Reading a Medium Voltage Transformer Fuse Sizing Chart the Specifier Way
A medium voltage transformer fuse sizing chart is a family-locked lookup tool: you read ampere cells only after matching voltage band, fuse type, and the maker’s notes to your nameplate full-load current, inrush hold, and code-maximum ceiling. Paste an anonymous blog ampere into the wrong chart family and you get a fuse that nuisances on energize—or sits too high to protect the winding. Specifiers start with chart-family lock and nameplate inputs, then check inrush and E-rating floors against the code-max ceiling—and only then ask which published 6–10 kV oil-immersed fields can feed a fuse OEM table.

Contents
- Lock the chart family before you read any ampere cell
- Gather nameplate and system inputs before the first chart row
- Check magnetizing inrush and E-rating before accepting a chart ampere
- Treat code-maximum size as a ceiling, not the chart answer
- Stop when the published table is the wrong artifact
- Product Fit: When Published Oil-Immersed Distribution Data Feeds the Fuse Chart
- FAQ
- References
Lock the chart family before you read any ampere cell
Read the table title and notes first; a medium-voltage transformer fuse sizing chart is family-specific. Overhead cutout fuse-link schedules, indoor E-rated current-limiting catalogs, IEC RMU switch-fuse schedules, and LV control-circuit VA charts can share the words “transformer” and “fuse,” yet they are different species of MV transformer fuse selection table.
Imagine an EPC inbox PDF titled “transformer fusing” that is actually a construction fuse-link schedule for overhead pots. That packet is useful for its own link types; it is the wrong grid for an indoor E-rated primary on a pad-mount.
| Chart family | Typical voltage class | What the table assumes | Wrong artifact when… |
|---|---|---|---|
| Construction fuse-link (cutout) | Often single-phase line voltages through distribution MV | Link carries transformer full load and opens on a stated overload multiple in minutes | You need an indoor E-rated current-limiting barrel for a metal-enclosed bay |
| E-rated MV power fuse | Named primary voltage bands (for example 2400–13200 V charts) | Catalog E-rating, mounting, and inrush notes for that maker | You copy one maker’s E cell into another brand’s speed curve |
| IEC RMU switch-fuse | Network voltage × transformer kVA for a named RMU | Named fuse brands, ambient band, often “no overload” | You treat an RMU schedule as a universal US primary fuse table |
| Control-circuit fuse chart | ≤600 V Class CC / midget, VA-sized | NEC 450.3(B)-style control transformer rules | You apply it to a medium-voltage distribution primary |
A control-circuit fuse chart belongs to panel and control-power work; keep it out of medium-voltage primary selection. Brand-locked RMU notes (named fuse types, temperature band, no overload) also stay inside that switchgear family.

Gather nameplate and system inputs before the first chart row
You need rated kVA, primary voltage, phases, connection/vector, impedance band, and mounting or location notes before opening columns. Transformer primary full-load current is the continuous primary ampere at rated kVA and voltage—the number that lines up with a transformer primary fuse sizing chart row after you lock the family.
For three-phase units, FLA = kVA × 1000 / (√3 × VLL). One-phase work uses kVA × 1000 / V. Vector group / connection matters because closed-delta, open-delta, and wye legs are not interchangeable on construction fuse-link tables; some bulletins size the largest transformer on a closed-delta lead.
Percent impedance on the nameplate feeds fault-duty estimates and some code location bands later; it is not itself a fuse ampere. Also record whether the fuse sits outdoors without enclosure, indoors in a switch, or on a utility cutout—those columns change which chart page applies.
| Pre-lookup input | Why it matters | Worked pattern (attributed example only) |
|---|---|---|
| Rated kVA | Selects the chart row band | 300 kVA three-phase |
| Primary voltage | Opens the correct voltage page | 4160 V line-to-line |
| Calculated FLA | Baseline continuous current | 42 A on that Mersen 4160 V example |
| Chart cell in that bulletin | Maker-specific recommendation | Typical 65E in that Mersen AP14 example—not a universal industry ampere |
A plant engineer with 300 kVA at 4160 V primary can use that FLA-to-row pattern inside the matching E-rated bulletin. Pasting “65E” onto another maker’s barrel ignores speed, mounting, and interrupting rating differences.

