ZGS Series Box-Type Substation(10kV U.S.)
Product Overview and Features
The ZGS13-H-/10 series American-style box-type substation is a power equipment with advanced design concepts. Its unique "M"-shaped structure closely connects the substation with high- and low-voltage equipment, forming a unified whole. This integrated design not only improves equipment stability and safety, but also effectively saves installation space, meeting the demand for equipment integration in modern power systems.
With three sides exposed to the air, the substation offers excellent heat dissipation, effectively reducing equipment temperature during operation and extending its service life. Furthermore, the substation's design allows for the separation of high- and low-voltage equipment housings from the main body of the substation, greatly facilitating routine maintenance and overhaul. Users can easily inspect and maintain equipment, reducing maintenance costs.


In terms of core components, the ZGS13-H-/10 series substation utilizes a sheet-type oil tank, no oil pillow, and a fully enclosed S11 series oil-immersed transformer. These designs ensure efficient and safe operation of the transformer. Key components such as the high-voltage bushing, tap changer, oil level indicator, pressure relief valve, and oil drain valve are all installed in a high-voltage compartment on the end plate, ensuring safety and ease of operation. Meanwhile, the low-voltage bushing is installed in a low-voltage compartment on the end plate. This rational layout facilitates observation and operation, allowing users to quickly perform necessary monitoring and adjustments.
The ZGS13-H-/10 series American-style box-type substation has become an ideal choice for urban and rural power construction and transformation with its superior design, good heat dissipation performance and convenient maintenance. It can meet the growing demand for electricity and provide users with a safe and stable power supply.
Model Meaning

Areas of application and environments of use
It is widely used in various public places such as urban power grid renovation, residential neighborhoods, as well as indoor and outdoor places such as factories, mines, hotels, airports,railroads, wharves, highways and so on.
1.The surrounding air temperature: the highest temperature+40℃,the lowest degree -25℃;
2. Relative humidity:
Daily average relative humidity: ≤95%; daily average water vapor pressure does not exceed 2.2kPa;
Monthly average relative humidity:≤90%; monthly average water vapor pressure does not exceed 1.8kPa;
3.Altitude: below 1000m;
4.Earthquake intensity: no more than 8;
5.The surrounding air should not be corrosive or combustible gases, water vapor and other obvious pollution sites;
6.No violent vibration places;
7.Beyond the GB17467-2010《High-voltage /low-voltage pre-assembled substation》stipulated in the normal conditionsof use, by the user and the company to negotiate.
Main technical parameters
| Name | Unit | Standard parameter values | |
| Pre-assembled substations | |||
| Rated voltage | High voltage side | kV | 12 |
| Low voltage side | kV | 0.4. | |
| Transformer rated capacity | kVA | 100,125,160,200,250 315,400,500,630,800,1000 | |
| Pressure regulation without load | ±2x2.5% | ||
| Connection method | △/Yn11 | ||
| Rated insulation level | Lightning impulse withstand voltage (full wave, peak) | kV | 75 |
| Industrial frequency withstand voltage 1min | kV | 35 | |
| Low-voltage side frequency and voltage phase to phase and phase to ground (1min) | Main circuit | kV | 2.5 |
| Control and metering circuits | kV | 2 | |
| Noise level | dB | 50 | |
| Protection class | lp34 | ||
| Cooling method | |||
Load switch
| Load switch | Four-station | Two-station | ||
| Lightning surge withstand voltage (peak, full wave) | Ground-to-ground, interphase | kV | 75 | 75 |
| Isolation Interrup Ground-to-ground,interphase | kV | 85 | 85 | |
| 1min frequency withstand voltage | Ground-to-ground, interphase | kV | 42 | 42 |
| Isolation InterrupGround-to-ground, interphase | kV | 48 | 48 | |
| Rated current | A | 630 | 100 | |
| Rated short-circuit closing current (peak) | kA | 31.5 | 16 | |
| Rated short-time withstand current | kA | 12.5 | 6.3 | |
| Rated short circuit duration | s | 2 | 2 | |
| Rated peak withstand current | kA | 31.5. | 16 | |
| Mechanical life | 次 | 2000 | 2000 | |
| Transition time between main disconnections 0 in the case of division and closure | ms | 16~22/15~20 | 11~15 | |
Fuse
| Capacity(kVA) | Backup protection fuse rated current (A)/opening k (A) | Insertion fuse rated current(A) |
| 100 | 40/40 | 10 |
| 125 | 50/40 | 15 |
| 160 | 63/40 | 25 |
| 200 | 80/40 | 25 |
| 250 | 80/40 | 25 |
| 315 | 80/40 | 25 |
| 400 | 100/40 | 40 |
| 500 | 100/40 | 40 |
| 630 | 125/40 | 65 |
| 800 | 175/40 | 65 |
| 1000 | 200/40 | 100 |