What a Medium Voltage Switchgear Specification Must Lock First
A usable medium voltage switchgear specification is the ordered set of nameplate and construction fields you fix so bids stay comparable: governing standard system, voltage with its insulation pair, frequency and continuous current, short-time and peak fault ratings with duration, construction class, IP, and site ambient/altitude. Specifying engineer / EPC teams that skip that order often receive IEC and ANSI quotes that look similar on paper and fail in the plant room. The sections below walk the lock order, then read a printed KYN28A-12 table as a worked IEC/GB-family example.

Nameplate literacy comes before purchase paperwork.
Contents
- Lock the Standard System Before Any Rating Number
- Pair Rated Voltage with Power-Frequency and BIL
- Fix Frequency and Continuous Current on the Nameplate
- State Short-Time and Peak Fault Ratings with Duration
- Choose Metal-Clad, LSC/PM, and IP Language Deliberately
- Record Site Ambient, Altitude, and Service Envelope
- Select KYN28A-12 When Your Spec Fits These Printed Ratings
Lock the Standard System Before Any Rating Number
Name the governing standard system first so voltage words and construction words stay consistent across bids. An EPC comparing one IEC metal-enclosed lineup against an IEEE metal-clad lineup for the same room learns this when IEC voltage labels and ANSI class labels land in the same spreadsheet without a shared framework.
IEC 62271-200 is the modern IEC family for AC metal-enclosed switchgear above 1 kV through 52 kV. IEEE C37.20.2 defines metal-clad construction and preferred rating bands used on many North American projects. Those two routes use different voltage labels, different construction vocabulary, and different preferred bus bands.
KYN28A-12 is printed to GB/T3906 / GB/T11022 and IEC 60298. IEC 60298 is the legacy metal-enclosed reference named with that model; IEC 62271-200 is the modern family buyers often specify. Keep both facts visible without treating them as one interchangeable standard set.
Project annexes still pair legacy IEC 298 language with IEC 62271-200 clauses in the same indoor MV package. That coexistence is why a metal clad switchgear specification must name the route before any rating cell is filled.
Pair Rated Voltage with Power-Frequency and BIL
Rated voltage is a set with power-frequency withstand and lightning impulse; orphan BIL cells break comparability. Rated voltage Ur is the maximum rms voltage the assembly is designed for under normal conditions, and it must sit above the highest operating voltage on the feeder.
Power-frequency withstand Ud is the one-minute dielectric withstand paired with Ur. Lightning impulse / BIL Up is the 1.2/50 surge level paired with the same Ur column. Under IEC practice, those three cells travel together.
Many IEC projects rate 11 kV systems on 12 kV equipment with paired withstand values. One utility metal-clad table maps Un 11 kV to Ur 12 kV with Ud 28 kV and Up 95 kV. That pair is a utility example for how Ur, Ud, and Up lock together — not a silent rewrite of every manufacturer row.
Published rated voltages for KYN28A-12 include 3.6, 7.2, and 12 kV. One-minute power-frequency withstand values print as 24, 32, and 42 kV for the three voltage columns.
Lightning impulse withstand prints as 40, 60, and 75 kV. When you compare MV switchgear ratings, read those three columns as one insulation set.

