Leave Your Message

ZN28-12 Vacuum Circuit Breaker

ZN28(A)-12 series vacuum circuit breakers are a kind of indoor high voltage switch device which is used in the AC three-phase power system of frequency 50Hz, rated voltage 12kV. This device is conformed to the standard GB1984-89. This device adopts unibody installation of operating mechanism and circuit breaker technology, which has two styles,respectively, 2N28-12 unibody structure and ZN28(A)-12 separable structure. it is suitable to various fixed switchgears, such as GG1A, XGN2A-10, etc.

    Application

    The ZN28(A)-12 series vacuum circuit breaker is a high-voltage switchgear designed specifically for AC three-phase power systems. Its rated voltage is 12kV and is suitable for indoor installation. This device strictly adheres to the GB1984-89 standard to ensure its safety and reliability in power systems. The ZN28(A)-12 series utilizes advanced integrated operating mechanism and circuit breaker installation technology, offering two different structural forms: the integrated 2N28-12 and the separate ZN28(A)-12. These two designs enable the device to flexibly adapt to a variety of application scenarios, particularly compatibility with various fixed switchgear types such as the GG1A and XGN2A-10, further enhancing its application scope and efficiency in power systems.
    The ZN28(A)-12 series vacuum circuit breakers can be used with the CD17 DC electromagnetic operating mechanism and the CT19 and CD19L spring-energy storage operating mechanisms. 
    This flexible combination allows users to select the most appropriate operating mechanism based on specific power system requirements, thereby achieving more efficient power control and protection. Whether in power distribution, equipment protection, or fault isolation, the ZN28(A)-12 series vacuum circuit breakers demonstrate outstanding performance and stability, becoming an indispensable component of modern power systems.

    Outline and Installation Dimension(mm)

    ZN28(A)-12

    Technical Parameter

    Item Unit Value
    Rated voltage kV 12
    Rated current A 630 1000 1250 1250 1600 1250 1600 2000 2500 1600 2500 3150
    Rated short-circuit breaking current KA 20 25 31.5 40
    Rated short-circuit switch off current (virtual value) kA 50 63 80 100
    Rated peak withstand current(peak) kA 50 63 80 100
    Rated thermo stability current(valid) kA 20 25 31.5 40
    Rated thermo stability time s 4
    Rated operations of short-circuit breaking current interruption times 30(50)
    Breaking time CD10 magnetic control mechanism ms <80
    Rated operation sequence   0.3
    Power frequency withstand voltage (1 min) kV 42(fracture 48)
    Impulse withstand voltage kV 75(fracture 85)
    Mechanical life times 10000