Applied Voltage Test for Power Transformer

2026-10-05

An applied voltage test for power transformer is a separate source withstand test: every terminal of the winding under test, including the neutral, is tied together, and that voltage stresses the winding to earth and to the other windings.

Shops also call this separate-source AC withstand an applied potential test. The tie, the split from the induced voltage test, and the pass language follow, with the S9-35 kV series as the oil-immersed transformer under discussion.

Studio product photo of an oil-immersed power transformer discussed as the equipment in an applied voltage test.

A bushing voltmeter answers a service-voltage question. The stress in this withstand is ground-wall insulation, meaning the insulation from the copper to earth, the core, the frame, and the tank.

Contents

  • What the Applied Voltage Test Stresses.
  • How the Winding Is Connected for the Hold.
  • How Applied Voltage Differs from the Induced Test.
  • Why Non-Uniform Insulation Changes the Terminal.
  • What IEC 60076-3 and IEEE C57.12.90 Each Cover.
  • What Counts as a Pass on This Withstand.
  • The S9 35 kV Series as the Transformer Under Test.

What the Applied Voltage Test Stresses

It stresses the shorted winding, including the neutral, to earth and to the other windings. Turn-to-turn insulation waits for a different test.

Ground-wall is the insulation between the winding and the tank, and it also includes the path to the core and the frame. Winding-to-winding insulation is in the same job, because the windings that are not under test are held at earth while the tested winding is raised.

A commissioning reader who shorts the primary and the secondary, then applies voltage between those two bundles, is already looking at that path. The leftover question is turn-to-turn insulation, which a shorted winding cannot show.

With every terminal of the tested winding at one potential, there is no voltage from turn to turn along that winding. The neutral is in the same tie so the end that often looks “quiet” in service is included in the stress to earth.

People reach this topic after a voltmeter question, or after a request to prove the copper between turns. The applied voltage test answers the major insulation. The induced voltage test is the one that puts voltage between turns.

On a forum thread about insulation testing, the writer already treated a shorted primary and a shorted secondary as the straightforward check between windings. The same note asked how to reach turn-to-turn insulation, which is the split this section is for.

How the Winding Is Connected for the Hold

Tie every terminal of the tested winding together, earth the other windings plus the core, frame, and tank, and use a near-sine wave at not less than 80% of rated frequency. Start at not more than one-third, hold 60 seconds, and come back below one-third before switch-off.

This power frequency withstand comes from an external source, so the transformer is not excited the way it is in service. The measured peak divided by √2 is the test value, and the wave is approximately sinusoidal.

The timing and the tie are set out in a clause-by-clause explanation of IEC 60076-3.

Step What happens
Tie Every terminal of the tested winding, including the neutral
Earth The other windings, plus core, frame, and tank
Frequency Not less than 80% of rated frequency
Value Measured peak divided by √2
Start Not above one-third of the test voltage
Hold 60 seconds at the full test voltage
Finish Return below one-third before switch-off
Pass No collapse of the test voltage

The crew raises the source from that one-third region, stays at full voltage for the hold, and only then comes back down. Opening the switch while the winding is still at full voltage is the ending the timing is written to avoid.

When the next winding becomes the one under test, its own terminals are the ones tied together. The winding just finished joins the earthed group with the core, the frame, and the tank.

On the studio photo below, the bushings are the terminals the tie would join on the winding under test. The conservator and the radiator tank belong with the earthed metalwork.

Studio photo of an oil-immersed transformer with bushings and a conservator.

The photograph is a studio view of the oil-immersed unit. Bushings, conservator, and tank are the parts the tie and the earth connection refer to.

A separate shop paraphrase of the liquid-immersed test code starts no higher than one-quarter and holds for one minute. That fraction stays beside the one-third start above, and the two are not averaged into one ramp.

How Applied Voltage Differs from the Induced Test

The induced voltage test is the one that stresses turn-to-turn and phase-to-phase insulation. The one-hour partial-discharge sequence on the Houston factory-test slides belongs to that induced voltage test.

A 2022 insulation thread already separates a shorted-winding voltage from the turn-to-turn question.

