Leave Your Message

YBW Pre-Assembled Substations

YBW-12/0.4 prefabricated substation delivers a safe, reliable, and durable power solution for high-demand areas like city centers and industrial parks. Designed with standardized components for universal compatibility, it ensures easy operation and maintenance. Key features include an emergency generator connection for rapid power switchover, integrated backflow protection, and reserved space for future DTU automation upgrades. This versatile substation provides a robust and adaptable foundation for modern grid requirements.

    Product Overview and Features

    YBW-12/0.4 prefabricated high and low voltage substation is an innovative power equipment with standardized design. It can provide customized solutions according to the specific needs of users. In accordance with the company's "1135" distribution network operation service management requirements, in order to improve equipment selection standards, improve the quality control system, enhance the durability of distribution network equipment, and highlight the core performance of the equipment, on the basis of safety and reliability, the design follows the principles of safety, reliability, durability, standardization, and universal interchangeability. Within a certain range and a certain period, it is designed and launched based on the principles of safety, reliability, durability, standardization, and universal interchangeability of equipment from different manufacturers, thereby enhancing the convenience of operation and maintenance of box-type substations.
    This flexible design enables the YBW-12/0.4 substation to adapt to diverse application scenarios and meet various power supply needs. The substation is equipped with an emergency power plug that can be connected to a generator, ensuring rapid switchover to emergency power in the event of a main power failure, ensuring continuous and reliable power supply. The YBW-12/0.4 substation also features backflow protection, effectively protecting the power system from equipment damage and safety hazards caused by backflow. The product design reserves space for a DTU (Data Terminal Unit) automation terminal to facilitate future intelligent upgrades. Users can implement intelligent system management based on their actual needs, improving power monitoring and dispatching efficiency.
    YBW (2)
    YBW (1)
    The YBW-12/0.4 prefabricated high- and low-voltage substation is particularly suitable for spacious areas with high power loads, such as city centers, industrial parks, and large commercial complexes. This substation not only meets high-load power supply demands but also represents an indispensable new complete set of equipment for the construction and renovation of urban and rural substations. With its efficient design and flexible configuration, the YBW-12/0.4 substation provides users with safe, stable, and economical power solutions, contributing to the construction and development of modern power systems.

    Model Meaning

    AYB

    Areas of application and environments of use

    Widely used in coal mines, steel mills, hydroelectric power stations,solar photovoltaic projects and other outdoor places.
    1.The surrounding air temperature: the highest temperature+40℃,the lowest degree -25℃;
    2. Relative humidity:
    Daily average relative humidity: ≤95%; daily average water vapor pressure does not exceed 2.2kPa;
    Monthly average relative humidity:≤90%; monthly average water vapor pressure does not exceed 1.8kPa;
    3.Altitude: below 1000m;
    4.Earthquake intensity: no more than 8;
    5.The surrounding air should not be corrosive or combustible gases, water vapor and other obvious pollution sites;
    6.No violent vibration places;
    7.Beyond the GB17467-2010《High-voltage /low-voltage pre-assembled substation》stipulated in the normal conditionsof use, by the user and the company to negotiate.

    Main technical parameters

    Name Unit Standard parameter values
    12kV Ring network cabinet
    High-voltage side wiring method   Terminal type, ring type
    Rated voltage kV 12
    Rated frequency Hz 50
    Rated current A 630(Load switches, circuit breakers)
    Control mechanism   Motorized and manually operated
    Temperature rise test current A 1.1Ir
    Rated industrial frequency 1min withstand voltage (relative to earth) kV 42
    Rated lightning impulse withstand voltage peak (1.2/50μs,relative to earth) short-circuit closing current kV 75
    Rated short-circuit breaking current kA 31.5 (Fuse)
    Rated short-circuit closing current kA 50
    Rated short-time withstand current and duration kA/s  20/3
    Rated peak withstand current kA 50
    Short-time frequency withstand voltage for auxiliary and control circuits kV 2
    Power supply Control loop V DC 48/110/220,AC110/220
    Auxiliary circuit V AC 380/AC 220
    Annual gas leakage rate V/V ≤0.1%
    Transformers
    Rated capacity kVA 400、500、630
    Core Material   Silicon steel sheet
    Rated voltage of high voltage winding kV 10/10.5,Determined with the project unit prior to delivery
    Rated voltage of low voltage winding kV 0.4
    Tap range   ±2x2.5%
    Linkage group   Dyn11
    Frame Circuit Breakers (0.4kV)
    Rated current A 800、1000、1250
    Rated Working Voltage V 400
    Rated insulation voltage V 690
    The number of poles   3P
    Rated operating short-circuit breaking capacity kA 65
    Rated peak withstand current kA 80
    Molded Case Circuit Breakers(0.4kV)
    Rated current A 250、400、630
    Rated Working Voltage V 400
    Rated insulation voltage V 690
    The number of poles   3P
    Rated operating short-circuit breaking capacity kA 50
    Case Requirements
    Overall dimensions (LxWxH) mm 3600x2200x(≤2500)
    Shell material   Stainless steel or GRC
    Protection class   IP33D
    Enclosure level   10

    Leave Your Message