01
XGN66-12 Enclosed Fixed Ring High Voltage Switchgear
Product Overview and Features
XGN66-12 type fixed enclosed switchgear (hereinafter referred to as switchgear) is our new generation of high-voltage electrical complete sets of products, in line with the national standard GB3906 "35KV AC metal-enclosed switchaear" the Ministry of Electric Power, DLT404 "indoor AC high-voltage switchgear ordering technical conditions," the requirements, but also to meet the international standard lEC60298 "1kV to, It also meets the requirements of international standard lEc60298 "Requirements for AC metal-enclosed switchgear and control equipment below 1kV and 52kV".
The product absorbs advanced foreign technology, it is small in size, only 50% of the size of an ordinary switchgear cabinet;The switchgear is equipped with high-reliability circuit breakers, ensuring stable operation and excellent performance under various operating conditions. High reliability not only improves the safety of the power system, but also reduces the probability of failure, thereby reducing maintenance costs and the risk of power outages.
The device also features an advanced "five-prevention" interlocking mechanism to ensure operational reliability and safety. This easy-to-use interlocking mechanism effectively prevents misoperation and safeguards both equipment and personnel. Through these designs, the XGN66-12 fixed enclosed switchgear not only improves the overall efficiency of power systems but also provides users with a safer and more reliable power experience, adapting to growing power demands and complex power usage environments.
Switchgear is 3.6, 7.2, 12kv three-phase alternating current 50Hz single bus sectionalized indoor complete set of devices, as the acceptance and distribution of electrical energy. And has the circuit control, protection and monitoring functions, can be used in various types of power plants, substations and industrial and mining enterprises, high-rise buildings and other places, can also be combined with the ring network cabinet applied to the opening and closing of the house.

Model Meaning

Areas of application and environments of use
Widely used in urban power grid renovation, residential neighborhoods, schools and industrial and mining enterprises and other power distribution places, ring network power supply units and terminal equipment, plays a role in the distribution of electric energy, control and protection of electrical equipment, can also be installed in the pre-installed box-type substation.
1.The surrounding ambient temperature -25℃ - 40℃
2.Altitude: below 1000m;
3.Humidity: average daily relative humidity does not exceed 95%;
average monthly relative humidity does not exceed 90%;
4.Anti-seismic capacity of 8 degrees;
5.No violent vibration, corrosion, fire, explosion hazardous places.
Main technical parameters
| Name | Unit | Parameters |
| Switchgear | ||
| Rated Voltage | kV | 3.6、7.2.12 |
| Rated frequency withstand voltage | kV | Phase to ground,Between phases : 42;Opening distance: 45 |
| Rated lightning impulse withstand voltage | kV | Phase to ground,Between phases : 75;Opening distance: 85 |
| Rated frequency | Hz | 50 |
| Rated current | A | 630、1250 |
| Rated short-circuit breaking current (peak) | kA | 20、25、31.5 |
| Rated short-circuit closing current (peak) | kA | 50、63.80 |
| Rated dynamic stabilizing current (peak) | kA | 50、63、80 |
| Lightning thermal stabilizing current 4S(RMS) | kA | 20、25.31.5 |
| Protection class | IP2X | |
| Dimension(WXDXH) | mm | 900x 1000x2300 |
| Weight(WxDxH) | kg | ≈600 |
| Vs1-12 type vacuum circuit breaker | ||
| Rated Voltage | kV | 12 |
| Rated current | A | 630 1250 |
| Rated short-circuit breaking current | kA | 2025 31.5 |
| Rated short-circuit closing current | kA | 50 63 80 |
| Rated short-time withstand current(4S RMS) | kA | 2025 31.5 |
| Rated peak withstand current (peak) | kA | 50 63 80 |
| Mechanical life | time | 10000 |
| Rated short-circuit breaking current breaking times | time | 50 |
| Rated operation sequence | Switch off-0.35-Switch on-off180s-Switch on-off | |