Check magnetizing inrush and E-rating before accepting a chart ampere
The fuse must ride through magnetizing inrush at the chart’s hold points and match E-rating open-time bands—not merely equal FLA. Magnetizing inrush is the short high current when the transformer is energized; charts and notes often hold twelve times FLA at 0.1 s and higher multiples at shorter times.
One Mersen transformer-protection bulletin states its typical charts will carry magnetizing inrush of 25× FLA for 0.01 s and 12× FLA for 0.1 s. A Basler transformer-protection application guide hosted by IEEE PES repeats the classical 12× FLA for 0.1 s measure and notes fuses are a common choice below 10 MVA. IEEE section training slides put the same idea on a time-current curve: inrush must sit left of the fuse melting curve.
An E-rated fuse is a NEMA/general-purpose MV power fuse whose E number tracks defined open-time bands at stated percentages of rating. As summarized in a Littelfuse medium-voltage application paper, E-rated fuses ≤100E open in 300 s at 200–240% of continuous rating, while ratings above 100E open in 600 s at 220–264%. That is why field engineers confuse an 80E label with “80 A continuous” or with 250% of FLA—the E number is not a one-line synonym for either.
The same paper’s rule of thumb places a minimum rating near 1.4× circuit FLA when overload is not the fuse’s job (or about 1.1× if the load never exceeds rating). E-rated fuse transformer protection therefore starts above FLA on purpose: the floor is inrush hold plus E open-time behavior, checked on the maker’s time-current curve.

Treat code-maximum size as a ceiling, not the chart answer
Code percentages cap how large a primary fuse may be; useful protection still needs the damage and total-clearing check. NEC 450.3(A) sets maximum percentages of rated current by location, impedance band, and device type for transformers over 1000 V—it is not a recommended chart cell.
As summarized from that same MV fuse application paper’s reprint of Table 450.3(A), an any-location primary fuse with transformer impedance 6% or less may be as large as 300% of rated current (next standard rating notes apply), while supervised primary-only installations often list 250%. Teams that size at 250–300% “because code allows it” can still violate the transformer damage / through-fault curve if the fuse total clearing stays above the damage envelope.
Mersen’s MAXIMUM FUSE SIZE note states the same split plainly: the code may allow sizing near 250% of primary current or the next standard rating, yet sizing that large may not provide adequate protection, so the fuse total clearing curve must not exceed the transformer damage curve. A Basler transformer-protection application guide hosted by IEEE PES likewise describes typical fuse carry in the 150–300% band of transformer rated current while still treating coordination as a study, not a blog paste.
Fuse interrupting rating is a separate column from ampere or E number: available fault current at the fuse must stay inside the interrupting capability of the chosen device. Chart amperes never replace that check.
Stop when the published table is the wrong artifact
Abandon anonymous blog tables, brand-locked RMU schedules used out of family, LV control charts, and shared-fuse multi-transformer topologies. Eaton’s construction fuse-link bulletin states its tables are a guide until a more detailed study can be made, and it ties recommended links to carrying full load and opening in about five minutes near three times full load—for those link types only.
Schneider’s RM6 FAQ table pairs network voltage with transformer kVA for named fuse brands and notes the RMU is not guaranteed with other manufacturers’ fuses, ratings are in amperes with no overload, and ambient sits between −25 °C and +40 °C. That is a valid MV transformer fuse selection table inside its family—and the wrong artifact for a US E-rated indoor primary outside that RMU.
Shared primary fuses for several transformers are not a single-row chart lookup. On a Mike Holt thread about one load-break switch fuse set feeding three loop-fed pad-mounts, a reply stressed that each transformer must be protected at not more than 300% of its rated current, so a shared set is governed by the smallest unit—while simultaneous inrush and utility ground coordination still sit outside any one blog cell.
From the field: Overhead crews often reject folk divisors such as “kVA divided by 5” or “double the FLA” and ask for the utility’s laminated chart or company spec-book schedule instead. A utility fuse schedule remains the source of truth for those pots; a random web ampere grid does not.
If your topology is a utility loop, multi-transformer bay, or NESC-governed line, stop treating a single OEM row as finished coordination.
Product Fit: When Published Oil-Immersed Distribution Data Feeds the Fuse Chart
ANDELI publishes HV, kVA, Z%, and vector fields for fuse-chart inputs rather than fuse amperes. When a buyer shortlists a liquid-filled distribution step-down and needs published nameplate inputs for a fuse OEM chart—not a fuse catalog—the 6–10 kV series oil-immersed distribution transformer is the matching published source for those fields.

