Magnetising Current Test of Transformer
A magnetising current test of transformer is an open-circuit screening measurement of exciting current that checks magnetic-circuit and related winding/tap health by comparing phase readings and baselines. Crews usually run it before DC winding resistance, or demagnetise afterward, so residual flux does not fake a failure. The sections below cover setup cues, phase-pattern literacy, residual-magnetism order, fences versus magnetic-balance / power-factor / CT work, and published MV oil-immersed ratings that feed the same vocabulary.

Contents
- What the Magnetising (Excitation) Current Test Proves
- Open-Circuit Setup Cues: Isolation, Open Windings, Taps, and Test Side
- Reading Phase Patterns and Baselines
- Residual Magnetism and Test Order
- What This Test Is Not: Magnetic Balance, Power Factor, and CT Curves
- When to Escalate Beyond Excitation Current
- When Published Oil-Immersed Product Ratings Feed the Test
- FAQ
- References
What the Magnetising (Excitation) Current Test Proves
It screens magnetic-circuit and related winding/tap paths by measuring open-circuit exciting current—not a full insulation verdict.
On a three-phase power or distribution unit, the Magnetising current test (also called an excitation current test or excitation / exciting current test) energises one winding with other windings open and records the current drawn. Industry education frames that reading as a way to locate defects that change magnetic-circuit reluctance: core laminations and joints, winding shift, inter-turn insulation trouble, and Tap changer effects.
In plain terms, you are watching a no-load style milliamp or amp reading to see whether the magnetic path and related windings look consistent with prior work. The measured total is often called no-load current (Io); it includes a magnetising (reactive) component and a core-loss component.
Transformer excitation current write-ups treat Im as typically about 0.25–5% of full-load current, with some special designs near 10%. Factory and routine no-load booklets often place measured no-load current around 1–5% of rated current for small power transformers and about 0.1–0.3% for large units.
Those bands explain order of magnitude only. They do not replace a site procedure, nameplate data, or a prior commissioning baseline for the asset in front of you.
Open-Circuit Setup Cues: Isolation, Open Windings, Taps, and Test Side
Energise one winding with others open, record tap positions, and treat voltage and test-side choice as procedure-dependent.
A practical magnetizing current test procedure starts with isolation and lockout that match your site rules. Keep untested windings open-circuited so the measurement stays an open-circuit / no-load style check rather than a loaded ratio test.
Record Tap changer position on every run. Educational field write-ups commonly repeat lowest, normal, and highest tap so a sticking or mis-set tap does not hide inside a single reading.
Voltage choice is procedure-dependent. Workshop-style notes often show about 415 V three-phase or 230 V single-phase / phase-voltage examples; field diagnostic practice for power transformers also describes HV-side open-circuit excitation, often at rated frequency with voltages commonly up to about 10 kV, other windings floating except where a grounded neutral is required.
Decide HV versus LV test side from the approved method for that unit class—not from a universal “always LV” or “always HV” slogan. Log ambient conditions, instrument range, and which bushings were energised so the next crew can compare like with like.

Reading Phase Patterns and Baselines
Compare phases and prior or factory baselines; treat two-high/one-low patterns and percent guidance as conditional cues.
On many three-limb cores, outer-limb phases read similarly higher while the centre limb reads lower. That two-high / one-low shape can be a normal magnetic-path fingerprint, not automatic condemnation.
Educational sources often treat agreement within about 30% of a previous test as satisfactory and flag roughly 50× the factory exciting current as warranting further analysis. Service notes sometimes say phase-to-phase difference generally should not exceed 30% on the same run. Instrument OEM guidance tables may cite symmetrical phases within 5% for exciting current while still noting the same two-high / one-low pattern.
Those percentages sit in different guidance sources. Use them as screening language beside the asset’s own history—not as a single branded acceptance law.
| Cue | What crews often see | How to use it |
|---|---|---|
| Typical three-limb pattern | Two similar higher outer-limb currents; one lower centre-limb current | Confirm against this unit’s prior or factory shape before calling a fault |
| Versus prior test | About 30% agreement with previous often treated as satisfactory in educational guidance | Investigate larger unexplained shifts after residual-magnetism checks |
| Versus factory | About 50× factory exciting current called out for investigation | Escalate; do not stop at one milliamp snapshot |
| OEM symmetry cue | Symmetrical phases within 5% in some exciting-current guidance tables | Contrast with 30% educational figures; match the method you actually used |
| Pattern labels (HLH / LHL) | Design-dependent screening shorthand | Treat as labels to escalate from, not a universal fault dictionary |
When a commissioning crew screens a three-phase distribution transformer before energisation, the decision is comparative: does today’s R/Y/B set still look like yesterday’s set and the magnetic core / laminations story you expect for that design?

