01
YBW Pre-Assembled Substations
Product Overview and Features
YBW-12/0.4 prefabricated high and low voltage substation is an innovative power equipment with standardized design. It can provide customized solutions according to the specific needs of users. In accordance with the company's "1135" distribution network operation service management requirements, in order to improve equipment selection standards, improve the quality control system, enhance the durability of distribution network equipment, and highlight the core performance of the equipment, on the basis of safety and reliability, the design follows the principles of safety, reliability, durability, standardization, and universal interchangeability. Within a certain range and a certain period, it is designed and launched based on the principles of safety, reliability, durability, standardization, and universal interchangeability of equipment from different manufacturers, thereby enhancing the convenience of operation and maintenance of box-type substations.
This flexible design enables the YBW-12/0.4 substation to adapt to diverse application scenarios and meet various power supply needs. The substation is equipped with an emergency power plug that can be connected to a generator, ensuring rapid switchover to emergency power in the event of a main power failure, ensuring continuous and reliable power supply. The YBW-12/0.4 substation also features backflow protection, effectively protecting the power system from equipment damage and safety hazards caused by backflow. The product design reserves space for a DTU (Data Terminal Unit) automation terminal to facilitate future intelligent upgrades. Users can implement intelligent system management based on their actual needs, improving power monitoring and dispatching efficiency.


The YBW-12/0.4 prefabricated high- and low-voltage substation is particularly suitable for spacious areas with high power loads, such as city centers, industrial parks, and large commercial complexes. This substation not only meets high-load power supply demands but also represents an indispensable new complete set of equipment for the construction and renovation of urban and rural substations. With its efficient design and flexible configuration, the YBW-12/0.4 substation provides users with safe, stable, and economical power solutions, contributing to the construction and development of modern power systems.
Model Meaning

Areas of application and environments of use
Widely used in coal mines, steel mills, hydroelectric power stations,solar photovoltaic projects and other outdoor places.
1.The surrounding air temperature: the highest temperature+40℃,the lowest degree -25℃;
2. Relative humidity:
Daily average relative humidity: ≤95%; daily average water vapor pressure does not exceed 2.2kPa;
Monthly average relative humidity:≤90%; monthly average water vapor pressure does not exceed 1.8kPa;
3.Altitude: below 1000m;
4.Earthquake intensity: no more than 8;
5.The surrounding air should not be corrosive or combustible gases, water vapor and other obvious pollution sites;
6.No violent vibration places;
7.Beyond the GB17467-2010《High-voltage /low-voltage pre-assembled substation》stipulated in the normal conditionsof use, by the user and the company to negotiate.
Main technical parameters
| Name | Unit | Standard parameter values | |
| 12kV Ring network cabinet | |||
| High-voltage side wiring method | Terminal type, ring type | ||
| Rated voltage | kV | 12 | |
| Rated frequency | Hz | 50 | |
| Rated current | A | 630(Load switches, circuit breakers) | |
| Control mechanism | Motorized and manually operated | ||
| Temperature rise test current | A | 1.1Ir | |
| Rated industrial frequency 1min withstand voltage (relative to earth) | kV | 42 | |
| Rated lightning impulse withstand voltage peak (1.2/50μs,relative to earth) short-circuit closing current | kV | 75 | |
| Rated short-circuit breaking current | kA | 31.5 (Fuse) | |
| Rated short-circuit closing current | kA | 50 | |
| Rated short-time withstand current and duration | kA/s | 20/3 | |
| Rated peak withstand current | kA | 50 | |
| Short-time frequency withstand voltage for auxiliary and control circuits | kV | 2 | |
| Power supply | Control loop | V | DC 48/110/220,AC110/220 |
| Auxiliary circuit | V | AC 380/AC 220 | |
| Annual gas leakage rate | V/V | ≤0.1% | |
| Transformers | |||
| Rated capacity | kVA | 400、500、630 | |
| Core Material | Silicon steel sheet | ||
| Rated voltage of high voltage winding | kV | 10/10.5,Determined with the project unit prior to delivery | |
| Rated voltage of low voltage winding | kV | 0.4 | |
| Tap range | ±2x2.5% | ||
| Linkage group | Dyn11 | ||
| Frame Circuit Breakers (0.4kV) | |||
| Rated current | A | 800、1000、1250 | |
| Rated Working Voltage | V | 400 | |
| Rated insulation voltage | V | 690 | |
| The number of poles | 3P | ||
| Rated operating short-circuit breaking capacity | kA | 65 | |
| Rated peak withstand current | kA | 80 | |
| Molded Case Circuit Breakers(0.4kV) | |||
| Rated current | A | 250、400、630 | |
| Rated Working Voltage | V | 400 | |
| Rated insulation voltage | V | 690 | |
| The number of poles | 3P | ||
| Rated operating short-circuit breaking capacity | kA | 50 | |
| Case Requirements | |||
| Overall dimensions (LxWxH) | mm | 3600x2200x(≤2500) | |
| Shell material | Stainless steel or GRC | ||
| Protection class | IP33D | ||
| Enclosure level | 10 | ||