Dry-Type Transformers vs. Oil-Immersed Transformers: Differences and Application Scenarios
In the power distribution system, dry-type transformers and oil-immersed transformers are two of the most common types. However, when it comes to selecting the right type for actual projects, many people tend to get confused or are not clear about when to choose a dry-type transformer and when to choose an oil-immersed one. Today, we will break down the differences between the two from three dimensions: product differences, advantage comparisons, and application scenarios.
1.The core differences between dry-type transformers and oil-immersed transformers
The appearance differences between dry-type transformers and oil-immersed transformers are quite obvious. The outer coils of dry-type transformers are usually filled with epoxy resin, and the red epoxy resin material is very conspicuous and easy to identify.
From the outside, an oil-immersed transformer appears as a fully sealed metal casing. Inside the box, insulating oil is added. The vertical grids are the heat dissipation fins of the transformer, distributed around the box.
The main differences between dry-type transformers and oil-immersed transformers are as follows:
Product structure differences: In dry-type transformers, the core and coil windings can be directly observed. For oil-immersed transformers, the core and windings are completely submerged in a sealed oil tank.
Insulation medium differences: Dry-type transformers rely on solid materials such as epoxy resin and insulating paper for insulation; oil-immersed transformers mainly achieve insulation and heat dissipation through the flow of oil.
Thermal dissipation method differences: Dry-type transformers have two cooling methods: natural air cooling and forced air cooling. When the temperature reaches the set value, the fan below the transformer starts to dissipate heat; for oil-immersed transformers, the heat dissipation mainly relies on the natural circulation of the internal oil, which transfers the heat to the heat dissipation fins on the outer shell for release.
Product size difference: For the same capacity specification, the volume of the oil version is generally larger than that of the dry version.
Voltage level difference: The voltage level of dry-type transformers is generally below 35kv, while oil-immersed transformers can cover all voltage levels.
Product capacity difference: The capacity of dry-type transformers is generally below 3150 kVA, while the capacity of oil-immersed transformers is not limited.
Overload capacity difference: Compared to dry-type transformers, oil-immersed transformers have a stronger overload capacity.
2.Comparison of the advantages of dry-type transformers and oil-immersed transformers
In comparison, the manufacturing process of dry-type transformers is more complex. They require epoxy resin pouring through a vacuum pouring equipment, followed by multiple processing steps such as drying and demolding. The overall production cost is relatively high.
In terms of product features, the advantages of dry-type transformers are as follows:
1.Fireproof and explosion-proof, with high safety performance
2.The materials are environmentally friendly and pollution-free
3.No maintenance required, saving costs in the long run
Oil-immersed transformers also have their unique advantages:
1.Voltage and capacity are not limited
2.Strong overload capacity, capable of supporting high-load operation
3.Sealed structure, moisture-proof and dust-proof, resistant to rain and snow, with strong environmental adaptability
In terms of product installation, dry-type transformers can be installed side by side with the distribution cabinets, thus saving more space; for oil-immersed transformers, an oil tank needs to be set up for installation. Considering safety, they are usually installed outdoors or in separate distribution rooms.
| Product Comparison | Dry-Type Transformer | Oil-Immersed Transformer |
| Appearance | Core and windings visible, epoxy resin in prominent red | Only enclosure visible, usually silver-gray paint, some models with oil conservator |
| Insulation | Solid insulating materials such as epoxy resin, insulating paper | Core and windings immersed in transformer oil inside tank, liquid insulation |
| Heat Dissipation | Natural air cooling + fan cooling | Internal circulation of transformer oil for heat dissipation |
| Terminals | Rubber bushings | Porcelain bushings |
| Voltage Rating | 10kV, 20kV, 35kV | Suitable for various voltage levels, including UHV up to 1000kV |
| Capacity Specification | Generally capacity ≤ 3150kVA | Unlimited |
| Overload Capacity | Recommended to operate at rated capacity | Good overload capacity |
| Product Features | Fire and explosion-proof, high safety; environmentally friendly materials, pollution-free; maintenance-free | Sealed structure, moisture and dust resistant, unaffected by rain or snow, strong environmental adaptability |
| Size & Weight | Compact size, light weight (compared to oil-immersed type) | Large size, heavy weight (compared to dry-type) |
| Installation | Can share switchgear room with distribution cabinets, more space-saving | Requires oil containment pit, installed outdoors or in a separate transformer room |
3.The application scenarios of dry-type transformers and oil-immersed transformers
The classification of application scenarios for dry-type transformers and oil-immersed transformers is not absolutely fixed.
Dry-type transformers have the characteristics of being oil-free, fireproof and explosion-proof. They are suitable for installation in indoor environments, especially in places with high population density and strict safety requirements. Typical application scenarios include: residential communities, commercial complexes, office buildings, data centers, hospitals, schools, stations, etc.
Oil-immersed transformers are widely used in outdoor substations and heavy industry due to their unrestricted voltage levels and capacities. Additionally, oil-immersed transformers adopt a fully sealed structure, which is more adaptable to harsh environments such as sandstorms, rain, snow, and high temperatures, and are particularly suitable for outdoor use. Typical application scenarios include: power plants, substations, urban and rural power grids, heavy industrial enterprises, wind power, and photovoltaic projects, etc.
In simple terms, dry-type transformers are suitable for indoor environments and those with high safety requirements; while oil-immersed transformers are suitable for outdoor settings, and are widely used in areas such as power grids and heavy industries.
| Applicable Scenarios | Dry-Type Transformer | Oil-Immersed Transformer |
| Scenario Description | Indoor & High-Safety Requirement Locations | Outdoor & Industrial/Power Grid Side |
| Typical Applications | Commercial Centers, Office Buildings,Hospitals, Schools, Airports, Subway Stations,Data Centers,Residential Community Distribution Rooms | Power Plants, Substations,Large Industrial Parks/Factories,Urban & Rural Power Grids,New Energy Wind/PV Projects |
4.Safe and stable. Made by Andeli
Transformer selection is only the first step; reliable manufacturing processes are the cornerstone for safe operation.
As a 40-year-old transformer factory, Andeli Electric has always placed quality at the top priority. Its products have passed certifications from the national power grid, the European Union, and other globally recognized bodies, and have accumulated a rich reputation for quality.
If you are looking for a reliable supplier for transformer production, we sincerely invite you to visit and inspect our factory, and discuss cooperation with us!