Read Ur beside its power-frequency and lightning-impulse pair as one set.
Fix Frequency and Continuous Current on the Nameplate
State rated frequency and continuous current so thermal limits are explicit on the RFQ. A rating nameplate is expected to state voltage, insulation withstand, frequency, continuous current, bus rating, and fault withstand figures.
KYN28A-12 is printed for three-phase AC at 50 Hz. Published rated current options run from 630 A through 4000 A. If the one-line needs a separate main-bus continuous figure, write that cell beside the feeder continuous current so thermal claims stay scanable.
IEEE preferred bus continuous currents often sit at 1200, 2000, 3000, and 4000 A on metal-clad projects. Keep that preferred band on the IEEE route; do not paste it onto an IEC/GB nameplate that already prints its own current list.
State Short-Time and Peak Fault Ratings with Duration
A short-circuit kiloampere without a time window is incomplete, and peak withstand belongs beside it. Buyers who write a short-circuit figure alone then open three bids with three different assumed times.
Short-time withstand current is the thermal fault current for a stated duration. Short-time withstand options on KYN28A-12 print as 20-50 kA for 4 s.
Peak withstand current is the dynamic fault figure printed beside that column. Peak withstand values print as 50, 63, 80, 100, and 125 on the KYN28A-12 peak column.
| Field to lock | Why it must be complete | Worked reading cue |
|---|---|---|
| Governing standard system | Keeps IEC/GB and ANSI/IEEE words from mixing | Name IEC/GB or IEEE before voltage cells |
| Rated voltage Ur + Ud + Up | Insulation is a paired set | Match system voltage to one Ur column |
| Frequency and continuous current | Makes thermal claims comparable | State Hz and ampere options together |
| Short-time Ik with duration + peak | Avoids the duration trap | Keep time beside kA; keep peak beside short-time |
| Construction / LSC / PM or metal-clad wording | Changes what is being bought | Write the construction class on purpose |
| IP and site ambient/altitude | Stops catalog normals from becoming silent assumptions | State enclosure IP and service envelope |
Choose Metal-Clad, LSC/PM, and IP Language Deliberately
IEEE treats metal-clad as a specific compartmented class; metal-enclosed is the broader family. That metal-clad construction isolates major compartments with grounded metal barriers and uses drawout circuit breakers. Specifiers still ask whether metal-clad and metal-enclosed are “really different,” because the parent family and the stricter subclass share overlapping rating language.
IEC specs often use LSC / LSC2B and Partition class PM instead of IEEE metal-clad wording. LSC classifies how much of the assembly can remain energized when an accessible high-voltage compartment is opened. Partition class PM means metallic partitions and shutters between compartments, not insulating partitions alone.

Compartment metal walls are what PM language is trying to buy.
From the field: Specifiers frequently confuse metal-clad vs metal-enclosed and LSC2B PM wording. One tender thread asked why a clause allowed LSC2A only for vacuum contactor feeders while circuit-breaker feeders stayed on LSC2B PM — the construction sentence, not the voltage cell, was doing the real work (Eng-Tips community discussion).
IP degree of protection closes the enclosure claim. KYN28A-12 lists enclosure IP4X and IP2X between compartment panels. Write those IP cells next to the construction class so the metal clad switchgear specification and the enclosure claim stay aligned.
Associated vacuum circuit breaker families named with this lineup include Vd4 and VS1-12. Name the breaker family only after the assembly construction words are already locked.
Record Site Ambient, Altitude, and Service Envelope
Ambient, altitude, and related service limits belong in the specification because tabulated ratings assume normal service unless negotiated. Indoor rooms above the printed altitude, or hotter plant halls, are buying decisions — not footnotes.
Normal published service conditions for KYN28A-12 include −25 °C to +40 °C and altitude below 1000 m. If the substation sits above that altitude, or outside that ambient band, the envelope must be stated so the quotation cannot assume catalog normals.

Indoor rooms still need the ambient and altitude cells written beside the ratings.
Humidity, seismic intensity, and indoor application notes printed with KYN28A-12 support the same envelope discussion. Keep them next to the ratings rather than in a separate later pile.
Select KYN28A-12 When Your Spec Fits These Printed Ratings
Use the printed KYN28A-12 table as a worked IEC/GB-family example when those nameplate cells match the fields you already locked. Andeli KYN28A-12(Z)(GZS1) is indoor armored withdrawable AC metal-enclosed switchgear for three-phase AC 50 Hz receive, distribute, control, protect, and monitor duty.
| Locked field | Printed KYN28A-12 reading |
|---|---|
| Standards named | GB/T3906, GB/T11022, IEC 60298 |
| Rated voltage | 3.6 / 7.2 / 12 kV |
| 1 min PF withstand | 24 / 32 / 42 kV |
| Lightning impulse (full wave) | 40 / 60 / 75 kV |
| Frequency / continuous current | 50 Hz; 630-4000 A |
| Short-time / peak | 20-50 kA for 4 s; peak 50 / 63 / 80 / 100 / 125 as printed |
| IP | Enclosure IP4X; compartment IP2X |
| Ambient / altitude | −25 °C to +40 °C; below 1000 m unless negotiated |