Residual Magnetism and Test Order
Run excitation before DC winding resistance—or demagnetise—because residual flux can distort exciting-current readings.

From the field: After DC winding-resistance work, residual magnetism can leave the core “remembering” flux and skew the next excitation reading. Substation crews who discuss test order keep saying the same operational point: do exciting current before winding resistance when both are on the plan, and demagnetise when DC work has already magnetised the core. — source: transformer testing education on excitation-before-DC-resistance residual-magnetism practice.
Educational transformer-testing sections state the magnetising / excitation run should be carried out before DC resistance measurement for the same reason. Field teams that already see a false fail on a previously DC-tested unit usually demagnetise with an approved decaying AC method, then re-run excitation before trusting pass/fail language.
| Check | Prefer | Invalidates or weakens the reading |
|---|---|---|
| Test order | Excitation / exciting current before DC winding resistance | DC winding resistance first with no demagnetisation |
| After WRM | Demagnetise, then re-measure excitation | Treating the post-WR excitation set as a clean baseline |
| Insulation resistance (Megger-style) | Usually does not magnetise the core when done correctly | Confusing IR sequence with WRM magnetisation risk |
| Documentation | Note demag status next to milliamp values | Orphan readings with no order or demag note |
Residual magnetism is a confounder, not a core defect by itself. Clear the confounder before you escalate into expensive teardown language.
What This Test Is Not: Magnetic Balance, Power Factor, and CT Curves
Magnetising / excitation current screening answers a different question than magnetic-balance, power-factor / tan-δ insulation, or CT knee-point tests.
Magnetic balance looks at voltage/current sharing among windings for a related but distinct screening question. Do not collapse MBT and magnetising current into one meter reading just because both mention “magnetic.”
A Power-factor / tan-δ test evaluates insulation dielectric behaviour. Exciting-current pattern literacy does not certify insulation power factor, and a healthy PF result does not prove the magnetic circuit looks normal on an open-circuit excitation set.
A Current transformer excitation curve characterises an instrument transformer’s knee-point behaviour. That is a different asset class and a different procedure from a power or distribution transformer magnetising current screen.
When a specifying engineer refuses to treat excitation milliamps as a power-factor insulation pass, that fence protects both the test plan and the procurement conversation. Magnetic-balance, power-factor, and CT curve procedures belong in their own commissioning packages.
When to Escalate Beyond Excitation Current
Abnormal or unexplained patterns escalate to TTR, winding resistance (after a demag plan), and other diagnostics—not more of the same single reading.
Escalate when phase asymmetry breaks the unit’s expected pattern after residual magnetism is ruled out, when versus-prior or versus-factory guidance thresholds are clearly exceeded without a method change, or when tap positions do not explain the shift.
Typical next steps named in comparative excitation guidance include turns-ratio (TTR), winding resistance after an explicit demagnetisation plan, and other diagnostics the site procedure already owns. Pattern labels such as HLH/LHL remain design-dependent screening language; they point you toward follow-on tests rather than naming the exact fault by themselves.
If the reading is still unstable after demag and a clean re-run, stop stacking identical excitation shots. Change the diagnostic question.
When Published Oil-Immersed Product Ratings Feed the Test
Published nameplate and table values for a 6–10 kV oil-immersed distribution transformer supply Dyn11 / GB 1094 / no-load current % context for this vocabulary—they are selection facts, not a field-kit or certified excitation-test platform claim.

