ZN85-40.5 Indoor Vacuum Circuit Breaker
Application
The ZN85-40.5G (3AV3) indoor AC high-voltage vacuum circuit breaker is designed for three-phase AC power systems, suitable for applications with a frequency of 50 Hz and a rated voltage of 40.5 kV. This circuit breaker is widely used to protect and control power equipment in industrial and mining enterprises, power plants, substations, and distribution substations, ensuring the safety and stability of power systems. It is also particularly well-suited for locations requiring frequent operation, such as high-load industrial production lines and critical power dispatching centers. With its superior performance and reliability, the ZN85-40.5G (3AV3) circuit breaker can effectively cope with various complex power environments and meet the requirements of modern power systems for efficiency, safety, and intelligence.
Type and Meaning

Service Environment
Environmental temperature is from: -15~40℃;
Environmental humidity:
Daily average relative humidity≤95%
Monthly average relative humidity≤90%
Earthquake intensity≤8
Keep away from such environment as subject to dust, dirt, smog, corrosive of flammable gas,vapor and salt pollution.
Structrue Feature
The arc-extinguish chamber is on the upper part and the mechanism is on the lower part. This structure is convenient for debug.
Complex insulating structure using air and organic material; Compressible dimension and small weight.
Vacuum arc-extinguish chamber of Cutler-Hammer Company (USA) and domestic ZMD are both appli cable for the VCB. Both two kinds of chambers extinguish arc by vertical magnetic field and featuring with low cut-off and good on-off capability with asymmetry.Simple spring operation mechanism is free from maintenance within 10000 times of operations.Lead-screw propeller, easy and stable operation and good self-locking capability.
Outline and Installing Dimensions(mm)


Main technical parameters
| Item | Unit | Value |
| Rated voltage | kV | 40.5 |
| 1 min power frequency withstand voltage (virtual value) | kV | 95 |
| Lighting impulse withstand voltage (peak) | kV | 185 |
| Rated frequency | Hz | 50 |
| Rated current | A | 1250 1600 2000 |
| Rated short-time withstand current | kV | 25 31.5 |
| Rated peak withstand current | kV | 63 80 |
| Rated short circuit duration | S | 4 |
| Rated short-circuit breaking current | kA | 25 31.5 |
| Rated short-circuit making current | kA | 63 80 |
| Rated operating sequence | 0-0.3s-CO-180s-CO | |
| Break time | ms | <80 |
| Rated short-circuit breaking current times | times | 20 |
| Rated breaking current of capacitor bank | A | 630 |
| Rated back-back capacitor bank drop-out current | A | 400 |
| Rated operating voltage | V | -110/~110-220/~220 |
| Mechanical endurance | 10000 |