ZW7-40.5 Outdoor Vacuum Circuit Breaker
Application
ZW7-40.5 series outdoor high voltage vacuum circuit breaker is used at three phase AC 50Hz, rated voltage is 40.5kV outdoor high-voltage electrical equipment,attached the spring operator or electromagnetic actuator can be well controlled electric opening and closing can also be Manaul storage, manually open and close. Design performance meet GB1984-89 <AC high voltage circuit breakers>;national standards, and meet the lEC-56 <high voltage AC circuit breakers> ; international Electro-technical Commission standards.ZW7-40.5 series vacuum circuit breaker is mainly used for outdoor 35kV power transmission system control and protection also applies to urban and rural power distribution networks and industrial and mining enterprises in the normal operation and short circuit protection purposes, The overall structure of the insulator pillar product type, built vacuum interrupter type on the case, porcelain vase for the next pillar case. For frequent operation place. And has good sealing, anti-aging, high pressure, no burning, no explosion, long life, convenient installation and maintenance features.
Type and Meaning

Outline and Installation Dimension (mm)

Technical Parameter
| No. | ltem | Unit | Value | ||
| 1 | Rated voltage | KV | 40.5 | ||
| 2 | Rated current | A | 1600 | ||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Rated short-circuit breaking current(valid) | kA | 20 | 25 | 31.5 |
| 5 | Rated short-circuit making current(peak) | kA | 50 | 63 | 80 |
| 6 | Rated peak withstand current | kA | 50 | 63 | 80 |
| 7 | 4S Rated short time tolerance current | kA | 20 | 25 | 31.5 |
| 8 | 1 min power frequency withstand voltage(valid) | kV | dry-type:95 (wet-type:80) | ||
| 9 | Lightning shock pressure(peak) | kV | 185 | ||
| 10 | Rated operating sequence | Part-0.3S-Joint points-180S-Joint points | |||
| 11 | Rated short open circuit current switch frequency | times | 20 | ||
| 12 | Operating mechanism rated switching voltage | times | 10000 | ||
| 13 | weight | kg | 1000 | ||
Main Mechanical Parameters
| No. | ltem | Unit | Value |
| 1 | Arcing chamber contact clearance | mm | 22±2 |
| 2 | Arcing chamber Super stroke | mm | 5±1 |
| 3 | Phases center distance | mm | 710 |
| 4 | Arcing chamber Contact switching bounce time | ms | ≤5 |
| 5 | Three phase points, closing not synchronism | ms | ≤2 |
| 6 | Average closing speed | m/s | 0.75±0.2 |
| 7 | Average opening speed | m/s | 1.7±0.2 |
| 8 | Closing time | ms | 30~100 |
| 9 | Opening time | ms | 15~60 |
| 10 | Each phase main loop resistance(without CT) | μΩ | ≤100 |
| 11 | Action contact allowed to wear accumulative thickness | mm | 3 |