Buyers who finish excitation-test literacy often evaluate an Oil-immersed distribution transformer 6–10 kV for feeder and plant distribution work. Andeli’s published 6–10 kV series oil-immersed distribution transformer is a sealed oil distribution family with cold-rolled silicon-steel core construction and OF copper windings.
Published connection groups include the Dyn11 vector group plus Yzn11 and Yyn0. Standards named on that product page include GB 1094.1-2013, GB 1094.2-2013, GB 1094.3-2017, GB 1094.5-2008, and GB/T 6451-2015 under the broader GB 1094 series naming used on the page.
Published HV combination examples include 11 / 10.5 / 10 / 6.3 / 6 kV with LV 0.4 kV in the distribution table. Normal service conditions on the page list altitude below 1000 m, ambient max +40 °C, and outdoor min −25 °C.
Published S11 no-load current examples on the same table include 1.5% at 30 kVA, 1.1% at 100 kVA, 0.6% at 630 kVA, and 0.4% at 2500 kVA. Those percentages are nameplate/table context for no-load / exciting-current vocabulary; they are not a field kit acceptance oracle for your excitation instrument.
Browse the transformer hub for the wider family, then return to commissioning with residual-magnetism literacy still in hand. The brand home is at andelipower.com.
FAQ
What does a magnetising current test of a transformer actually check?
It screens for magnetic-circuit and related issues—core structure, winding shift, inter-turn insulation concerns, and Tap changer effects—by measuring open-circuit exciting current and comparing phases and baselines.
How do you perform the test step by step?
Isolate the unit, open untested windings, set and record taps, apply the procedure’s AC voltage on the chosen side, measure each phase, and log results before any DC winding-resistance work when both tests are planned. That sequence is the core magnetizing current test procedure crews follow in the field.
What does a normal three-phase reading pattern look like?
Many three-limb designs show two similar higher outer-limb currents and one lower centre-limb current; always confirm that shape against the unit’s own prior or factory pattern.
What percent difference is a problem?
Educational guidance often cites about 30% versus a previous test and roughly 50× factory as investigation triggers, while some OEM exciting-current tables cite 5% phase symmetry—treat each figure as conditional guidance for its source method.
Why must this test come before DC winding resistance?
DC winding resistance can leave residual magnetism that distorts the next excitation reading, so run excitation first or demagnetise before trusting a post-WR set.
Is this the same as a magnetic balance test or a power-factor test?
No. Magnetic balance is a related but distinct screen, and power-factor / tan-δ answers an insulation question rather than open-circuit excitation pattern health.
How is magnetising current calculated from an open-circuit test?
Open-circuit measurement yields Io; educational splits describe Io ≈ Im + core-loss component, and Im ≈ V/(2πf Lm) appears in calculation literacy—field acceptance still leans on measured baselines more than a single formula.
Does this apply to instrument CTs?
A power/distribution magnetising current screen is not a CT excitation-curve / knee-point test; instrument CTs need their own excitation procedure.
Where do published no-load current % values appear for Andeli 6–10 kV oil-immersed units?
On the published 6–10 kV series oil-immersed distribution transformer tables (for example S11 30 kVA at 1.5% and 100 kVA at 1.1%), as nameplate/table context only.
What is the 80% rule for transformers?
That loading rule is outside this excitation-current topic; stay with open-circuit magnetising / excitation screening here rather than feeder loading heuristics.
What is the formula for calculating transformer current?
Rated load current and magnetising / excitation current answer different questions—use nameplate ampacity for loading, and open-circuit excitation readings for magnetic-circuit screening.
References
- Transformer Excitation Current — Voltage Disturbance (independent technical overview of excitation components and open-circuit purpose).
- Power Transformers Testing Booklet for True Engineers (PDF) — Electrical Engineering Portal booklet ranges for no-load current magnitude.
- Simple ageless methods for field testing power transformers, Part II (preview PDF) — Transformer Magazine field notes on excitation current as an open-circuit HV-side screen.
- Why does a transformer still have magnetizing current when loaded? — Physics Forums community discussion clarifying that magnetizing current remains present to sustain core flux.