What a Current Transformer Wiring Diagram Must Show First

2026-09-19

A current transformer wiring diagram is right when the primary conductor runs from source to load, the secondary lands on the meter or relay and stays a closed low-impedance circuit, and polarity follows the nameplate. A switchgear specifier uses that drawing to check letter families, a closed secondary, phase match, lead burden, and which indoor or outdoor body the burden note may name.

A current transformer is a series instrument transformer. The primary carries the line current, and the secondary is a scaled current the meter or relay can read without carrying the full primary amperes.

Indoor switchgear current transformer in the primary path for a wiring diagram check.

Contents

  • What a current transformer wiring diagram has to show.
  • Polarity marks are model letters, not a lead color.
  • Keep every current secondary closed.
  • Three-phase CT wiring follows the meter.
  • Lead burden on a 5 A secondary.
  • Indoor 12 kV and outdoor 12 kV are different diagram notes.

What a current transformer wiring diagram has to show

Show the series primary, the polarity direction, the secondary into the meter or relay, and a closed low-impedance path. The 1 A and 5 A secondary ratings are the usual pair, and the published Andeli rows used here are 5 A secondaries.

The primary sits in series with the power circuit, either as a wound primary or as a single conductor through a window. The meter stays on the secondary, so it never has to carry the full line amperes.

A usable wiring diagram has four items a photograph often leaves out. Mark the source-to-load direction, name the polarity lead from the plate in hand, land the secondary on the meter or relay, and show that the loop stays closed.

The current transformer category is only the family index. Ratio, class, and rated output come from the matching product, and terminal letters are read from the nameplate on the unit, not from a copied color code.

Secondary burden is the load the secondary must drive. It includes the meter or relay plus the leads, and the diagram should name that load before anyone argues about which letter is white.

Polarity marks are model letters, not a lead color

Face the marked source side toward the source, then use the letters on that nameplate. Polarity marks in the P/S, H/X, and K/k families are the same idea, white is not always the polarity lead, and the dot shows direction rather than a terminal you land a wire on.

Nameplate beside a paper drawing with characters left unreadable.

P1 or H1 faces the source unless that nameplate says otherwise. Current enters the polarity mark on the primary and leaves the polarity mark on the secondary when the current transformer is oriented correctly.

Drawings you inherit may use any of the three families below. These Andeli products print ratio, class, and rated output, and they do not print this letter table.

Role IEC-style marks IEEE-style marks Older marks
Source side P1 H1 K
Load side P2 H2 L
Secondary polarity S1 X1 k
Secondary return S2 X2 l

Color belongs to one model. Carry a lead color only for the plate you are reading. Schneider’s 3090SCCT uses white for X1 and black for X2, while some Flex-Core split-core series use black as the X1 lead.

If the plate uses multi-core marks such as 1S1 and 2S1, follow those suffixes. Each core has its own polarity lead, and a metering core is not interchangeable with the protection core on the same drawing.

The dot on a sketch is the direction mark installers ask about. It tells you which way the body faces, and it is not the X1 screw you must land a white wire on.

Keep every current secondary closed

Do not leave a current-output secondary open while primary current can flow. Short it, or keep the burden connected, before the primary is energized. 29 CFR 1910.269 tells the employer not to open a current-transformer secondary while the transformer is energized, and to bridge that secondary if the primary cannot be de-energized first.

A clamp-sensor thread says that sensor's secondary has to stay shorted through a burden, because an open secondary can generate a very high voltage, and that note is not a metering terminal mark.

Important: An open current secondary can reach several kilovolts. Installation guidance warns that even small current transformers can exceed 1 kV open-circuit, and large windings can exceed 10 kV — installation note.

A shorting block is the link you close before anyone lifts a meter off a current-output secondary. Current transformer wiring still fails if that loop is opened while the primary can carry current.

The list below is the pre-energizing check.