The product photo matches the printed KYN28A-12 table above.
Choose KYN28A-12 indoor metal-enclosed switchgear when your locked cells sit inside that printed set. Skip it when the project is locked to IEEE C37.20.2 metal-clad wording Andeli does not print, when you need a hipot or commissioning procedure instead of a nameplate lock order, or when the ratings fall outside the printed voltage columns.
Related MV and HV devices sit on the Medium and Highty Voltage hub. Compare the locked cells to the printed table first, then open the linked KYN28A-12 model for more detail.
FAQ
What should a medium voltage switchgear specification include?
Lock the governing standard system, rated voltage with power-frequency and BIL, frequency, continuous and bus current, short-time current with duration, peak withstand, construction class (metal-clad or LSC/PM), IP, auxiliaries you actually need, and site ambient/altitude. That ordered field set is what makes quotations comparable before purchase.
What is the difference between metal-clad and metal-enclosed switchgear?
Metal-enclosed switchgear is the broader family. Metal-clad switchgear is a specific compartmented drawout subclass under IEEE C37.20.2, with grounded metal barriers between major compartments. IEC buyers often express the same construction idea with LSC and PM language instead of the IEEE metal-clad label.
Which ratings appear on an MV switchgear nameplate?
Expect maximum or rated voltage, BIL, power-frequency withstand, frequency, continuous current, main bus rating when used, and fault figures such as short-time and peak or momentary values. Read those cells as a set, not as independent marketing numbers.
What does LSC2B PM mean in an IEC MV switchgear specification?
IEC 62271-200 LSC2B describes a service-continuity class where other high-voltage compartments can remain energized when an accessible compartment is opened, when the assembly is designed and classified that way. PM means metallic partitions and shutters. Tender clauses that mix LSC2B PM with limited LSC2A exceptions for contactor feeders are construction decisions, not voltage decisions.
How do BIL and power-frequency withstand relate to rated voltage?
They form the insulation pair with Ur. Power-frequency withstand is the one-minute AC dielectric figure; BIL is the lightning-impulse figure. Utility IEC tables often map an eleven-kilovolt system onto a twelve-kilovolt Ur with paired Ud/Up values, while a manufacturer table may print a different Ud/Up pair for the same Ur column.
Why must short-time current include a duration?
Thermal withstand is incomplete without time. The same kiloampere figure for one second, three seconds, or four seconds is not the same claim. KYN28A-12 prints its short-time column with a four-second duration, which is why duration must travel with the kiloampere number.
Should I write the specification to IEC or to IEEE C37.20.2?
Pick one governing route for the assembly language you will accept. IEC/GB metal-enclosed wording and IEEE metal-clad wording are not detail-for-detail substitutes. KYN28A-12 is printed to GB/T3906, GB/T11022, and IEC 60298, while tenders may still ask for the modern IEC 62271-200 family.
Which site conditions must be stated with the ratings?
State ambient temperature, altitude, and any humidity or seismic limits that change the envelope. Catalog tables assume normal service; indoor substations above the printed altitude limit or outside the printed ambient band need negotiated language beside the ratings.
References
- IEC metal-enclosed switchgear and controlgear assembly standard abstract (Part 200, 2021 edition)
- City Power technical specification — metal-clad withdrawable switchgear (CP_TSSPEC_035)
- Project ANNEXURE K — indoor MV metal-clad air-insulated switchgear clauses
- Switchgear and Switchboard Inspection and Testing Guide (testing community wiki)