Current Transformer Diagram: What Specifiers Must Verify on the Drawing
A current transformer diagram is useful only when it lets you match the nameplate to the drawing—polarity, ratio, cores and classes, burden, and grounding—before anyone wires or buys. EPC reviewers reject incomplete prints early because missing marks force late change orders. The next sections cover symbol and polarity literacy, nameplate-to-drawing fields, a scoped indoor MV example, and a short acceptance checklist.

Contents
- What a Usable Current Transformer Diagram Must Show
- Current Transformer Symbols and Polarity Marks (P1/S1 vs H1/X1)
- Reading CT Ratio and Secondary Rating on the Drawing
- Cores, Accuracy Classes, and Burden on the Same Sheet
- Grounding and Open-Secondary Notes the Drawing Should Carry
- Example: Mapping an Indoor MV Multi-Core Nameplate to the Diagram
- Specifier Checklist Before Approving the Current Transformer Diagram
- Continue with Andeli Current Transformer Options
What a Usable Current Transformer Diagram Must Show
A usable diagram records polarity, ratio and secondary rating, cores and classes, burden, and grounding notes so hardware matches the scheme. A current transformer (CT) scales line current to a measurable secondary for meters and relays; the drawing is the contract that proves those jobs are assigned correctly.
When an EPC reviews a 12 kV indoor switchgear package, the print should answer five questions at a glance: which terminal faces the source, what ratio and secondary amperes are stated, which core serves metering versus protection, what VA burden is rated, and where secondary grounding is noted. If any of those answers is missing, the drawing is not ready for approval.
| Nameplate / scheme field | What the diagram must show | Why it matters in RFQ review |
|---|---|---|
| Polarity | Source-facing primary mark (P1 or H1) and matching secondary leave mark (S1 or X1) | Wrong polarity can reverse directional or differential relay sensing |
| Ratio and secondary | Rated primary:secondary current, usually ending in 1 A or 5 A | Instruments and relays expect the published secondary value |
| Cores and accuracy class | Each secondary core labeled metering or protection with its class | One unlabeled secondary cannot carry two duties |
| Burden | Rated output in VA for the connected instruments and leads | Accuracy claims hold only within rated burden |
| Grounding / secondary state | Single-point secondary ground note when required; closed or shorted secondary under primary current | Open secondary creates an open-circuit secondary hazard |
Current Transformer Symbols and Polarity Marks (P1/S1 vs H1/X1)
Pick a current transformer symbol that matches core count; mark source-facing polarity in the label system the drawing uses. Single-line sheets may show one secondary or several; a multi-core CT needs a dual-core or multi-secondary symbol so nobody assumes a single instrument circuit.

On many ANSI-style prints, H1 faces the source and X1 is the secondary leave terminal: primary current into H1 corresponds to secondary current out of X1. IEC-style sheets often print P1 / P2 / S1 / S2 (or K/L and k/l), with P1 toward the source. Current transformer polarity is not cosmetic: for directional or differential schemes, polarity on the diagram must match the relay expectation.

Tip: Field teams often ask whether every P1 must face upstream power flow. Switchgear layouts sometimes rotate labels for visibility, so the drawing and as-built notes must state the convention the relay scheme actually uses.
Reading CT Ratio and Secondary Rating on the Drawing
Read published primary:secondary current and copy that CT ratio onto the print without inventing values from generic examples. Nameplates and diagrams usually state a 1 A or 5 A secondary.
Read the published ratio as rated primary to rated secondary current, such as 300:5. A general education example such as 1000:5 illustrates the idea of proportional secondary current; it is not an Andeli model rating and should not be pasted onto a product-specific drawing.
When the secondary rating on the nameplate disagrees with the SLD, stop the review. Meters, transducers, and relays are sized for a stated secondary; changing that value on paper without matching hardware creates wrong scaling and wrong protection settings.
Cores, Accuracy Classes, and Burden on the Same Sheet
Label each secondary core’s class and rated burden (VA); metering and protection classes are not interchangeable. Drawings should state metering class and protection class separately when both exist.
IEC 61869-2 defines metering accuracy classes such as 0.2 and 0.2S used on nameplates and drawings. Protection classes such as 10P families describe performance under high fault multiples. Show each secondary core and its duty on the diagram so a specifier can see which circuit serves energy measurement and which serves relays.
Burden is the secondary load, often in VA, that bounds guaranteed accuracy. List rated burden (VA) that matches the connected instruments and leads. If a metering package’s VA exceeds the published burden, the accuracy statement on the nameplate cannot be accepted as drawn.
Grounding and Open-Secondary Notes the Drawing Should Carry
Note single-point secondary ground when required; keep the secondary closed or shorted under primary current. Secondary grounding often appears as one bonded point on MV inductive CT circuits, typically called out at S1, so circulating paths do not create measurement noise or safety gaps.
Keep the secondary closed on a burden or shorted before disconnecting instruments. An open secondary under primary current can drive hazardous voltage and damage insulation or terminal blocks. Scheme notes still need shorting provisions on the print even when wiring sequence is handled elsewhere.
Important: Never leave a CT secondary open while primary current is flowing. Treat that open-circuit secondary hazard as a print note, then follow site procedures for shorts and instrument swaps.
Example: Mapping an Indoor MV Multi-Core Nameplate to the Diagram
Map a real indoor multi-core nameplate onto the diagram fields before you accept the print. Use LZZBJ9-12 dual-class, VA, and ratio fields as a scoped indoor ≤12 kV example only. For example, an indoor 12 kV CT may publish combined classes such as 0.2S/10P15 with stated VA.

