Custom Bus Work for Retrofit Dry Type Transformer

2026-10-06

The job in custom bus work for retrofit dry type transformer is the Retrofit dry-type bus interface: build the outgoing connection so the new unit lands on the lineup that stays. A conventional exit, standard enclosed busbar outgoing lines, or a side exit can be a catalog form, and a special outgoing line is defined when the standing gear asks for a landing those forms miss. Side versus top, and the choice of shell, still leave the transformer throat and the phase marks to be read from that lineup.

The old transformer comes out. The switchgear, the bus run, and the floor marks stay, and the replacement has to meet those marks. A buyer who already has that lineup is choosing an interface, and the winding family is already settled by the unit being installed.

Public retrofit pages often stop once they say the new bars should line up with the existing low-voltage gear. That lining-up is the job. The series page goes further and names the outgoing forms a shop can actually order, which is the split those pages leave out.

Three red coils on a blue frame with copper links between the coils and a silver housing along the base

What Custom Bus Work Means on a Retrofit

Custom bus work on a retrofit is the connection that makes the new transformer meet landing points that already exist, while the transformer itself is the rest of the replacement.

ELSCO describes custom bus work as the bus-bar portion of a retrofit, lined up with existing connection points and low-voltage gear. That vendor also treats high-voltage cabling as the high-voltage run when that side is cable. Andeli's printed words on this series are outgoing lines and standard bus bars, so the choice here stays on those words rather than on a service slogan.

A terminal is the conducting element that connects the transformer to an external conductor that is not part of the transformer. The definition, from the distribution-transformer rules, names the joint between the unit and a conductor that belongs to the lineup. It does not pick a side, a top, or a throat.

A plant that keeps the same switchgear and only swaps the transformer is the scene this job describes. The connection points, the gear, and the floor elevation are already built. The outgoing form has to agree with them, or the user has to describe a special line because none of the catalog exits will land.

The gallery frame above is the open coil assembly, with copper links between the coils and bars along the top of the frame. Those parts are the transformer. A finished joint into a switchgear lineup, and a throat flange, sit outside this frame.

Standard Outgoing versus Special Outgoing

Conventional outgoing lines, an enclosed-busbar exit, and a side exit are catalog forms, and a special outgoing line is the form the user has to define.

The four outgoing forms on the series page are conventional outgoing lines, standard enclosed busbar outgoing lines, standard side outgoing lines, and special outgoing lines designed to user requirements.

The catalog name Standard enclosed busbar outgoing line is the enclosed-busbar exit the series page says it can build. A buyer whose lineup is already enclosed bus starts there and compares that exit with the throat on the gear. When the phase spacing or the landing height will not meet that catalog exit, the order moves to a special outgoing line, and the user has to describe the landing.

Printed form Catalog status on the series page Still taken from the lineup
Conventional outgoing lines Named as a manufacturable interface form Which face and landing the gear already uses
Standard enclosed busbar outgoing line Named as an enclosed-busbar catalog exit Whether the run is metal-enclosed bus and how the throat is built
Standard side outgoing lines Named as a side catalog exit Whether the low-voltage bars leave on the side
Special outgoing line Designed to user requirements Geometry the catalog forms miss

Catalog names and their status sit beside the landing the gear still has to supply. The user describes that landing when a catalog form will not fit.

Three red coils in a blue frame with bars across the top and a blue cover on the right side

The photograph shows bars across the top of the coils and a blue cover on one side of the frame. That hardware is part of the transformer assembly. A flange bolted to switchgear sits outside this frame, so the photo stops short of a completed enclosed-bus joint.

Side versus Top LV Bus

Side and top LV outgoing are the two low-voltage directions this series prints, so the bars leave from the side or from the top according to the face the lineup already presents.

Side and top outgoing can both be used for the low voltage bus bars, and special methods can be designed when the user defines them.

Low voltage bus bars on this page are the standard bars for the low-voltage outgoing. They are the joint toward the low-voltage gear. High-voltage cabling, when the high-voltage side is cable, is a different run and should not be mixed into the same face decision.

Installers sometimes want the secondary out of the rear cover and straight into a panel. Others say they have only seen side exits on small dry-type units, and one later note on a different unit described lugs up at the coils under a sticker that warned against wiring above a marked line.

Another question asks whether bus duct can leave the bottom of a terminal box instead of the top. Rear and bottom are user questions. The series page prints side and top, and it does not print rear or bottom as standard forms.

Look at the face the existing gear presents. If that face is the side or the top, the printed low-voltage options already name it.

If someone needs the rear or the bottom, that request is a special method the user has to describe, and the page does not list it as a catalog exit.