Important: A reader who already shorts each winding and applies voltage between them still asked, “I would like to know how to test turn to turn insulation.” That shorted connection is the ground-wall and winding-to-winding job, and turn-to-turn insulation belongs to the induced voltage test.

IEEE Houston section slides list applied voltage with lightning impulse, switching impulse, and induced voltage. Applied voltage is the stress to ground, and it is described as critical for a fully insulated winding.

Induction raises the flux so a voltage appears between turns and between phases. The applied-voltage tie is built so that difference on the tested winding stays at zero while the stress goes to earth and to the other windings.

Partial discharge watched over a long enhancement is part of the induced story on those slides. Folding that hour into the applied-voltage hold would mix two dielectric jobs.

The studio photo below shows the radiator tank and the conservator, the metal boundary that ground-wall insulation has to stand. The view is a product photograph of the tank.

Studio photo of an oil-immersed transformer tank with radiators and a conservator.

A specifier who has just watched a shorted-winding setup still needs a name for the test that creates turn-to-turn stress. That name is the induced voltage test, and the applied voltage test remains the ground-wall withstand.

Why Non-Uniform Insulation Changes the Terminal

On non-uniform insulation the applied-voltage test uses the neutral-terminal voltage. The line terminal is the job of LTAC or switching impulse.

Non-uniform insulation, sometimes called graded insulation, puts more dielectric at the line end than at the neutral. The neutral terminal is the level this withstand is allowed to use on that winding.

LTAC is the line-terminal AC withstand used when the applied-voltage test stays at the neutral. Switching impulse is the other line-end test named for the same graded case.

A reader who expects one applied-voltage level to cover both the line bushing and the neutral on a graded winding is asking one terminal to do two jobs. The neutral sets this test. The line end is assigned elsewhere.

Fully insulated windings are the other case. There the stress to ground can matter along the winding, which is why the Houston slides single out applied voltage for fully insulated windings.

Asking which terminal owns the number comes before anyone looks up a level. Until uniform and graded construction are separated, a single kilovolt figure looks as if it belongs on every bushing.

What IEC 60076-3 and IEEE C57.12.90 Each Cover

IEC 60076-3:2013 sets insulation levels and dielectric tests for power transformers, and the third edition renamed the line-terminal AC withstand from ACSD to LTAC.

IEC 60076-3:2013 was published on 2013-07-31.

The consolidated file is IEC 60076-3:2013+AMD1:2018.

IEEE C57.12.90-2021 is the liquid-immersed test code, and its catalog scope includes dielectric tests. Instrument transformers sit outside that catalog.

The two documents answer two different requests. One names insulation levels and the dielectric tests, including the LTAC rename. The other is the test code for liquid-immersed distribution, power, and regulating transformers.

The one-third start lives in the clause explanation of the IEC dielectric test. The one-quarter start is a shop paraphrase of the IEEE code, and it is left as that paraphrase.

IEC 60076-3 leaves insulation-resistance testing and power-factor testing outside its dielectric list. A megger sheet or a dissipation-factor sheet is a different appointment from this withstand.

Readers also ask which IEEE document applies, and some of those questions wander into oil breakdown or a small control transformer. The IEEE name that belongs here is the liquid-immersed test code above, while oil breakdown and the control-transformer case are other jobs.

What Counts as a Pass on This Withstand

The pass for this withstand is no collapse of the test voltage. On a hipot set, excess return current trips the test, and the write-up gives no minimum passing current.

Hipot, or high-pot, is the shop name for a go/no-go dielectric withstand above nominal voltage. The hipot explanation treats a trip on excess return current as the failure, and it offers no separate minimum pass current.

A crew that wants a leakage number in milliamps will not find that floor in this description. The written pass is that the voltage stays up for the hold.

A TestGuy thread opens with a search for a definitive answer on which DC insulation-resistance voltage to use when the two windings differ. That search is a megger question sitting next to this topic, and the applied-voltage hold remains an AC withstand with its own tie and timing.

Power-factor and insulation-resistance results can sit on the same commissioning list as a withstand. Each one reads the insulation in its own way, while this withstand is decided by a collapse or by a trip.

Field crews often meet a megger and a power-factor set long before anyone rolls out a separate-source withstand. Knowing which instrument is in the truck keeps this hold from being read as a resistance reading.