  • De-energize the primary, or short the secondary first.
  • Pass one conductor through a metering or protection current transformer, and keep the neutral out of that window.
  • Set polarity from the nameplate.
  • Match that current transformer to the same phase as its voltage input.
  • Close the burden, then remove the short only after the meter or relay is landed.

A voltage-output sensor rated 0.333 Vac uses a built-in burden, so the shorting rule above belongs to current-output secondaries. These Andeli rows are current-ratio tables with 5 A secondaries.

Core-balance wiring is a different scheme. All phase conductors and the neutral pass through the window, and the earth conductor stays outside, which is the residual-current drawing rather than the default for these metering and protection bodies.

Secondary leads landed on a closed shorting link.

Three-phase CT wiring follows the meter

Use one current transformer per phase, or two current transformers in a V connection, only when the meter is built for that count. Land each current transformer on the same phase as its voltage input, because one reversed unit is what makes power read negative.

A 3 phase current transformer wiring diagram stays a meter landing. A power-transformer winding sketch is a different drawing, and the three-phase CT set follows the element count printed on the meter.

Phase A current belongs with phase A voltage. Crossing them is a wiring error even when every ratio on the drawing is right.

From the field: Mixed polarity is what makes kW read negative, and protection cares about direction because a reversed current transformer can make a directional relay look at the wrong side of a fault — field report.

Check the finished set before the primary is treated as complete. Each dot or polarity letter faces the same source-to-load way, each secondary returns to its own meter element, and no phase is swapped with its neighbor.

Two current transformers in a V connection are enough only when the meter is built for two elements. Adding a third body, or omitting one the meter expects, changes the diagram the meter was designed to read.

Lead burden on a 5 A secondary

If the meter is far from the current transformer, lead burden belongs on the diagram. A long 5 A loop is much heavier than the same loop at 1 A, and these published Andeli ratios are 5 A secondaries.

A run of about 200 m with a loop near 3 ohm is about 75 VA at 5 A and about 3 VA at 1 A before the relay burden is added. That pair is an example, not these nameplates.

Rated output is the burden the published class is stated at. A worked example of how such ratings are written is 15 VA class 0.5 for measurement and 10 VA class 10P10 for protection, and that pair is an example, not these nameplates.

When the meter is in the same cubicle, lead burden is often small beside the meter itself. When the meter is in a remote panel, put the lead VA on the drawing before you accept the accuracy class as still meaningful.

The 1 A and 5 A secondary choice is the practical lever. The same copper loop that is heavy at 5 A is light at 1 A, which is why a long run sometimes forces a 1 A secondary even though the rows below are 5 A secondaries.

Which product fits the indoor or outdoor 12 kV diagram

Name LZZBJ9-12 for indoor 12 kV and below, with 10 VA, 10 VA, 10 VA, and 15 VA at cos φ = 0.8. Name LZZBJ71-12 for outdoor 12 kV, with 10 VA, 15 VA, 20 VA, and 20 VA at the same power factor. Keep LZZBJ9-10 as the indoor 10 kV body and do not copy its ratio column.

Weatherproof outdoor current transformer on an overhead line structure.

Indoor switchgear and outdoor overhead lines do not share one burden note. The metering core and protection core also stay separate.

Diagram context Body Published combinations Rated output at cos φ = 0.8
Indoor, 12 kV and below LZZBJ9-12 0.2S/10P15, 0.2/10P15, 0.5/10P15 10 / 10 / 10 / 15 VA
Indoor, 10 kV compact switchgear LZZBJ9-10 10 kV body Nameplate on the unit
Outdoor, 12 kV overhead LZZBJ71-12 0.2S/10P15, 0.2/10P15, 0.5/10P15 10 / 15 / 20 / 20 VA
Not this diagram LZZBJ71-27.5 and LZZBJ71-35 Different voltage family Outside this 12 kV drawing

Indoor LZZBJ9-12

On LZZBJ9-12, the 100/5 ratio is printed with 15 kA thermal for one second and 37.5 kA dynamic. Any other indoor thermal pair belongs with its own ratio row, because 150-200/5, 300-600/5, and 800-2500/5 are ranges rather than every intermediate ratio.