Enclosure IP20/IP23 versus an Open Coil

An IP20 / IP23 casing is the shell around the coils, and choosing that shell still leaves the lineup bus to be matched on its own.

The series page names those two protection levels and three casing metals: cold-rolled steel, stainless steel, and aluminum alloy. An open coil is the same kind of unit with the windings visible, which is what the gallery frames show.

A shell hides those windings. The bus joint on the gear is outside either choice.

MGM's bulletin says retrofit designs can be supplied with an enclosure or without one. That comment belongs to MGM. It supports the split between a cased unit and an open coil, and the casing level stays off the switchgear bus.

Normal service for this series is indoor. High buildings, airports, substations, and commercial centers are the places the application text names.

An outdoor throat, a wet pad-mount bottom entry, or a yard lineup sits outside that indoor service. Air temperature and altitude from the service block are collected with the voltages in the table farther down, and they stay with indoor use.

Three red coils clamped in blue steel with top connections and a long silver housing at the base

This frame is another open view of the coils, the top connections, and the housing along the base. The view is the unit before a casing is discussed. An IP shell and a switchgear throat sit outside this photograph.

What the Existing Lineup Forces You to Match

The existing lineup forces the landing: spacing, phasing, floor-to-bus height, and whether the run is a throat or a cable chamber.

Nonsegregated-phase bus is one metal-enclosed bus type named on the IEEE C37.23 abstract, along with cable bus, segregated-phase bus, and isolated-phase bus. A lineup that already uses that bus is the case where the new transformer has to meet a bus termination.

The abstract page records that edition as inactive-reserved. The usable fact is the bus-type name, and the abstract stops before any throat drawing.

Transformer throat is the flange a metal-enclosed bus termination is built to meet. Eaton describes the transformer termination as a flange with flexible copper braids to the bushing pads, drilled or undrilled for the given transformer.

Drilling follows the transformer being matched. Eaton's voltage list and expansion-joint gap stay with Eaton's bus duct.

Important: On a Mike Holt thread, one electrician wrote that the existing gear must have a bus duct throat, and another split that throat from an air terminal chamber used when the run becomes cable.

That split is user language from one switchgear thread. If the run stays bus, the throat is the interface people on that thread expect to find. If the run is being changed to cable, they look for an air terminal chamber instead.

Treat the thread as user language. The ampacity in the original post belongs to that poster's project.

Olsun says primary and secondary throats on a liquid-filled unit may not be required for the dry-type retrofit. MGM says coordination to the switchgear may require a transition throat, and that flex connectors can be supplied.

The two comments are competing manufacturer statements. Andeli's page leaves both comments off its printed rules.

People who measure retrofits ask for floor-to-bus height, breaker positions, motor-control-center locations, photos, connection-point distances, and enclosure size. Olsun's list adds impulse level, primary and secondary termination details, location, spacing, and phasing, plus a picture.

The series page leaves that list off any printed order form. The lineup still holds those facts, and a special outgoing line is where the user writes them down when a catalog form will not land.

The lineup also has to leave a path to take the transformer out later, and bolted joints have to be tightened to the manufacturer's instructions. Clearance figures from a low-voltage installation paper stay with that paper. A nonstandard phase order has to be read off the existing bus and identified on the new joint, because a fresh front-to-back habit can reverse an arrangement the gear already uses.

What Andeli Prints and What It Does Not Print

The SCB series page prints the outgoing menu and the casing levels, and it leaves the throat drawing off the page.

The outgoing menu is printed on the SCB series dry-type transformer page.

The product named here is the SC(B) 6–10 kV dry-type.

The series sits in the transformer catalog as an indoor resin-insulated unit for high buildings, airports, substations, and commercial centers. The application text names a NOMEX paper insulation system for that transformer. The paper belongs to the winding insulation, and the bus bars are a separate metal joint.

Throat size, bus ampacity, flange drilling, a short-circuit rating, a UL mark, and a retrofit bus SKU are absent from that page.

The series tables print the electrical set below. Read that set as the identity of the transformer being dropped in. Read the bus interface from the outgoing menu and from the lineup, not from this voltage list alone.

Printed item Value on the series tables
High voltage 6, 6.3, 6.6, 10, 10.5, 11 kV
Taps ±2×2.5% and ±5%
Low voltage 0.4 kV
Connection group Dyn11 or Yyn0
Service place indoor
Highest air +40°C
Lowest air -5°C
Altitude below 1000 m

Open that product page when the decision is which printed outgoing form to compare with the lineup. Skip it when the job needs a published throat drawing, a bus ampacity, or a listed retrofit bus assembly, because those items are absent there. Take spacing, phasing, and the throat-versus-cable choice from the existing lineup, then describe a special outgoing line if the catalog forms miss the landing.