On the S11 distribution table, HV options include 6 / 6.3 / 10 / 10.5 / 11 kV with LV 0.4 kV, vector groups Dyn11 / Yzn11 / Yyn0, and impedance voltage of 4.0% (30–500 kVA), 4.5% (630–1600 kVA), and 5.0% (2000–2500 kVA). A 630 kVA S11 row lists 810 W no-load loss, 6200 W load loss, 0.6% no-load current, and 4.5% impedance. Normal service notes altitude below 1000 m and ambient from −25 °C to +40 °C.
Those fields—oil-immersed distribution transformer kVA, primary kV, vector group, and percent impedance—feed the fuse OEM chart after you lock family and run FLA. They are not a substitute for E-rating, interrupting rating, or a coordination study. Browse the transformer hub for related distribution families once the nameplate inputs are confirmed.
FAQ
How do you use a medium voltage transformer fuse sizing chart?
Lock the chart family from the title and notes, convert nameplate data to FLA, then read only that family’s voltage and mounting columns while checking inrush hold, E-rating bands, and the code-maximum ceiling against the damage curve.
Which nameplate fields must be known before opening a chart?
Rated kVA, primary voltage, phases, vector group / connection, percent impedance band, and where the fuse is mounted (cutout, indoor switch, outdoor without enclosure) before the first ampere cell.
When is copying a blog or OEM table the wrong move?
When the PDF is a different chart family, brand-locked to another RMU or fuse line, sized for LV control transformers, or applied to a shared-fuse multi-transformer topology that a single row cannot cover.
What does an E-rating mean versus transformer FLA?
An E-rated fuse uses NEMA open-time bands at stated percentages of its continuous rating; the E number is not the same thing as transformer FLA, and chart recommendations usually sit above FLA so inrush does not melt the element.
How is inrush placed on the fuse curve?
Place the magnetizing-inrush point—often around 12× FLA at 0.1 s in classical notes—left of the fuse minimum-melting curve on the maker’s time-current curve, and confirm any shorter-time multiples the chart footer states.
What is a typical code-maximum versus a recommended chart cell?
NEC 450.3(A) percentages (for example 250% or 300% of rated current in summarized rows) are legal ceilings for transformers over 1000 V; the chart cell is the maker’s protection recommendation and still needs a damage-curve check.
Can one fuse set protect several MV transformers from a single chart row?
Not as a simple one-row paste. Shared primary fuses are limited by the smallest transformer’s rated current under the 300% discussion on practitioner forums, and loop or utility coordination still requires a study beyond the chart.
Is a 6–10 kV oil-immersed nameplate enough to pick a fuse ampere?
No. Published HV, kVA, LV, vector, and Z% values are chart inputs only; fuse ampere, E-rating, and interrupting rating come from the matching fuse maker’s family table and coordination notes.
References
- IEEE SA — C37.40-2003 abstract — high-voltage fuse definitions and service conditions above 1000 V; public abstract has no ampere chart (superseded status noted on page).
- IEEE Central Illinois — Time-Current Curves training slides — pedagogy for placing inrush left of the fuse curve.
- Electrical Technology — How to Size a Transformer (kVA / current math) — three-phase and single-phase kVA ↔ current formulas used as FLA input math.
- TestGuy — ETT III: Fuses — NETA ETT study-guide hub on power-fuse properties, types, and applications; lists medium-voltage fuse rating definitions and a selection guide for transformer primary fuses in utility and industrial substations.