Negotiated custom ratings stay off the printed list, and the full ratio list stays with the LZZBJ9-12 specification.

When the drawing is an indoor cubicle at 12 kV and below, compare the published ratio and the 10 / 10 / 10 / 15 VA output with the meter burden before the drawing is fixed.

Indoor LZZBJ9-10

LZZBJ9-10 is the indoor resin-cast body for 10 kV switchgear, including metering and feeder protection in compact secondary gear.

The diagram may name LZZBJ9-10 as the 10 kV body, and no ratios are taken from the LZZBJ9-10 ratio column. The LZZBJ9-10 indoor current transformer identifies that body.

Outdoor LZZBJ71-12

LZZBJ71-12 is the outdoor body for 12 kV overhead lines, weatherproof, for energy metering and fault protection.

On LZZBJ71-12, the 400/5 ratio is printed with 45 kA thermal and 112.5 kA dynamic. The 5-100/5 outdoor row is printed as 200 I In thermal and 500 I In dynamic, and those multiples stay as multiples of rated current.

LZZBJ71-27.5 and LZZBJ71-35 are a different voltage family and stay out of this 12 kV note. The LZZBJ71-12 outdoor current transformer covers the outdoor 12 kV body, and the higher-voltage rows printed beside it stay off this drawing.

Name the indoor 12 kV body when the cubicle is 12 kV and below, and name the outdoor 12 kV body when the line is overhead. The two burden sets are different, so the drawing follows the installation rather than one VA string.

For an indoor diagram at 12 kV and below, the matching body is the LZZBJ9-12 indoor current transformer. Outdoor overhead work at 12 kV points to LZZBJ71-12, with 10 / 15 / 20 / 20 VA, rather than the indoor 10 / 10 / 10 / 15 VA set.

LZZBJ9-12 indoor current transformer product photo

Indoor compact switchgear stays on LZZBJ9-10, with that ratio column left off the diagram.

LZZBJ71-27.5 and LZZBJ71-35 stay with the other voltage family. Leave these current-ratio bodies off a request that needs a 0.333 Vac voltage-output sensor.

FAQ

How are current transformers wired?

The primary runs from source to load in series with the line, and the secondary lands on the meter or relay as a closed low-impedance loop. Polarity follows the nameplate on that unit, and the secondary rating you expect is usually 1 A or 5 A.

Does it matter which wire goes where on a current transformer?

Yes. Reversing one current transformer turns power and power-factor readings negative, and a directional relay can treat the fault as being on the other side.

The polarity lead is whichever terminal that nameplate marks. White is not always that lead, and a copied color code from another model will land the wrong wire.

How do you install a current transformer without opening the secondary?

Short the secondary, or de-energize the primary, before any secondary wire is lifted. Then pass one conductor, set polarity, match the phase to the voltage input, and close the burden before the short comes off.

How is a three-phase current transformer set wired?

Give the meter one current transformer per phase, or two in a V connection, only if the meter is built for that count. Each current transformer stays on the same phase as its voltage input.

Which secondary terminal should be grounded?

Low-voltage secondaries at 1 kV and below stay ungrounded unless the meter calls for a bond. Above 1 kV, use a single-point ground, often on the polarity secondary terminal, and skip a second bond because a blank symbol is not permission to earth every return lead.

What is the most common use for a current transformer?

Metering and protection. The secondary gives the energy meter a scaled current, and a separate protection core gives the relay its own current.

What are the practical limits of a current transformer wiring diagram?

The diagram can show direction, phase match, a closed secondary, and lead burden. It cannot replace the nameplate, and an open secondary or an uncounted lead run will still make the reading wrong after the landings look tidy.

Can the LZZBJ9-10 ratio table be used on a wiring diagram?

No. LZZBJ9-10 is the indoor resin-cast body for 10 kV switchgear, and the LZZBJ9-10 ratio column cannot supply ratios for the diagram.

References