Leave Your Message

S9-35kv Series Transformer

Application
The product conforms to the technical parameters and requirements of lEC60076 and China Standard GB1094 & GB/T6451, and a series of significant innovation is applied in aspects of material,design and structure.lt has the features of high efficiency and low loss.lt can save a lot of operation cost,and the social benefits are very significant.In conclusion,it is a nationally pro-moted new product and it is deeply favored by customers.

Altitude: ≤1000m

Installation site: In places without corrosive gases and obvious dusts.

    Product Fectures

    1.Product Has High fficiency, Low Loss, Low Noise Characte ristics;
    2.Internal Heat, And Short Circuit Capability;
    3.Empty, Load Loss IS Low
    4.Reliable Operation, Long Life, Maintenance-free.
    S9-35kv Series Transformers (1)
    S9-35kv Series Transformers (2)
    S9-35kv Series Transformers (3)

    Application Standards

    IEC 60076-1-2-3 2000 Power Transformer
    GB 1094.1-2-1996 Power Transformer
    GB 1094.3-5-2003 Power Transformer
    GB/T6451-1999 Technical parameters and requirements for three-phase oil-immersed power transformer

    Transformer Model description

    Transformer Model description

    ransformer Normal Service Conditions

    The height above the sea level is below 1000m
    Ambient temperature:
    Highest air temperature +40℃
    Highest daily average air temperature +30℃
    Highest annual average air temperature +20℃
    Lowest outdoor air temperature -25℃

    Transformer Special Service Conditions

    The height above the sea level is above 1000m
    Ambient temperature:
    Highest air temperature is above 40℃
    Lowest air temperature Lower than25℃

    Performance Characteristics

    1.The features of this product are high efficiency and low loss.lt can save a lot of operation cost,and the social benefits are very significant.
    2.The iron cores are made of the imported high-conduction magnetism,cold-roll,and grain-ori.ented silicon-steel sheets.The iron cores and windings adopt the vacuum drying and vacuumoil-filling processes,which make the internal moisture down to the very low level.
    3.The conservator is hermetically sealed,which make the internal running oil to insolate with oxygen and moisture efficiently.
    4.The above features guarantee the transformer does not need do replace the oil during the normal operation,greatly decrease the maintenance cost,and prolong the service life.

    Main Technical Parameters of S9-M-50~2500/35 Series of Transformers

    Rated capacity (KVA) Voltage combination(kV) Connect- ing group No-load lossess (W) Load-loss (W)(75C) Short circuit impedance (%) No-load current (%) Weight(kg) Overal dimension (mm) Gauge (mm)
    High voltage (KV) Tapping (%) Low voltage (kV)
    Body Oil Gross weight Lengthxwidthxheight
    50 35 ±5 0.4 Yyno 215 1210 6.5 2.00 230 320 650 1150x720x1200 550x550
    100 305 2020 1.80 380 400 980 1200x740x1300 550×550
    125 340 2380 1.75 440 430 1100 1250x780x1380 550×550
    160 360 2830 1.65 510 460 1200 1300×800×1400 660×660
    200 430 3300 1.55 600 500 1400 1400x840×1500 660×660
    250 510 3950 1.40 690 530 1500 1530x860×1580 660×660
    315 610 4750 1.40 800 570 1670 1600x890x1630 660x660
    400 735 5750 1.30 930 650 1950 1730x50x1700 660x660
    500 870 6900 1.30 1070 710 2300 1800×980×1800 820x820
    630 1040 8250 1.25 1300 830 2650 1900x1000x1850 820x820
    800 1250 9900 1.05 1600 900 3100 1950x1060x1900 820x820
    1000 1480 12150 1.00 1800 1080 3700 1980x1100x1950 820×820
    1250 1760 14600 0.90 2100 1150 4000 2010x1160x1980 820x820
    1600 2130 17500 0.85 2550 1250 4730 2040×1310×2000 820x820
    2000 2500 20680 0.75 3100 1400 5600 2170×1380×2700 1070×1070
    2500 2975 24500 0.75 3650 1500 6300 2300x1450x2900 1070×1070

    Main Technical Parameters of S9-M-800~20000/35 Series of Transformers

    Rated capacity (kVA) Voltage combination(kV) Connect- ing group No-load lossess (W) Load-loss (W)(75°C) Short circuit impedance (%) No-load current (%) Weight(kg) Overal dimension (mm) Gauge (mm)
    High voltage (KV) Tapping (%) Low voltage (KV)
    Body Oil Gross weight Lengthxwidthxheight
    800 35 ±5 3.15 6.3 10.5 Yd11 1250 9900 6.5 1.05 1680 970 3200 2000×1100×1950 820x820
    1000 1480 12150 1.00 1800 1100 3570 2100×1200×2100 820×820
    1250 1760 14650 0.90 2060 1200 4040 2150×1250x2150 820x820
    1600 2130 17500 0.85 2400 1250 4550 2200x1340x2180 820×820
    2000 2600 19350 0.75 2820 1420 5720 2250×1380×2210 1070x1070
    2500 3150 20700 0.75 3330 1550 6000 2300x1400x2300 1070x1070
    3150 35 38.5 ±5 3.15 6.3 10.5 3860 24300 7.0 0.70 3800 1670 7060 2480x1900x2450 1070×1070
    4000 4630 28800 0.70 4500 1830 8200 2800x2250x2500 1070×1070
    5000 5480 33000 0.60 5300 2000 9500 3000×2370×2800 1070×1070
    6300 6570 36900 7.5 0.60 6550 2300 11280 3200×2520x2900 1070x1070
    8000 ±2x2.5 3.15 6.3 10.5 9000 40500 0.55 8150 2700 14000 3300×2700×3200 1475x1475
    10000 10600 47700 0.55 9600 3050 16250 3400x2800x3400 1475x820
    12500 12600 56700 8 0.50 11000 3660 18800 3500x2930x3500 1475x1070
    16000 15300 69300 0.50 13650 430 22250 3620×3040×3600 1475x1070
    20000 18090 83500 0.50 15500 5530 25000 3700x3100x3700 1475×1475

    Leave Your Message