Leave Your Message
News Categories
Featured News

Which Fields Belong on a Dry Type Transformer Specification

2026-09-23

# Which Fields Belong on a Dry Type Transformer Specification

A usable dry type transformer specification locks more than capacity: voltages, insulation construction, cooling assist, enclosure IP, ambient and altitude, and impedance must sit on the same RFQ or drawing note so the published unit matches the room and the protection study. Walk the field map below in that order, then confirm the same items against the ANDELI SCB series published 6–10 kV tables.

ANDELI SCB cast-resin dry-type transformer studio photo, three-quarter view with red coils, blue frame, and side terminal box

Contents

  • What a Dry Type Transformer Specification Must Lock.
  • Lock kV and kVA With Vector Group and Taps.
  • Lock Insulation Construction and Thermal Class.
  • Lock Cooling Assist: Natural Air vs Forced Air.
  • Lock Enclosure IP for the Room and Environment.
  • Lock Ambient Temperature and Altitude.
  • Lock Impedance for Protection and Regulation.
  • Reading ANDELI SCB published specification fields.
  • FAQ.
  • References.

What a Dry Type Transformer Specification Must Lock

Specification / nameplate fields belong on one RFQ note together: capacity with voltages, insulation construction, cooling, IP, ambient/altitude, and impedance — not kVA alone.

When a specifying engineer / EPC RFQ lists only “1000 kVA dry-type,” vendors can still return units that miss fan assist, enclosure rating, or the impedance the short-circuit study assumed. Purchasing guides for dry-type equipment treat the shopping list as a co-dependent set: rated power, taps, temperature rise, enclosure, cooling class, and an impedance range from the fault or arc-flash study (NEMA LV dry-type purchasing guide).

Field Why it matters What to write on the RFQ / drawing note
kVA / rated capacity Sets load headroom; not a substitute for voltages or %Z Load-based kVA, not primary-amp guesswork
Primary / secondary voltage (kV) Fixes the step-down identity HV and LV options together
Vector group Dyn11 / Yyn0 and taps Controls phase shift and voltage adjust Dyn11 or Yyn0 plus tap range
Insulation construction Separates cast-resin from VPI inside dry-type Construction note, not a types gallery
Insulation class B/F/H with temperature rise Bounds winding thermal duty Class paired with allowed rise
Cooling assist Clarifies natural air vs forced-air rating AN / AF (AA / FA) literacy, or published fan language
Enclosure IP Matches casing to room risk IP required for the room (e.g., IP20 / IP23)
Ambient / altitude Aligns site with nameplate service basis Indoor ambient band and altitude limit
Impedance / %Z Feeds fault current and regulation Acceptable %Z range, then published table step

Use that field map when you open the electrical, construction, cooling, enclosure, site, and impedance sections that follow.

Single red cast-resin high-voltage coil with vertical tap points for an SCB dry-type transformer

Lock kV and kVA With Vector Group and Taps

Start from load kVA, then put HV/LV options, taps, and Dyn11/Yyn0 on the same line.

Rated capacity is the same on the primary and secondary in ordinary three-phase step-down service — amp math on one side does not invent a different kVA on the other (MEP Engineering discussion). Specifiers who size from a 208 V panel amp listing and then treat the 480 V side as the same amp count still need a load-kVA basis before they pick a catalog step.

Buyer questions that ask for “the” 750 kVA or 2000 kVA dry-type specification still leave voltages, taps, and connection unspecified. Capacity alone does not finish the note.

On ANDELI’s 6–10 kV SCB series dry-type tables, published HV options include 6 / 6.3 / 6.6 / 10 / 10.5 / 11 kV with LV 0.4 kV, taps ±2×2.5% or ±5%, and vector group Dyn11 / Yyn0. Write those four items on one line when the project uses that family, so the vendor cannot swap a voltage or connection silently.

Lock Insulation Construction and Thermal Class

Treat cast-resin vs VPI as a construction field, and pair insulation class with temperature rise.

A cast resin dry type transformer uses epoxy or resin to encapsulate the HV winding; cast resin / epoxy cast HV construction is one common published form, while VPI impregnates windings under vacuum pressure. Both sit inside the dry-type family. Treat the choice as a specification field for fire, moisture, and maintenance expectations — not as a substitute for a separate types-identification article.