Diagram of three red coils with leader lines to the top bars, leads, base fan, and mounting feet

The diagram marks the top bars, the leads, the fan along the base, and the mounting feet. Use it to recognize the unit whose page carries the outgoing menu. The leader lines name parts on the unit, and a throat flange or a switchgear lineup sits outside the frame.

FAQs

What does custom bus work mean when the dry-type is a retrofit into an existing lineup?

It means the outgoing interface that has to meet connection points, gear, and floor marks that stay when the transformer is replaced. The dry-type is already the replacement unit. The bus work is how that unit lands.

A service page may call the whole replacement a retrofit and the bar work a narrower piece of it. On this series, the practical reading is the outgoing form: a catalog exit, or a special line the user describes from the lineup.

How is a standard enclosed busbar outgoing line different from a special outgoing line?

A standard enclosed busbar outgoing line is a catalog form the series page says it can build, next to conventional outgoing lines and standard side outgoing lines. A special outgoing line is designed to user requirements when those catalog forms miss the landing on the gear.

The difference shows up when the lineup is already enclosed bus. Start with the catalog enclosed-busbar exit. Move to a user-defined line only when the throat, the spacing, or the landing height will not agree with that exit.

When does the low-voltage side leave from the side, and when from the top?

It leaves from the side when the existing gear presents a side face, and from the top when the gear presents a top face. Both directions are printed for the low voltage bus bars on this series.

Rear and bottom show up when an installer wants the secondary out the back or bus duct out the bottom of a terminal box. Those faces are user questions. They are outside the printed standard forms, so they belong in a special method the user has to describe.

Does an IP20 or IP23 casing replace the need to match the lineup bus?

No. The casing is the shell around the coils, in cold-rolled steel, stainless steel, or aluminum alloy, at the protection levels the page names. The lineup bus is a separate interface.

An open coil and a cased unit can both still need a throat, a flex link, or a cable chamber, depending on what the gear already is. The shell choice does not settle that landing.

What does the existing lineup force you to match?

Spacing, phasing, floor-to-bus height, and the choice between a throat and a cable chamber. Photos, connection-point distances, enclosure size, and termination details come from the gear as well.

The series page can name a catalog outgoing form. The flange on a lineup that is already built has to be read on site.

If the run is bus, electricians on a public thread expect a bus duct throat. If the run becomes cable, they look for an air terminal chamber.

What does the Andeli SCB page print about bus work, and what does it leave off?

It prints conventional outgoing lines, standard enclosed busbar outgoing lines, standard side outgoing lines, and special outgoing lines to user requirements. It also prints side and top low-voltage bus bars, plus IP20 and IP23 casings in the three metals named above.

It leaves off a retrofit bus SKU, throat size, bus ampacity, flange drilling, a short-circuit rating, and a UL mark. Those gaps are why a special outgoing line still needs a description from the lineup.

If the old unit was liquid-filled, do the primary and secondary throats have to stay?

Olsun says primary and secondary throats on the liquid-filled unit may not be required on the dry-type retrofit. MGM says coordination with the switchgear may still require a transition throat, and that flex connectors can be supplied.

Hold both as competing manufacturer statements. Neither statement is printed as an Andeli rule. The lineup, and the outgoing form chosen for it, still decide whether a throat stays, drops, or is replaced by a transition piece.

Can a nonstandard phase order on the existing bus simply be ignored?

No. The phase order on the existing bus has to be matched and identified, because the gear may already carry an arrangement a new front-to-back habit would reverse.

A Physics Forums poster worried about that kind of existing arrangement and about whether it still has to be marked. The code book was not opened, so the thread stays user language. The usable point is the worry itself: read the marks on the bus that stays.

References

  • 10 CFR Part 431 Subpart K defines a terminal as the conducting element that connects a distribution transformer to an external conductor that is not part of the transformer: https://www.ecfr.gov/current/title-10/chapter-II/subchapter-D/part-431/subpart-K.
  • The IEEE C37.23 abstract names nonsegregated-phase bus among metal-enclosed bus types and records that edition as inactive-reserved: https://standards.ieee.org/ieee/C37.23/5577/.
  • A Physics Forums poster asked whether a nonstandard phase order on an existing bus can be left unmarked, which is the user worry kept here: https://www.physicsforums.com/threads/nec-408-3-e-3-phase-busbar-arrangement.363511/.