limits, even on the same ratio row. Secondary burden is the meters, relays, fuses, and wiring on the secondary, and in plain language it is the connected VA that can pull the reading off when the load gets heavy.

The potential transformer explanation says ratio error and phase-angle error increase when the burden exceeds the rated value. Every meter and relay on that secondary then inherits the error, which is why the class output and the heating limit cannot be swapped.

From the field: A September 2020 note on the voltage transformer burden thread asks whether the burden reading should include secondary fuses and wiring up to the VT secondary. The same note says a circuit with one or two relays can sit far below a high nameplate burden, and the 0.3W-Z span plus a guess near 1 VA belong to that conversation.

A protection circuit with one or two relays can sit well under a thermal limiting output of 600 or 300. The accuracy output is the figure that has to cover the real burden if the class is to hold, and the thermal limiting output remains the heating figure printed beside it.

A replacement conversation still asks for location, line-to-ground connection, secondary voltage, ratio, accuracy class, burden, thermal rating, and fusing. One such question used 115 V and ratio 175 on a 34.5 kV system, and those figures stay with that question.

The answer depends on whether the secondary is for revenue metering or for protection. Metering follows the meter owner's class and burden, and protection follows the relay functions, the combined relay burden, and the voltage range those relays accept.

Jobs This Voltage Transformer Must Not Take

A power transformer, including a distribution transformer, transfers load energy out to the feeder. This voltage transformer gives meters and relays a proportional voltage, and the burden explanation states that it does not transfer usable power.

A control power transformer, also called a CPT, supplies control circuits and sits at a higher power level than a metering PT.

A low-voltage metering unit for about 600 V, with a 120 V secondary sitting in a motor control center, is a different application from this 35 kV indoor unit. Any UL or CSA wording on that low-voltage pattern stays with that pattern, and the JDZX9-35 printing does not include it.

JDZ9-6-10 is a different model. The indoor job stays on JDZX9-35, which is its own model in the voltage-transformer group.

Job on the secondary Output that fits the job Work that belongs on another device
Metering and billing 0.2 and 0.5 on the first ratio image, 40 and 80 at COS∅=0.8 Load energy through a power transformer
Protection 3P and 6P output of 100 Control circuits fed by a CPT
Synchronizing The voltage reference, with polarity matched A distribution transformer moving feeder energy

When JDZX9-35 Fits Indoor 35 kV Switchgear

Choose JDZX9-35 when the job is the printed indoor switchgear voltage transformer for metering, measurement, protection, and ferroresonance damping. The heading reads JDZX9-35, and the specification table type cell still prints JDZ9-35(W).

Top view of a maroon cast voltage transformer with a center bushing stud, side body sections, a steel base, and a clear terminal box at one edge.

Open the JDZX9-35 voltage transformer and set the meter list and the relay list against the printed class outputs and the thermal limiting output. Related models are grouped on the voltage transformer hub, and the model for this job is JDZX9-35.

The useful comparison is 0.2 at 40, 0.5 at 80, the paired outputs 20/50 and 30/30, the 3P 6P output at 100, and thermal limiting output at 600 or 300, all at COS∅=0.8. A blank place on a row stays blank while that comparison is made.

Specifying engineers, EPC designers, and plant or utility buyers place this voltage reference in indoor medium-voltage gear. They read the metering output and the protection output before they treat 600 or 300 as an accuracy figure.

FAQ

What is the application of a potential transformer in a medium-voltage switchgear line?

It supplies meters, relays, and a synchronizing check with a low voltage that follows the line. On the indoor unit discussed here, the printed work is metering, measurement, protection, and ferroresonance damping together.

How does a potential transformer serve metering and protection at the same time?

The metering winding and the protection winding are separate outputs on the same printed rows. Meters use the 0.2 or 0.5 class output, and relays use the 3P and 6P output, so both jobs can share the unit while the thermal limiting output stays in its own place.

What secondary voltage and ratio should a buyer read before using a 35 kV indoor VT?

Read the ratio from the image, because the ratio is not typed as text. One image prints 35000/√3 / 100/√3 / 100/3, and the other prints 35000/√3 / 100/√3 / 100/√3 / 100/3.

Why is the accuracy-class output different from the thermal limiting output?

The accuracy-class output is the figure tied to 0.2, 0.5, 0.2/0.5, 0.5/0.5, or 3P 6P at COS∅=0.8. The thermal limiting output is the other printed figure, 600 on the first row and 300 on the second, and fuses plus wiring sit inside the burden the secondary actually carries.

How is a potential transformer different from a power transformer in the same substation?

A power transformer transfers usable load power to the feeder. A potential transformer gives instruments and relays a proportional voltage, and burden above the rated value increases ratio error and phase-angle error.

What should an engineer ask a vendor when replacing a potential transformer on a 35 kV system?

Ask for location, line-to-ground connection, secondary voltage, ratio, accuracy class, burden, thermal rating, and fusing, then split the answer by metering versus protection. Keep 115 V and ratio 175 off this nameplate, because those figures came from a different replacement question.

Can this voltage transformer feed control power circuits?

A control power transformer supplies control circuits in switchgear and control panels. This voltage transformer remains the reference for meters and relays, so control power stays with a CPT.

References

  • IEC 61869-3:2011 abstract on inductive voltage transformers for measuring instruments and protective devices. https://webstore.iec.ch/en/publication/6051.
  • Substation explanation of metering and protection as accuracy-class uses of a potential transformer. https://www.electricalvolt.com/electrical-substation-components/.
  • Instrument-transformer note on polarity and the higher power level of a control power transformer. https://wiki.testguy.net/t/instrument-transformers-types-and-testing-at-a-glance/3321.
  • Potential-transformer explanation of burden error and the limit on transferring usable power. https://www.electricityforum.com/iep/electrical-transformers/potential-transformer.
  • Field thread on whether a voltage-transformer burden reading includes fuses and wiring. https://forum.testguy.net/threads/6628-Voltage-Transformer-Burden-Measurement.