The insulation class of dry type transformer systems is commonly stated as insulation class B/F/H. Dry type transformer temperature rise is the paired winding-rise allowance that belongs on the same note. ANDELI SCB loss-table headers publish insulation/rise columns labeled 130 °C (B) / 100 °C, 155 °C (F) / 120 °C, and 180 °C (H) / 145 °C.

The SCB product description names a Dupont NOMEX paper insulation system, resin-cast HV coils with glass-fiber/epoxy composite, and foil LV windings. Quote construction language that matches the printed unit when you write the RFQ line.

Lock Cooling Assist: Natural Air vs Forced Air

Use AN/AF or AA/FA literacy for cooling assist; for ANDELI, describe the published temperature controller and fans.

Cooling-class labels tell the buyer whether fans are part of the rated story. Purchasing guides list AN / AF (AA / FA) family cooling classes so overload and dual ratings stay unambiguous (NEMA PS4). Distribution primers teach the same idea with AA (self-cooled), AFA (forced-air), and AA/FA (self plus forced) language (Iowa State distribution transformers notes).

Some owner medium-voltage dry-type sections treat fan assist as a second rating above the natural-air base — one campus example cites fans increasing kVA rating by 33% for AA/FA service (UW facilities MV dry-type specs). Confirm the manufacturer’s dual-rating method before you copy that percentage onto another brand.

ANDELI’s published SCB description includes a temperature controller and cross-flow cooling fans. Keep AN/AF or AA/FA as general selection literacy beside that printed accessory language.

Open-frame SCB dry-type transformer with three red cast-resin coils and a bottom cross-flow cooling fan bank

Lock Enclosure IP for the Room and Environment

Choose the IP the room needs; published SCB options include IP20 and IP23.

Ingress protection describes how closed the metal cover is against fingers, dust, and dripping water. Related buyer questions about whether dry transformers need a special enclosure are really IP and ventilation questions for the room, not a single universal cabinet.

IEC dry-type practice distinguishes units without enclosure (including IP00 language in the standard family) from enclosed units and points to enclosure degrees of protection under IEC 60529 terminology in the IEC 60076-11 sample clauses (IEC 60076-11 sample PDF).

For indoor commercial-center or substation rooms, pick the IP that matches finger access and dripping risk. ANDELI SCB protective casing options include IP20 and IP23, with casing materials listed as cold-rolled steel, stainless, or aluminum alloy on the product page.

Lock Ambient Temperature and Altitude

Check indoor ambient and altitude against the printed service basis before treating a catalog step as final for that room.

Nameplate thermal and dielectric ratings assume a service envelope. If the room runs hotter or the site sits higher than the printed basis, derating or negotiation may be required before the unit ships as tabulated.

ANDELI SCB normal service conditions for indoor units list ambient highest +40 °C and lowest −5 °C, hottest monthly average +30 °C, hottest yearly average +20 °C, and altitude below 1000 m. Put those limits beside the capacity and IP lines so a high-rise or hot plant room does not silently exceed the printed basis.

Important: Match ambient and altitude to the printed service basis before you treat any catalog capacity step as final for that room. A unit specified only by kVA can still be wrong for a site above the published altitude or outside the indoor ambient band.

Lock Impedance for Protection and Regulation

Agree an acceptable impedance range with the protection study, then match the published table step for that family.

Percent impedance voltage describes how “stiff” the transformer is electrically under fault and how voltage regulation behaves under load. Specifying engineers on medium-voltage projects often set impedance partly to limit facility fault current before they name a capacity step (Electrical Engineering thread).

From the field: When buyers ask how to spec an MV transformer beyond kVA, replies repeatedly push impedance as a protection decision — lock an acceptable %Z range with the short-circuit study, then match a published table value rather than leaving %Z blank for the vendor to fill (community discussion).

Some owner standards publish default impedance when drawings are silent — one campus MV dry-type section uses 5.75% for non-network and 7% for three-transformer networks as examples only (UW facilities specs). Confirm project documents before adopting those defaults.

Published impedance voltage on the ANDELI SCB tables includes 4.0%, 6.0%, and 8.0% depending on rating band. Choose the study range first, then pick the printed step that sits inside it.