The S9 35 kV Series as the Transformer Under Test

The S9-35 kV series transformers are an oil-immersed 35 kV family this applied-voltage test can be about.

The printed connections are Yyno and Yd11.

On the lower table the low voltage is 0.4 kV and the short-circuit impedance is 6.5%.

Rated capacity on that table runs from 50 kVA to 2500 kVA.

A printed 50 kVA row lists no-load loss of 215 W and load loss of 1210 W at 75°C.

The higher-capacity table runs from 800 kVA to 20000 kVA.

From 3150 kVA the high-voltage column is printed 35 / 38.5 kV.

Low voltage on that table is 3.15, 6.3, or 10.5 kV.

Impedance is 6.5% through 2500 kVA, 7.0% at 3150 kVA, 4000 kVA, and 5000 kVA, 7.5% at 6300 kVA, 8000 kVA, and 10000 kVA, and 8% from 12500 kVA through 20000 kVA.

Tapping is ±5% on the smaller units and ±2×2.5% from 8000 kVA.

The cores are high-permeability cold-rolled grain-oriented silicon steel, and the oil filling is done under vacuum after vacuum drying.

A hermetically sealed conservator keeps the oil isolated from oxygen and moisture. In normal operation the series is described as free of routine oil replacement.

Normal service is below 1000 m, with a highest air temperature of +40°C, a highest daily average of +30°C, a highest annual average of +20°C, and a lowest outdoor air temperature of -25°C.

The printed standards line includes IEC 60076-1-2-3 2000, together with GB 1094 and GB/T 6451.

An applied-voltage level, a 60-second factory hold, and BIL stay unpublished on this series, and no NETA or IEEE certificate is shown beside that standards line.

The series sits with the other oil-immersed units in the transformer range. The useful next look is the printed high voltage, the connections, and the impedances, while the applied-voltage level stays unpublished there.

Utilities, EPCs, industrial plants, and specifying engineers who need a 35 kV oil-immersed unit can use the series as the transformer under discussion. A buyer who needs a published hipot level, a dry-type unit, or a class other than this 35 kV family needs a different sheet.

Studio photo of an S9 series oil-immersed power transformer with conservator and bushings.

The frame shows the conservator, the bushings, and the radiator tank in a studio setting. It is the product the recommendation points to.

FAQ

What is an applied voltage test for a power transformer?

It is a separate-source AC withstand on the shorted winding, including the neutral, to earth and to the other windings. Turn-to-turn stress is left for the induced voltage test.

How is an applied voltage test different from an induced voltage test?

The applied voltage test holds the tested winding at one potential so the stress is ground-wall and winding-to-winding. The induced voltage test produces the turn-to-turn and phase-to-phase stress, including the long partial-discharge sequence on the factory slides.

Why are all terminals of the tested winding tied together, including the neutral?

The tie puts the whole tested winding, neutral included, at the same potential. That removes turn-to-turn voltage on that winding and places the stress on insulation to earth and to the windings that are earthed.

How long is the applied voltage held, and from what voltage does the operator start?

The hold at full voltage is 60 seconds, and the start is not above one-third. A shop paraphrase of the IEEE code uses a one-quarter start and a one-minute hold, and that paraphrase stays separate from the one-third start.

What does a pass look like, and what does a hipot trip mean?

The pass is no collapse of the test voltage. A hipot trip means return current went high enough to trip the set, and there is no minimum passing current in that description.

Which standard names this test, IEC 60076-3 or IEEE C57.12.90?

IEC 60076-3:2013 names insulation levels and dielectric tests, and its third edition uses LTAC for the line-terminal AC withstand. IEEE C57.12.90-2021 is the liquid-immersed test code whose catalog includes dielectric tests.

Does a non-uniform winding use the line-terminal voltage for this test?

On non-uniform insulation the applied-voltage test uses the neutral-terminal voltage. LTAC or switching impulse takes the line terminal.

Does the S9-35 kV page publish an applied-voltage test kV?

The S9-35 kV series prints the ratings and IEC 60076-1-2-3 2000. An applied-voltage level stays unpublished there.