Use that indoor resin body as the worked hardware for the fields below.
The LZZBJ9-12 type current transformer is built for indoor metering and protection in 12 kV and below AC systems. On the LZZBJ9-12 type current transformer, rated output is 10 VA for 0.2S, 0.2, and 0.5 classes and 15 VA for 10P15 at cosφ=0.8.
Published ratios on this model span from 5/5 up to 800-2500/5. Published combinations include 0.2S/10P15, 0.2/10P15, and 0.5/10P15, so the diagram must label which secondary carries the metering accuracy class and which carries the protection class.
| LZZBJ9-12 nameplate field (scoped example) | Diagram acceptance check |
|---|---|
| Accuracy combinations 0.2S/10P15, 0.2/10P15, or 0.5/10P15 | Two secondaries (or cores) labeled metering vs protection with matching classes |
| Rated output 10 VA (0.2S/0.2/0.5) and 15 VA (10P15) at cosφ=0.8 | Burden notes match instrument VA plus lead allowance |
| Ratio options from 5/5 through 800-2500/5 | SLD ratio and secondary amperes match the selected row |
| Indoor ≤12 kV metering and protection application | Symbol and notes fit indoor MV switchgear duty, not outdoor CT assumptions |
Thermal and dynamic rows on the same product table are ratio-specific. For the 5/5 row, published examples include 0.8 kA thermal and 1.9 kA dynamic; for 300-600/5 they include 45 kA and 112.5 kA; for 800-2500/5 they include 63 kA and 157.5 kA. Copy those figures only with the matching ratio row—never from another model’s table.
Specifier Checklist Before Approving the Current Transformer Diagram
Approve only when polarity, ratio, cores/classes, burden, and grounding notes are present and consistent. Walk the print once as if you must defend the acceptance in a design review.
- Confirm the current transformer symbol matches single-core or multi-core hardware.
- Confirm polarity marks: P1 or H1 toward the stated source convention; S1 or X1 as the secondary leave mark.
- Confirm CT ratio and secondary amperes match the nameplate.
- Confirm each accuracy class and burden (VA) is tied to a labeled core or secondary.
- Confirm secondary grounding and closed-secondary / shorting notes appear where the scheme requires them.
- Reject the drawing if any of the five acceptance fields is blank, contradictory, or unlabeled.
If the residual question is how to sequence field connections, use a wiring-focused article such as what a current transformer wiring diagram must show first after the print itself is complete. Settle the nameplate-to-drawing match on the print first.
Continue with Andeli Current Transformer Options
Pick an indoor multi-core CT only after the diagram fields above already match the nameplate.
Choose the LZZBJ9-12 type current transformer when you need an indoor ≤12 kV metering-and-protection CT with the published dual-class and VA fields shown in the worked example. It is not the default for outdoor CT needs or for projects that require credentials Andeli pages do not publish.

Browse related indoor CT bodies on the current transformer hub after the print fields are settled.
FAQ
How does a current transformer work?
A current transformer produces secondary current proportional to primary line current so meters and relays can read a standardized value while staying isolated from the primary circuit. On the diagram, that relationship appears as the stated ratio, polarity marks, and the secondary cores that feed instruments or protection.
How do I wire a current transformer?
Before any field sequence, confirm the diagram already shows polarity, ratio, cores/classes, burden, and grounding notes that match the nameplate. Connection sequencing belongs in a separate wiring-diagram article; confirm those five print fields first.
Which direction are P1 and P2 on a CT?
On common IEC-style installs, P1 faces the source and P2 faces the load or consumer side. If switchgear orientation differs for label visibility, the drawing and as-built notes must still state the convention the protection scheme expects.
What do H1 and X1 mean on a CT drawing?
H1 is the source-facing primary polarity mark on many ANSI-style drawings, and X1 is the secondary terminal that secondary current leaves when primary current enters H1. The same instantaneous direction idea appears under P1/S1 marking systems.
Why must the CT secondary stay closed?
With primary current flowing, an open secondary can induce hazardous voltage and damage insulation or terminal blocks. Keep the secondary on its burden or use shorting provisions before removing meters or relays.
How do metering and protection classes appear on one diagram?
Show each secondary core with its duty and class—for example metering 0.2S beside protection 10P15 on a dual-class indoor unit. Never leave a single unlabeled secondary when the nameplate publishes a combined metering/protection pair.
What is CT burden and why is it on the drawing?
Burden is the secondary load, usually stated in VA, that the CT must drive while still meeting its accuracy class. The drawing should list rated burden so instrument VA and lead losses stay inside that limit.
What is the most common use of a CT?
The most common plant uses are metering (energy and current measurement) and protection (relay inputs), often on separate cores of one multi-core CT. The diagram must show which secondary serves which job.