English outline of a three-phase dry-type transformer assembly with coil blocks, tap points, and base dimensions

Match the printed %Z step to the same note that already carries capacity and voltages.

Reading ANDELI 6–10 kV SCB Published Specification Fields

Use printed SCB fields for this family. Read the tables for voltages, capacity, taps, vector, impedance, IP, and ambient.

After the field map is locked, open one printed MV cast-resin table set and tick the same boxes. The ANDELI 6–10 kV SCB series dry-type transformer published specification tables describe a resin-insulated dry-type distribution family (SC(B) series) for indoor sites named in applications such as high buildings, airports, substations, and commercial centers.

ANDELI SCB series dry-type transformer product photo with red cast-resin coils, blue frame, and bottom cooling fans

The scan table below binds RFQ language to printed SCB values only.

Published parameter What the SCB tables show (as printed)
HV / LV HV 6 / 6.3 / 6.6 / 10 / 10.5 / 11 kV; LV 0.4 kV
Capacity band Rated capacity from 30 through 2500 kVA
Impedance voltage % Steps 4.0%, 6.0%, and 8.0% by capacity bands
Taps / vector ±2×2.5% or ±5%; Dyn11, Yyn0
Enclosure IP IP20 and IP23 options
Ambient / altitude Indoor +40 / −5 °C band; altitude below 1000 m
Cooling accessories Temperature controller and cross-flow cooling fans (AN/AF letter codes are selection literacy, not printed SCB nameplate marks)

Use the transformer hub for adjacent power and distribution options once the dry-type field note is complete. This page helps you match printed fields to the RFQ note; it is not a quote-submission form. It is not a fit when the project requires listing marks not printed on the SCB page, outdoor service outside the printed indoor ambient/altitude basis without negotiation, or when the only decision needed is oil-versus-dry or a types overview.

For type identification or a plain “what is a dry-type” explainer, use the published news pieces on those topics rather than expanding them here.

FAQ

Which fields belong on a dry type transformer specification?

Capacity, HV/LV voltages, taps, vector group, insulation construction, insulation class with temperature rise, cooling assist, enclosure IP, ambient/altitude, and impedance. Purchasing guides treat those as a set rather than kVA alone (NEMA PS4).

Is kVA enough to specify a dry-type unit?

No. Capacity questions for 750 kVA or 2000 kVA units still leave voltages, enclosure, cooling, and %Z open. Size from load kVA, then lock the rest of the field map.

What does AN vs AF (or AA/FA) cooling mean for selection?

AN/AF (or AA/FA family language) states whether the rating is air-natural, forced-air assisted, or both. Use that literacy on the RFQ; for ANDELI SCB, describe the published temperature controller and fans.

How should enclosure IP be written for indoor dry-type units?

Write the IP the room needs for finger, dust, and drip risk. Published ANDELI SCB casing options include IP20 and IP23.

Why lock ambient temperature and altitude?

Tabulated ratings assume a printed service envelope. ANDELI SCB indoor normal service lists +40 / −5 °C ambient with altitude below 1000 m — confirm the site against that basis.

How is impedance chosen and what values appear on SCB tables?

Set an acceptable %Z range with protection and regulation studies, then match a published step. SCB tables publish impedance voltage steps of 4.0%, 6.0%, and 8.0% by capacity band.

What IEC document covers dry-type transformers?

IEC 60076-11 covers dry-type power transformers within its published voltage scope (highest voltage for equipment up to and including 72.5 kV, with at least one winding above 1.1 kV) (IEC webstore abstract).

How does insulation class differ from temperature rise?

Insulation class (B/F/H) names the thermal system; temperature rise is the allowed winding temperature increase in normal service. Write both together on the specification note.

Where do cast-resin construction notes belong vs a types article?

Put cast-resin vs VPI on the RFQ as insulation construction. Keep type-identification galleries on a separate types article so this note stays field-lock focused.

What published data should be checked on ANDELI’s 6–10 kV SCB page?

Check HV/LV options, capacity band, taps, Dyn11/Yyn0, %Z steps, IP20/IP23, indoor ambient/altitude, and the printed fan/controller language on the SCB product page.

References

Authority and community sources used for field-lock literacy (not product pages).