Repair of Common Faults in Power Transformers
As an indispensable device in the power system, the stable operation of electrical transformers is of vital importance. However, in the actual operation process, electrical transformers are bound to encounter various faults. This article will provide you with a detailed analysis of common faults, causes and simple repair methods of transformers during operation, helping you quickly deal with transformer problems and ensuring the safe and stable operation of the power system.
Common Fault Phenomena and Causes of Transformers
1.Abnormal noise
When a transformer emits a loud and noisy sound, it is likely that there is a problem with the core, such as loose clamps or screws that hold the core in place. If the sound contains the sound of boiling water or bubbles escaping, it may be due to a winding fault causing nearby parts to heat up and vaporize, or poor contact of the tap changer, inter-turn short circuits, etc. At this time, the machine should be immediately shut down for maintenance. If the sound contains continuous and regular impacts or friction sounds, it may be caused by mechanical contact of components or static discharge, although it does not endanger operation, it should also be dealt with during planned maintenance.
2.Abnormal temperature
When the load, heat dissipation conditions and ambient temperature remain unchanged, if the temperature of the transformer continues to rise, it may be due to inter-turn, inter-layer, or inter-strand short circuits, local short circuits of the core, leakage magnetic field or eddy current causing the oil tank to heat up, long-term overloading operation, or deterioration of the heat dissipation conditions, etc.
3.Line surge current
Line surge current, including closing overvoltage and voltage peaks, is the primary factor causing transformer faults.
4.Poor manufacturing process
Loose terminals, loose pads, poor welding, etc. in the manufacturing process can also affect the normal operation of the transformer.
5.Insulation aging
Long-term overloading operation will cause the transformer to overheat, accelerate insulation aging, reduce insulation strength, and thereby cause faults.
Simple methods for maintenance and repair
1.Fault in the lead wire section
If the three-phase DC resistance is unbalanced or the resistance of a certain phase is infinitely large, it indicates that there is a fault in the lead wire section. The contact failure area can be re-grounded, the welding failure area can be re-welded, or the welding surface and the lead wire cross-section can be increased.
2. Coil fault
A coil fault is usually accompanied by a burnt smell. It can be detected by measuring the insulation resistance and DC resistance. If the insulation resistance is zero and the DC resistance increases and is unstable, the coil needs to be repaired or replaced according to the degree of damage.
3. Insulation degradation
Regularly conduct insulation resistance tests. If the measured value changes significantly or is lower than the required value, it may be that the transformer is damp or the oil insulation resistance has decreased. At this time, the transformer should be thoroughly dried, the oil replaced or filtered, and any loose seals or faulty desiccant should be repaired.
4. Core fault
Measure the insulation resistance of the through-core screw. If it is less than 10 megohms, it needs to be repaired. After removing the damaged through-core screw, replace the insulation.
5. Insulation damage at the low-voltage coil elbow
Remove the old insulation that has been broken down at the elbow, or replace the entire low-voltage coil.
6. Breakdown caused by core fault
For faults such as damaged insulation between core chips, local melting, etc., a layer of insulating paint can be applied at the damaged area. If the core is partially melted, the burned-out part should be scraped clean and then coated with insulating paint.