ZW8-12 Vacuum Circuit Breaker
Application
ZW8-12 series high-voltage vacuum circuit breaker is a kind of outdoor high-voltage switch equipment with 50Hz three-phase alternating current 12Kv rated voltage. it mainly apply to break and close the load current, overload and short-circuit in country power net, city power net and mini-type power system. The general framework of this product adopts the form of three-phase using same box, i.e, put the three-phase arc-extinguishing chamber inside of the metal box. For the SMG material has the advantage of space insulation and grounding insulation, the breaker has perfect performance and high insulation strength.
ZW8-12G is made of ZW8-12 circuit breaker and isolating switch, called the combination of circuit breakers, use for disconnect switches and self-prepare power supply. There are built-in PT and outer PT.
This series of operating mechanism for the CT23-type spring operating mechanism energy storage can be divided into two kinds of electric and manual.
Technical Parameter
| No. | ltem | Unit | Data | |||
| 6.3kA | 12.5kA | 20kA | ||||
| 1 | Rated voltage | kV | 12 | |||
| 2 | Maximum working voltage | kV | 12 | |||
| 3 | Rated current | A | 630 | |||
| 4 | Rated short circuit load dropout current | kA | 6.3 | 12.5 | 20 | |
| 5 | Rated short-circuit making current | kA | 16 | 31.5 | 50 | |
| 6 | Rated peak withstand current | kA | 16 | 31.5 | 50 | |
| 7 | Rated short time 1 min tolerance current | kA | 6.3 | 12.5 | 20 | |
| 8 | Rated insulation level | High-voltage test with working frequency | kV | 42 | ||
| Lightning shock pressure | 75 | |||||
| 9 | Rated operating sequence | Part-0.3S- Joint points -180S-Joint points | ||||
| 10 | Institutions life | times | 10000 | |||
| 11 | Rated short open circuit current switch frequency | times | 30 | |||
| 12 | Operating mechanism rated switching voltage | V | 110,220 | |||
| 13 | Operating mechanism rated points brake current | V | 110,220 | |||
| 14 | Contact clearance | mm | 11±1 | |||
| 15 | Super stroke (contact spring compression length) | mm | 3 | |||
| 16 | Three phase points, closing not synchronism | ms | ≤2 | |||
| 17 | Contact switching bounce time | ms | ≤2 | |||
| 18 | Average opening speed | m/s | 1.0±0.2 | |||
| 19 | Average closing speed | m/s | 0.7±0.15 | |||
| 20 | Opening time | The highest operating voltage | s | 0.015-0.05 | ||
| The minimum operating voltage | 0.03-0.06 | |||||
| 21 | Closing time | s | 0.025-0.05 | |||
| 22 | Each phase main loop resistance | μΩ | 120(≤200) | |||
| 23 | Action contact allowed to wear accumulative thickness | mm | 3 | |||