XGN15-12 10kV High Voltage Ring Network Switchgear

The XGN15-12 indoor AC high-voltage sulfur hexafluoride ring main unit (RMU) is a new generation of compact, scalable metal-enclosed switchgear featuring sulfur hexafluoride (SF6) load breakers as the main switches. Designed to meet the high-performance and high-reliability requirements of modern power systems, this equipment boasts excellent insulation and switching capabilities. The use of sulfur hexafluoride gas enables the RMU to safely operate at high voltages and currents within a compact footprint, significantly enhancing equipment safety and reliability.

    Product Overview and Features

    XGN15-12 type Indoor AC high-voltage sulfur hexafluoride ring network switchgear (hereinafter referred to as "ring network cabinet") is a new generation of compact and expandable metal-enclosed switchgear with sulfur hexafluoride load switch as the main switch.The compact design of the ring main unit (RMU) allows for flexible installation in space-constrained environments, making it suitable for cities, industrial parks, and other power-intensive areas. Furthermore, its scalability allows for flexible configuration based on actual needs, facilitating future system upgrades and expansion. The RMU is also equipped with advanced monitoring and protection devices that monitor the operating status of equipment in real time, ensuring the safe and efficient operation of the power system. By adopting this high-tech RMU, power companies can better cope with growing electricity demand and provide users with more reliable and high-quality power services.
    3
    4
    And the whole cabinet adopts air insulation, which is suitable for power distribution automation, Ring main unit is characterized by simple structure, flexible operation, reliable interlocking, etc. lt can provide satisfactory technical solutions for different applications and different user requirements. The adoption of sensing technology and the latest protection relay, coupled with advanced technical performance and lightweight and flexible assembly program, The use of sensing technology and the latest protection relays, coupled with advanced technical performance and lightweight, flexible assembly solutions, can fully meet the changing requirements of the market.

    Model Meaning

    XGN15-12

    Areas of application and environments of use

    Widely used in urban power grid renovation, residential neighborhoods,schools and industrial and mining enterprises and other power distribution places, ring network power supply units and terminal equipment,plays a role in the distribution of electric energy, control and protection of electrical equipment, can also be installed in the pre-installed box-type substation.
    1. The surrounding ambient temperature -25℃~40℃;
    2. Altitude: below 1000m;
    3. Humidity: average daily relative humidity does not exceed 95%;
    average monthly relative humidity does not exceed 90%;
    4. Anti-seismic capacity of 8 degrees;
    5. No violent vibration, corrosion, fire, explosion hazardous places.

    Main technical parameters

    Name Unit Parameters
    rated voltage KV 12
    Rated frequency Hz 50
    rated current A 630
    Fuse rated current A 125
    Rated short-time withstand current KA 25
    Rated short circuit duration S 2
    Rated short-circuit closing current KA 63
    Rated peak withstand current KA 63
    Rated load breaking current A 630
    Rated transfer opening current (with 125A fuse) A 1700
    Rated breaking current of fuse (RMS) KA 31.5
    Rated insulation level 1min frequency withstand voltage(RMS) Between phases,Phase to ground KV 42
    Opening distance KV 48
    Lightning impulse withstand voltage (Peak) Between phases,Phase to ground KV 75
    Opening distance KV 85
    Secondary circuit 1min frequency withstand voltage KV 2
    protection class   IP3X
    Three-phase center distance mm 210±2
    Overall dimensions load switch cabinet cabinet width mm 375,500,750
    cabinet depth mm 940
    cabinet height mm 1635,1850
    low voltage room heights mm 450
    Load switch mechanical life Closing/Opening time 5000
    Breakout/Earthing time 1000